Study on Development Characteristics of Partial Discharge in Oil-Pressboard Insulation under Constant DC Voltage

被引:1
|
作者
Zhang, Chengjie [1 ]
Li, Yuan [1 ]
Yang, Senhong [1 ]
Li, Ranran [1 ]
机构
[1] Sichuan Univ, Coll Elect Engn, 24 Yihuan Rd, Chengdu 610065, Peoples R China
关键词
oil-pressboard insulation; partial discharge; DC voltage;
D O I
10.3390/en16103970
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The converter transformer is the core equipment of HVDC transmission system, the valve-side winding of which needs to withstand DC voltage. Partial discharge is one of the main threats to the safe operation of converter transformer, yet the characteristics of partial discharge development of the oil-pressboard insulations under constant DC voltage are insufficiently understood. In order to better understand the partial discharge characteristics of the oil-pressboard insulation under DC voltage and provide deeper theoretical support for insulation diagnosis of converter transformers, development characteristics including the time-varying tendency of discharge magnitude and repetition rate of partial discharge in oil-pressboard insulation under constant positive and negative DC voltage were studied. The results indicate that the development of partial discharge in a needle-plane oil-pressboard insulation model under constant DC voltage has three stages: the intensive discharging stage, the silent-burst stage, and the breakdown stage. Throughout all stages, the partial discharge magnitude and repetition rate first decrease and increase afterwards. At the silent-burst stage, the partial discharge appears in the form of a "cluster" with very large magnitude and repetition rate. Each cluster exists for tens of seconds but with at a very long interval with each other. Further analysis shows that the repeated accumulation and dissipation of free charges on the surface of the pressboard cause the above phenomena. Negative charges are easy to accumulate and difficult to dissipate under the same voltage amplitude compared to positive charges, leading to a weaker actual electric field at the needle tip and thus partial discharges under negative DC voltage with a lower magnitude and longer interval.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Study on partial discharge and charge accumulation characteristics of oil-pressboard insulation under DC superimposed harmonic voltage
    Li, Shuqi
    Wang, Qiang
    He, Dongxin
    Wang, Liangkai
    Li, Qingquan
    Si, Wen
    HIGH VOLTAGE, 2023, 8 (06) : 1215 - 1224
  • [2] PD Characteristics of Oil-pressboard Insulation under AC and DC Mixed Voltage
    Li, Junhao
    Han, Xutao
    Liu, Zehui
    Yao, Xiu
    Li, Yanming
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (01) : 444 - 450
  • [3] Characteristics of Creeping Discharge Caused by a Needle Electrode in Oil-Pressboard Insulation under plus DC Voltage
    Li, Simeng
    Liu, Zhihua
    Ji, Shengchang
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (01) : 215 - 222
  • [4] Partial Discharge Characteristics of Fast Developing Discharge in Oil-pressboard Insulation
    Xu Z.
    Yang L.
    Wei Y.
    Cheng L.
    Zhao X.
    Yang X.
    Jiang Y.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (21): : 7529 - 7539
  • [5] Effect of Cellulose Impurities on Partial Discharges in Oil-pressboard Insulation under DC Voltage
    Li, Yuan
    Zhang, Qiaogen
    Ding, Yuqin
    Zhao, Yi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (04) : 2271 - 2273
  • [6] Discharge characteristics of oil-pressboard insulation under impulse voltage waveforms with different parameters
    Wang, Zhe
    Zhang, Qiaogen
    Wang, Tonglei
    Li, Jinzhong
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (06): : 1974 - 1980
  • [7] Characteristics of oil-pressboard insulation under polarity reversal voltage
    Wang, Yonghong
    Wei, Xinlao
    Chen, Qingguo
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2012, 32 (19): : 161 - 168
  • [8] Polarity Characteristics of Accumulated Charge in Oil-pressboard Composite Insulation Under DC Voltage
    Zhuang Y.
    Wang Y.
    Wei X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2022, 42 (23): : 8791 - 8802
  • [9] Influence of Fiber Impurities on DC Partial Discharge Process in Oil-pressboard Insulation
    Li, Yuan
    Zhang, Qiaogen
    Gao, Meng
    Ni, Heli
    Zhao, Yi
    Liu, Guangqi
    Wang, Ke
    2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,
  • [10] Flow Electrification Characteristics of Typical Plane Oil-Pressboard Insulation Under AC/DC Voltage
    Lin, Lin
    Chen, Qingguo
    Chi, Minghe
    Wei, Xinlao
    Zhu, Xuecheng
    Gao, Zhiwei
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 80 - 83