Reliable Assessment of Oil-Paper Insulation Used in Power Transformer Using Concise Dielectric Response Measurement

被引:5
|
作者
Mishra, Deepak [1 ]
Baral, Arijit [2 ]
Chakravorti, Sivaji [3 ]
机构
[1] Indian Maritime Univ, Dept Elect Engn, Kolkata 700043, India
[2] Indian Inst Technol, Indian Sch Mines, Dept Elect Engn, Dhanbad 826004, India
[3] Jadavpur Univ, Dept Elect Engn, Kolkata 700032, India
关键词
Mathematical models; Power transformer insulation; Current measurement; Dielectric measurement; Oil insulation; Dielectrics; Conductivity; Conductivity measurement; dielectric measurement; dielectrics; insulation; moisture content; power transformers; time-domain analysis; EFFECTIVE DIAGNOSIS; FREQUENCY-DOMAIN; TIME; CONDUCTIVITY; SPECTROSCOPY; DURATION; PART;
D O I
10.1109/TDEI.2023.3261824
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oil-impregnated paper is usually the preferred choice of insulation in power transformers. The working life of any transformer depends on its insulation condition. The paper conductivity, moisture content, and dissipation factor of solid insulation are a few crucial parameters used to determine the insulation condition. The reliable estimation of such parameters for the diagnosis of solid insulation requires a complete profile of polarization current, which is time-consuming. Hence, utilities always prefer noninvasive and rapid techniques to predict insulation conditions and minimize shutdown time. The proposed technique is based on short-duration polarization current data. The present manuscript suggested a method that uses the initial decay rate (IDR) of recorded polarization current data to predict various performance parameters related to paper insulation. In order to show the effectiveness of the proposed method, the analysis is performed on the data measured from various in situ transformers.
引用
收藏
页码:1255 / 1264
页数:10
相关论文
共 50 条
  • [31] Influence of Temperature and Moisture on the Dielectric Response of Oil-Paper Insulation System
    Provencher, H.
    Noirhomme, B.
    David, E.
    2008 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2008, : 667 - +
  • [32] Time domain measurements of dielectric response in oil-paper insulation systems
    DerHouhanessian, V
    Zaengl, WS
    CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 47 - 52
  • [33] Research on Life Prediction of Oil-Paper Insulation Based on Dielectric Response
    Liu, Ji
    Lv, Jialu
    Zhang, Mingze
    Jia, Haifeng
    Zhuang, Weitao
    Chen, Xin
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2020, 48 (03) : 281 - 290
  • [34] Method for predicting lifetime of oil-paper insulation based on dielectric response
    Liu J.
    Lü J.-L.
    Zhang M.-Z.
    Chi M.-H.
    Qi P.-S.
    Chen X.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2021, 25 (02): : 82 - 89
  • [35] Influence of the copper ion on aging rate of oil-paper insulation in a power transformer
    Liao, R. -J.
    Tang, C.
    Yang, L. -J.
    Feng, Y.
    Sun, C. -X.
    IET ELECTRIC POWER APPLICATIONS, 2009, 3 (05) : 407 - 412
  • [36] On the Frequency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures
    Fofana, I.
    Hemmatjou, H.
    Meghnefi, F.
    Farzaneh, M.
    Setayeshmehr, A.
    Borsi, H.
    Gockenbach, E.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) : 799 - 807
  • [37] Investigating the Impacts of Temperature on the Dielectric Response of Oil-paper Insulation System
    Peng, Hua-dong
    Dong, Ming
    Ren, Ming
    Wei, Jian-lin
    Miao, Jin
    Wu, Xue-zhou
    PROCEEDINGS OF 2011 INTERNATIONAL CONFERENCE ON ELECTRICAL INSULATING MATERIALS (ISEIM), 2011, : 233 - 236
  • [38] Aging and moisture evaluation characteristic parameters for oil-paper insulation of transformer using frequency dielectric spectroscopy
    Wang, Youyuan
    Gao, Jun
    Liu, Jiefeng
    Zhang, Yiyi
    Hao, Jian
    Ma, Zhiqin
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2015, 30 (22): : 215 - 221
  • [39] The Influence of Organic Acid on Thermal Aging of Power Transformer Oil-paper Insulation
    Cui Yunguang
    Wu Guangning
    Wang Xiaojian
    Peng Qian
    Chen Ling
    Gao Bo
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 116 - 119
  • [40] Application of molecular simulation in transformer oil-paper insulation
    Xiao, Xia
    Yang, Wenyan
    Li, Linduo
    Zhong, Tingting
    Zhang, Xiaolin
    JOURNAL OF ENGINEERING-JOE, 2019, (16): : 1324 - 1327