An Islanding Detection Method Based on the Reactive Power Disturbance for Multiple Inverter-Based DG Systems

被引:6
作者
Peng, Te [1 ]
Bai, Chenxi [1 ]
Song, Xuan [1 ]
Duan, Shanxu [1 ]
机构
[1] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan 430074, Peoples R China
关键词
Distributed generation (DG); disturbance synchronization; islanding detection; positive feedback of frequency difference; weak grid; FREQUENCY-SHIFT; FUTURE;
D O I
10.1109/TIE.2023.3274875
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this article, an islanding detection method for multiple inverter-based distributed generation systems is proposed, which is based on perturbing reactive power output. An asymmetric form of positive and negative reactive power disturbance (RPD) is presented so that there always exists a certain total amount of disturbance in the system. To decrease the disturbance amplitude without expanding the nondetection zone (NDZ), a positive feedback of frequency difference is added to the disturbance. A RPD synchronization method without communication among inverters is proposed so that the averaging effect caused by unsynchronized reactive disturbances can be eliminated and the island can be detected in a multiple distributed generator (DG) system. In addition, the islanding detection criterion is improved by establishing the relationship between the direction of disturbance and the numerical symbol of frequency difference, so there is no misjudgment of islanding detection in a weak grid. Finally, an experimental platform consisting of three 6kW three-phase grid-connected inverters and a 99.9 kVA islanding detection test device is established. The experimental and simulation results indicate that the proposed method performs fast and precise islanding detection for the multiple-DG system with small NDZ and little impact on power quality. Additionally, no misjudgment happens in a weak grid.
引用
收藏
页码:3253 / 3263
页数:11
相关论文
共 31 条
  • [1] [Anonymous], 2000, 9292000 IEEE, DOI DOI 10.1109/IEEESTD.2000.91304
  • [2] [Anonymous], 2014, IEC 62116: 2014
  • [3] Two-Level Islanding Detection Method for Grid-Connected Photovoltaic System-Based Microgrid With Small Non-Detection Zone
    Bakhshi-Jafarabadi, Reza
    Sadeh, Javad
    Chavez, Jose de Jesus
    Popov, Marjan
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2021, 12 (02) : 1063 - 1072
  • [4] Maximum Power Point Tracking Injection Method for Islanding Detection of Grid-Connected Photovoltaic Systems in Microgrid
    Bakhshi-Jafarabadi, Reza
    Sadeh, Javad
    Popov, Marjan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (01) : 168 - 179
  • [5] A Statistical Features Based Generic Passive Islanding Detection Scheme for IIDGs System
    Bansal, Yashasvi
    Sodhi, Ranjana
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (04) : 3176 - 3188
  • [6] The future of electronic power processing and conversion
    Blaabjerg, F
    Consoli, A
    Ferreira, JA
    van Wyk, JD
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2005, 20 (03) : 715 - 720
  • [7] Overview of control and grid synchronization for distributed power generation systems
    Blaabjerg, Frede
    Teodorescu, Remus
    Liserre, Marco
    Timbus, Adrian V.
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2006, 53 (05) : 1398 - 1409
  • [8] An Advanced Signal Decomposition Technique for Islanding Detection in DG System
    Chaitanya, Bokka Krishna
    Yadav, Anamika
    Pazoki, Mohammad
    [J]. IEEE SYSTEMS JOURNAL, 2021, 15 (03): : 3220 - 3229
  • [9] A Novel Hybrid Islanding Detection Method for Grid-Connected Microgrids With Multiple Inverter-Based Distributed Generators Based on Adaptive Reactive Power Disturbance and Passive Criteria
    Chen, Xiaolong
    Li, Yongli
    Crossley, Peter
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2019, 34 (09) : 9342 - 9356
  • [10] An Islanding Detection Method for Inverter-Based Distributed Generators Based on the Reactive Power Disturbance
    Chen, Xiaolong
    Li, Yongli
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (05) : 3559 - 3574