Electromagnetic and Mechanical Characteristics of Transformer under Multiple Short-Circuit Impacts

被引:5
作者
Lin, Xiaoqing [1 ]
Liu, Jun [1 ,2 ]
Wang, Feng [1 ]
Chen, She [1 ]
Ai, Wenhao [1 ]
Zhong, Lipeng [1 ]
Sun, Qiuqin [1 ]
机构
[1] Hunan Univ, Coll Elect & Informat Engn, Changsha, Peoples R China
[2] Guizhou Power Grid Co Ltd, Elect Power Res Inst, Guiyang, Peoples R China
基金
中国国家自然科学基金;
关键词
electromagnetic and mechanical characteristics; electromagnetic-mechanical field coupled method; short-circuit impacts; cumulative effects; power transformer;
D O I
10.1002/tee.23826
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The short-circuit withstand capability of the transformer is crucial to the reliability of power systems. Research on the short-circuit characteristics of windings is the basis for improving the stability of power transformers. Although many studies focus on electromagnetic force and cumulative deformation of two-winding transformers, there is a lack of careful comparison of the electromagnetic and mechanical characteristics of three-winding transformers, as well as the cumulative effect of stress, displacement and strain. In this paper, the model is established to study temporal response and spatial distribution of the electromagnetic and mechanical properties under short-circuit impacts. The results show that the short-circuit effects on medium and low-voltage windings are more severe than on high-voltage windings. The first current peak will lead to the greatest threat. Second, the influences of iron core and pre-stress on short-circuit characteristics are investigated. The characteristics of windings differ between inside and outside the iron core window, which is pronounced for high-voltage winding. Besides, the greater pre-stress is not better for the stability of windings. Finally, it is found that the residual stress and displacement continue to accumulate and the plastic strain appears under multiple short-circuit impacts. This work is helpful for the analysis of short-circuit withstand capability of transformers. (C) 2023 Institute of Electrical Engineer of Japan and Wiley Periodicals LLC.
引用
收藏
页码:1095 / 1103
页数:9
相关论文
共 45 条
  • [21] Short-circuit and load operation of single-phase transformer at low frequencies
    Koprivica, Branko
    Chwastek, Krzysztof
    Milunovic Koprivica, Sandra
    PRZEGLAD ELEKTROTECHNICZNY, 2019, 95 (07): : 21 - 24
  • [22] Dynamic Deformation Analysis of Power Transformer Windings in Short-Circuit Fault by FEM
    Zhang, Haijun
    Yang, Bin
    Xu, Weijie
    Wang, Shuhong
    Wang, Guolin
    Huangfu, Youpeng
    Zhang, Jingyin
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2014, 24 (03)
  • [23] Finite Element Analysis of Short Circuit Electromagnetic Force in Power Transformer
    Lee, J. Y.
    Ahn, H. M.
    Kim, J. K.
    Oh, Y. H.
    Hahn, S. C.
    2009 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-3, 2009, : 468 - +
  • [24] On-line identification of power transformer short-circuit parameters based on instantaneous phasor
    Han, Meiyu
    Zhao, Rende
    Zhang, Yunjian
    Zhang, Yinqing
    IET ELECTRIC POWER APPLICATIONS, 2023, 17 (08) : 1101 - 1110
  • [25] A 3D-coupled field-circuit model for analyzing the internal short-circuit faults of power transformer
    Hu, Guozhao
    Wu, Xixiu
    Long, Fei
    Wu, Shipu
    Lecture Notes in Electrical Engineering, 2015, 334 : 55 - 64
  • [26] Research on the application of transformer vibration model in the detection of turn-to-turn short-circuit fault
    Wu, Xutao
    Yan, Zhenhua
    Ji, Shengchang
    ADVANCES IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2013, 614-615 : 1332 - +
  • [27] Analysis of Physical Characteristics of Power Transformer Windings Under Inter-turn Short Circuit Fault
    Zhang B.
    Xian R.
    Yu Y.
    Xie T.
    Gao H.
    Chen L.
    Gaodianya Jishu/High Voltage Engineering, 2021, 47 (06): : 2177 - 2185
  • [28] Investigating Short-circuit in Power Transformer Winding with Quasi-static Finite Element Analysis and Circuit-based Model
    Barzegaran, M. R.
    Mirzaie, M.
    Akmal, A. Shayegani
    2010 IEEE PES TRANSMISSION AND DISTRIBUTION CONFERENCE AND EXPOSITION: SMART SOLUTIONS FOR A CHANGING WORLD, 2010,
  • [29] A Practical Example of Power Transformer Unit Winding Condition Assessment by Means of Short-Circuit Impedance Measurement
    Chiulan, Traian
    Pantelimon, Brandusa
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 2983 - +
  • [30] Analysis of Three-Phase Power Transformer Windings Forces Caused by Magnetic Inrush and Short-Circuit Currents
    Li, Hongkui
    Li, Yan
    Sun, Xi
    Li, Dongxu
    Jing, Youteng
    2009 INTERNATIONAL CONFERENCE ON APPLIED SUPERCONDUCTIVITY AND ELECTROMAGNETIC DEVICES, 2009, : 229 - +