Study on emergency ventilation strategies for various fire scenarios in a double-island subway station

被引:11
作者
Long, Zeng [1 ]
Zhong, Maohua [1 ]
Chen, Junfeng [1 ]
Cheng, Huihang [1 ]
机构
[1] Tsinghua Univ, Inst Publ Safety Res, Dept Engn Phys, Beijing 100084, Peoples R China
基金
中国国家自然科学基金;
关键词
Subway station; Fire; Ventilation mode; Numerical simulation; SMOKE EXTRACTION STRATEGIES; CONTROL-SYSTEM; TUNNEL FIRE; TRAIN FIRE; OPTIMIZATION; MODE; CONFINEMENT; SIMULATION; EFFICIENCY; MOVEMENT;
D O I
10.1016/j.jweia.2023.105364
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The double-island subway station with complex structure and dense crowds brings about serious fire safety is-sues. Aiming to control fire-induced smoke, numerical simulations were conducted to investigate the emergency ventilation strategies. The numerical model was validated by the reduced-scale model experiments and full-scale experiments. Various ventilation modes were compared under different fire scenarios and platform screen door (PSD) types. The results demonstrated that a reasonable co-work mode of ventilation system was vitally important in preventing smoke dispersion and reducing pollutant concentration. Opening the screen doors was found to be conducive to the joint ventilation in the platform and tunnel under the type of full-height PSD, whereas whether opening the half-height PSD had little influence on ventilation effect. On this basis, the optimal ventilation modes were developed respectively for platform fire, fire inside the carriage and carriage fire, among which the best control measurement for carriage fire was related with the location of the train. Additionally, a reasonable optimization of the ventilation system could further improve the safe environment. This work could provide guidance for emergency response under sudden fire accident, and provide reference for engineer design of ventilation system in the metro stations.
引用
收藏
页数:23
相关论文
共 62 条
[1]   Impact of air intake position on fire dynamics in mechanically ventilated compartment [J].
Acherar, Lahna ;
Wang, Hui-Ying ;
Garo, Jean-Pierre ;
Coudour, Bruno .
FIRE SAFETY JOURNAL, 2020, 118
[2]  
[Anonymous], 2017, 336682017 GBT CHIN N
[3]  
[Anonymous], 2013, Code for Design of Metro
[4]  
[Anonymous], 2016, SFPE Handbook of Fire Protection Engineering, V5th
[5]  
Beijing Urban Construction Design & development Group Co LTD, 2015, FEASIBILITY STUDY RE, P9
[6]  
Bickel J.O., 1996, TUNNEL ENG HDB, Vsecond, P387
[7]   Numerical simulation of different HGV fire scenarios in curved bi-directional road tunnels and safety evaluation [J].
Caliendo, Ciro ;
Ciambelli, Paolo ;
De Guglielmo, Maria Luisa ;
Meo, Maria Grazia ;
Russo, Paola .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2012, 31 :33-50
[8]  
Chen F, 2003, THEOR COMP FLUID DYN, V16, P349, DOI [10.1007/s00162-002-0086-5, 10.1007/S00162-002-0086-5]
[9]   Investigation of the performance of lateral ventilation in subway station fires [J].
Chen, Junfeng ;
Long, Zeng ;
Liu, Chang ;
Cai, Shuang ;
Xu, Bingzhou ;
Cheng, Huihang ;
Zhong, Maohua .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2022, 228
[10]   Fire evacuation strategy analysis in long metro tunnels [J].
Chen, Junfeng ;
Long, Zeng ;
Wang, Liang ;
Xu, Bingzhou ;
Bai, Qinglin ;
Zhang, Yingbin ;
Liu, Chang ;
Zhong, Maohua .
SAFETY SCIENCE, 2022, 147