A Study on Mechanical Durability of Insulating Materials for Dry-type Transformers

被引:0
|
作者
Chen, Baiquan [1 ]
Chen, Sixiang [1 ]
Xia, Yingyi [2 ]
机构
[1] Guangdong Power Grid Co Ltd, Foshan Power Supply Bur, Foshan, Peoples R China
[2] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu, Peoples R China
来源
2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA | 2023年
关键词
dry-type transformer; short-circuit impulse; mechanical tolerance; dielectric performance;
D O I
10.1109/ICPSASIA58343.2023.10294712
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The winding of dry-type transformers is primarily cast with epoxy resin insulation material. During a short-circuit fault, the winding is subjected to a huge short-circuit electromagnetic force, which can cause changes in the insulation performance. This paper investigates the maximum stress of transformers under short-circuit impact based on simulation experiments, and explores the mechanical tolerance performance of epoxy resin insulation materials using this as a basis. Tensile tests have been carried out to demonstrate that the extreme short-circuit electromagnetic stress does not reach the tensile strength limit of epoxy resin insulation materials. Through fatigue testing, it was confirmed that a single short-circuit fault of short duration would not cause epoxy resin to fracture and fail.Furthermore, considering that a short-duration short-circuit impact fault does not result in insulation failure, the dielectric properties of epoxy resin before and after short-circuit impact fatigue degradation have been tested. By comparing the dielectric parameters of epoxy resin specimens before and after degradation, the evolution of electrical insulation performance characteristics caused by changes in the mechanical properties of insulation materials under the stress of dry-type transformer winding has been analyzed. The results show that under short-circuit electromagnetic stress, the complex capacitance and dielectric loss factor of the dielectric material change with the same trend as before degradation, and the maximum dielectric loss factor rises to 103.7% of the value before degradation. The insulation dielectric performance decreases, and this law can provide a reference for the assessment of the life expectancy of dry-type transformers.
引用
收藏
页码:416 / 421
页数:6
相关论文
共 50 条
  • [1] Optimization of Mechanical Properties of Insulation Materials for Dry-Type Transformers
    Huang, Jing
    Chen, Bangfa
    Li, Woyang
    2023 IEEE/IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA, I&CPS ASIA, 2023, : 184 - 188
  • [2] Design of the Insulating Supports in Medium Voltage Dry-Type Transformers
    Gonzalez, E., V
    Gomez, P.
    Espino-Cortes, F. P.
    2011 ELECTRICAL INSULATION CONFERENCE (EIC), 2011, : 45 - 48
  • [3] Study of useful life of dry-type WTSU transformers
    Etxegarai A.
    Valverde V.
    Eguia P.
    Perea E.
    Renewable Energy and Power Quality Journal, 2020, 18 : 505 - 509
  • [4] HOTTEST SPOT TEMPERATURES IN VENTILATED DRY-TYPE TRANSFORMERS
    PIERCE, LW
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (01) : 257 - 263
  • [5] Analysis of temperature distribution in cast-resin dry-type transformers
    Rahimpour, Ebrahim
    Azizian, Davood
    ELECTRICAL ENGINEERING, 2007, 89 (04) : 301 - 309
  • [6] Analysis of Temperature Distribution in Cast-resin Dry-type Transformers
    Ebrahim Rahimpour
    Davood Azizian
    Electrical Engineering, 2007, 89 : 301 - 309
  • [7] Air temperature effect on thermal models for ventilated dry-type transformers
    Lee, Moonhee
    Abdullah, Hussein A.
    Jofriet, Jan C.
    Patel, Dhiru
    Fahrioglu, Murat
    ELECTRIC POWER SYSTEMS RESEARCH, 2011, 81 (03) : 783 - 789
  • [8] Influence of core window height on thermal characteristics of dry-type transformers
    Dawood, Kamran
    Kul, Seda
    CASE STUDIES IN THERMAL ENGINEERING, 2025, 66
  • [9] Diagnosis of Oscillation and Vibration of Dry-Type Transformers Caused by Harmonic Resonance
    Boonseng, Chongrag
    Boonseng, Rapeepornpat
    Kularbphettong, Kunyanuth
    2020 INTERNATIONAL CONFERENCE ON DIAGNOSTICS IN ELECTRICAL ENGINEERING, DIAGNOSTIKA, 2020, : 231 - 234
  • [10] Analysis of Loss of Life of Dry-Type WTSU Transformers in Offshore Wind Farms
    Etxegarai, Agurtzane
    Valverde, Victor
    Eguia, Pablo
    Perea, Eugenio
    INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2020, 10 (01): : 448 - 455