A Study on Mechanical Durability of Insulating Materials for Dry-type Transformers

被引:0
|
作者
Chen, Baiquan [1 ]
Chen, Sixiang [1 ]
Xia, Yingyi [2 ]
机构
[1] Guangdong Power Grid Co Ltd, Foshan Power Supply Bur, Foshan, Peoples R China
[2] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu, Peoples R China
来源
2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA | 2023年
关键词
dry-type transformer; short-circuit impulse; mechanical tolerance; dielectric performance;
D O I
10.1109/ICPSASIA58343.2023.10294712
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The winding of dry-type transformers is primarily cast with epoxy resin insulation material. During a short-circuit fault, the winding is subjected to a huge short-circuit electromagnetic force, which can cause changes in the insulation performance. This paper investigates the maximum stress of transformers under short-circuit impact based on simulation experiments, and explores the mechanical tolerance performance of epoxy resin insulation materials using this as a basis. Tensile tests have been carried out to demonstrate that the extreme short-circuit electromagnetic stress does not reach the tensile strength limit of epoxy resin insulation materials. Through fatigue testing, it was confirmed that a single short-circuit fault of short duration would not cause epoxy resin to fracture and fail.Furthermore, considering that a short-duration short-circuit impact fault does not result in insulation failure, the dielectric properties of epoxy resin before and after short-circuit impact fatigue degradation have been tested. By comparing the dielectric parameters of epoxy resin specimens before and after degradation, the evolution of electrical insulation performance characteristics caused by changes in the mechanical properties of insulation materials under the stress of dry-type transformer winding has been analyzed. The results show that under short-circuit electromagnetic stress, the complex capacitance and dielectric loss factor of the dielectric material change with the same trend as before degradation, and the maximum dielectric loss factor rises to 103.7% of the value before degradation. The insulation dielectric performance decreases, and this law can provide a reference for the assessment of the life expectancy of dry-type transformers.
引用
收藏
页码:416 / 421
页数:6
相关论文
共 50 条
  • [21] Load capability estimation of dry-type transformers used in PV-systems by employing field measurements
    David L. Alvarez
    Jorge Restrepo
    F. Faria da Silva
    Javier Rosero
    Electrical Engineering, 2021, 103 : 1055 - 1065
  • [22] Hotspot Temperature Prediction of Dry-Type Transformers Based on Particle Filter Optimization with Support Vector Regression
    Sun, Yuanyuan
    Xu, Gongde
    Li, Na
    Li, Kejun
    Liang, Yongliang
    Zhong, Hui
    Zhang, Lina
    Liu, Ping
    SYMMETRY-BASEL, 2021, 13 (08):
  • [23] Load capability estimation of dry-type transformers used in PV-systems by employing field measurements
    Alvarez, David L.
    Restrepo, Jorge
    da Silva, F. Faria
    Rosero, Javier
    ELECTRICAL ENGINEERING, 2021, 103 (02) : 1055 - 1065
  • [24] Dry-Type - vs. - Liquid-Immersed Transformers: Specification Installation and Operational Impact in a Marine Environment
    Wimmer, Jeffrey
    Tanner, M. R.
    Nunn, Tommy
    Kern, Joel
    2011 RECORD OF CONFERENCE PAPERS INDUSTRY APPLICATIONS SOCIETY 58TH ANNUAL IEEE PETROLEUM AND CHEMICAL INDUSTRY CONFERENCE (PCIC), 2011,
  • [25] Hot spot temperature estimation method for dry-type transformers considering heat dissipation characteristics of the insulation layer
    Yin, Xuegong
    Yan, Lidong
    Zhang, Yao
    Wang, Xiaopeng
    Lu, Xuan
    Zhang, Aoyu
    Wang, Yongqiang
    2022 IEEE 6TH ADVANCED INFORMATION TECHNOLOGY, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (IAEAC), 2022, : 1864 - 1868
  • [26] Inter-Turn Breakdown Fault Analysis and Winding Structure Optimisation of Winding of Dry-Type Transformers in Wind Farms
    Pu, Ziheng
    Yu, Xinyun
    Wang, Yaoqiang
    Liu, Hao
    Feng, Zihao
    ENERGIES, 2023, 16 (04)
  • [27] Modeling and experimental validation of dry-type transformers with multiobjective swarm intelligence-based optimization algorithms for industrial application
    Demirdelen, Tugce
    Esenboga, Burak
    Aksu, Inayet Ozge
    Ozdogan, Alican
    Yavuzdeger, Abdurrahman
    Ekinci, Firat
    Tumay, Mehmet
    NEURAL COMPUTING & APPLICATIONS, 2022, 34 (02): : 1079 - 1098
  • [28] Modeling and experimental validation of dry-type transformers with multiobjective swarm intelligence-based optimization algorithms for industrial application
    Tugce Demirdelen
    Burak Esenboga
    Inayet Ozge Aksu
    Alican Ozdogan
    Abdurrahman Yavuzdeger
    Fırat Ekinci
    Mehmet Tümay
    Neural Computing and Applications, 2022, 34 : 1079 - 1098
  • [29] Contributions to the Study of Energy Efficiency in Dry-Type Transformer under Nonlinear Load
    Silva, Danielle Cristinny L.
    Sousa, Renan H.
    Lima, Francisco Kleber A.
    Branco, Carlos Gustavo C.
    2015 IEEE 24TH INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE), 2015, : 456 - 461
  • [30] FEM SIMULATION OF TEMPERATURE FIELD OF DRY-TYPE TRANSFORMER
    Li, Chunhua
    Su, Baoguo
    Zhou, Guangyu
    2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,