Fire control and self-extinguishment by blocking smoke flow with water spray in a tunnel fire

被引:5
作者
Tanaka, Futoshi [1 ]
Harada, Naoki [1 ]
Yamaoka, Shohei [1 ]
Moinuddin, Khalid A. M. [2 ]
机构
[1] Univ Fukui, 3-9-1 Bunkyo, Fukui, Fukui 9108507, Japan
[2] Victoria Univ, POB 14428, Melbourne, Vic 8001, Australia
基金
日本学术振兴会;
关键词
Modeling; Smoke management; Tunnel fire; Water spray; Smoke blocking; Model experiment; Calorimetry method; VENTILATION; SYSTEM; HEAT;
D O I
10.1016/j.firesaf.2023.103999
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This study clarified the effect of water spray on fire control and extinguishment in a tunnel fire. A series of fire experiments were conducted using a 1:10 scale model tunnel to investigate the performance of water spray for suppressing the fire and blocking the smoke produced by the fire. The water spray trapped the smoke in the fire zone and prevented the inflow of fresh air from the tunnel portal. That is, the water spray sealed off the smoke and compartmentalized it in the tunnel. A calorimetry method was developed to estimate the chemical heat release rate (HRR) in the tunnel with the sealed-off descended smoke. Within the test conditions considered in this study, the following results were obtained. First, self-extinguishment occurred in 86% of the cases tested in the fire zone sealed off by the water spray. Second, the maximum HRR of the vitiated fire induced by the water spray was reduced to one-fifth compared to that during free burning. Finally, a ghosting flame and selfextinguishment by suffocation occurred when the smoke blocking rate exceeded about 60% and 80%, respectively.
引用
收藏
页数:10
相关论文
共 12 条
[1]  
Alpert R.L., 1972, FIRE TECHNOL, V8, P181, DOI [10.1007/BF02590543, DOI 10.1007/BF02590543]
[2]  
Amano Reiko, 2004, 6 AS OC S FIR SCI TE, P17
[3]   Study on smoke blocking and thermal radiation attenuation by water curtain in tunnel fire [J].
Chen, Yinuo ;
Jia, Jinzhang ;
Che, Guangbo ;
Zhu, Zhiheng ;
Shen, Zhiyuan ;
Wu, Yumo .
SCIENTIFIC REPORTS, 2023, 13 (01)
[4]   Model scale tunnel tests with water spray [J].
Ingason, Haukur .
FIRE SAFETY JOURNAL, 2008, 43 (07) :512-528
[5]   Combustion efficiency during fires in tunnels with natural ventilation by vitiated air including descending smoke [J].
Ishikawa, Tasuku ;
Kasumi, Keita ;
Tanaka, Futoshi ;
Moinuddin, Khalid A. M. .
FIRE SAFETY JOURNAL, 2021, 120
[6]   Experimental study of the effectiveness of a water mist segment system in blocking fire-induced smoke and heat in mid-scale tunnel tests [J].
Li, Qi ;
Tang, Zhi ;
Fang, Zheng ;
Yuan, Jianping ;
Wang, Junheng .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2019, 88 :237-249
[7]   Numerical studies on the smoke control by water mist screens with transverse ventilation in tunnel fires [J].
Liang, Qiang ;
Li, Yangfeng ;
Li, Junmei ;
Xu, Hui ;
Li, Kaiyuan .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2017, 64 :177-183
[8]   Large eddy simulation of smoke blocking by water sprays in a tunnel fire [J].
Nishino, Ryo ;
Ren, Ning ;
Noda, Yuki ;
Tanaka, Futoshi .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2022, 121
[9]  
Parker W.J., 1982, NBSIR 81-2427- 1
[10]   Experimental study of the effectiveness of a water system in blocking fire-induced smoke and heat in reduced-scale tunnel tests [J].
Sun, Jiayun ;
Fang, Zheng ;
Tang, Zhi ;
Beji, Tarek ;
Merci, Bart .
TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2016, 56 :34-44