A Study on Mechanical Durability of Insulating Materials for Dry-type Transformers

被引:0
|
作者
Chen, Baiquan [1 ]
Chen, Sixiang [1 ]
Xia, Yingyi [2 ]
机构
[1] Guangdong Power Grid Co Ltd, Foshan Power Supply Bur, Foshan, Peoples R China
[2] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu, Peoples R China
来源
2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA | 2023年
关键词
dry-type transformer; short-circuit impulse; mechanical tolerance; dielectric performance;
D O I
10.1109/ICPSASIA58343.2023.10294712
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The winding of dry-type transformers is primarily cast with epoxy resin insulation material. During a short-circuit fault, the winding is subjected to a huge short-circuit electromagnetic force, which can cause changes in the insulation performance. This paper investigates the maximum stress of transformers under short-circuit impact based on simulation experiments, and explores the mechanical tolerance performance of epoxy resin insulation materials using this as a basis. Tensile tests have been carried out to demonstrate that the extreme short-circuit electromagnetic stress does not reach the tensile strength limit of epoxy resin insulation materials. Through fatigue testing, it was confirmed that a single short-circuit fault of short duration would not cause epoxy resin to fracture and fail.Furthermore, considering that a short-duration short-circuit impact fault does not result in insulation failure, the dielectric properties of epoxy resin before and after short-circuit impact fatigue degradation have been tested. By comparing the dielectric parameters of epoxy resin specimens before and after degradation, the evolution of electrical insulation performance characteristics caused by changes in the mechanical properties of insulation materials under the stress of dry-type transformer winding has been analyzed. The results show that under short-circuit electromagnetic stress, the complex capacitance and dielectric loss factor of the dielectric material change with the same trend as before degradation, and the maximum dielectric loss factor rises to 103.7% of the value before degradation. The insulation dielectric performance decreases, and this law can provide a reference for the assessment of the life expectancy of dry-type transformers.
引用
收藏
页码:416 / 421
页数:6
相关论文
共 50 条
  • [41] Optimized gap positions for improved leakage impedance in dry-type transformer design
    Dawood, Kamran
    Tursun, Semih
    RESULTS IN ENGINEERING, 2024, 23
  • [42] Investigation on the Action of Eddy Current on Tank Vibration Characteristics in Dry-Type Transformer
    Zhang, Fan
    Ji, Shengchang
    Shi, Yuhang
    Zhu, Lingyu
    IEEE TRANSACTIONS ON MAGNETICS, 2019, 55 (02)
  • [43] Numerical Analysis on the Eddy Current Losses in a Dry-type 3000 KVA Transformer
    Chiv, Han-Chieh
    Pao, Hung-Kang
    Hsieh, Ren-Hong
    Chiu, Yu-Jen
    Jang, Jer-Huan
    5TH INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS ENGINEERING (CPESE 2018), 2019, 156 : 332 - 336
  • [44] An Approach Based on Transfer Learning to Lifetime Degradation Rate Prediction of the Dry-Type Transformer
    Li, Ying
    Zhang, Aimin
    Huang, Jingjing
    Xu, Zhe
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2023, 70 (02) : 1811 - 1819
  • [45] The Evaluation of Thermal endurance of Cast-Resin Dry-Type Transformer Insulation Structure
    Cai, Dingguo
    Tang, Jinquan
    Li, Jianfeng
    2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [46] Sterilization of Dry-Type Transformer Winding by Conducting Short-Circuit Test in Nuclear Power Plant: A Case Study
    Swamynathan K.
    Singadurai A.
    Sivakumar P.
    Journal of The Institution of Engineers (India): Series B, 2022, 103 (1) : 237 - 244
  • [47] Investigation of Causes of Dry-Type Transformer On-Load Tap-Changer Insulation
    Brilinskiy, Andrey S.
    Evdokunin, Georgy A.
    Chudny, Vladimir S.
    Mingazov, Radmir I.
    Ponomarev, Timofey A.
    PROCEEDINGS OF THE 2018 IEEE CONFERENCE OF RUSSIAN YOUNG RESEARCHERS IN ELECTRICAL AND ELECTRONIC ENGINEERING (EICONRUS), 2018, : 591 - 597
  • [48] Simulation Analysis of Dry-Type Transformer Thermal Network Model Considering Fluid Dynamics
    Tang Z.
    Liu X.
    Chen
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2022, 37 (18): : 4777 - 4787
  • [49] Analysis of the Dry-type Transformer Temperature Field Based on Fluid-solid Coupling
    Ding, Xueqian
    Ning, Wang
    PROCEEDINGS OF THE 2012 SECOND INTERNATIONAL CONFERENCE ON INSTRUMENTATION & MEASUREMENT, COMPUTER, COMMUNICATION AND CONTROL (IMCCC 2012), 2012, : 520 - 523
  • [50] Application of the integrated AE and HFCT sensors for online Dry-type Transformer Partial Discharge Monitoring. Case study
    Tikakosol, Kitimasak
    Tanitteerapan, Tanes
    Mungkung, Narong
    PRZEGLAD ELEKTROTECHNICZNY, 2021, 97 (02): : 105 - 111