A modelling study on the frosting characteristics of a novel dual-fan outdoor coil in an Air Source Heat Pump unit

被引:6
作者
Bai, Xiaoxia [1 ]
Liu, Shengnan [1 ]
Deng, Shiming [2 ]
Zhang, Long [3 ]
Wei, Minchen [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Hong Kong, Peoples R China
[2] Qatar Univ, Dept Mech & Ind Engn, POB 2713, Doha, Qatar
[3] Beijing Inst Technol, Sch Mech Engn, Dept Energy & Power Engn, Beijing, Peoples R China
关键词
Air source heat pump; Novel dual -fan outdoor coil; Dynamic mathematical model; Even frosting characteristics; Heating performances; PERFORMANCE; GROWTH; EXCHANGER; FLOW; FIN; TEMPERATURE; PREDICTION; DEFROST;
D O I
10.1016/j.applthermaleng.2022.119933
中图分类号
O414.1 [热力学];
学科分类号
摘要
Uneven frosting along the airflow direction in a traditional outdoor coil in air source heat pumps (ASHPs) was inevitable due to a fixed one-way outdoor airflow direction, causing a rapid deterioration in heating performances of ASHPs. To alleviate this uneven frosting phenomenon, a novel dual-fan outdoor coil where air flow direction can be alternately reversed was proposed in a previous experimental study. To more effectively and comprehensively study the operating characteristics of ASHPs having the dual-fan outdoor coil at different fan operating modes, with different configurations and under different operating ambient conditions, a dynamic mathematical model for the experimental ASHP having the dual-fan outdoor coil was developed and experimentally validated. Then a follow-up modelling study for different operating modes of the two fans, fin pitches and operating ambient conditions was carried out using the validated model. The modelling results demonstrated that by optimizing fan operating mode, the difference in frost thickness between the windward and leeward sides of the dual-fan outdoor coil can be reduced by up to 77.3 %, the averaged output heating capacity and COP improved by up to 11.1 % and 12.7 %, respectively, and the number of switching operation of the two fans decreased by 55.6 %. Besides, the recommendations for using the dual-fan outdoor coil at different operating modes of the two fans, different fin pitches and operating ambient conditions were also made. The model can be used as a useful tool in helping achieve higher operating efficiency for ASHPs having the novel dual-fan outdoor coil.
引用
收藏
页数:13
相关论文
共 37 条
  • [1] An experimental study on achieving even-frosting for an air source heat pump using a novel dual-fan outdoor coil
    Bai, Xiaoxia
    Liu, Shengnan
    Deng, Shiming
    Zhang, Long
    Wei, Minchen
    [J]. ENERGY AND BUILDINGS, 2022, 255
  • [2] Operating performances of an ASHP unit operated in a mild and humid region using tube-encircled photoelectric sensor based defrosting initiation strategy
    Bai, Xiaoxia
    Wang, Wei
    Sun, Yuying
    Liu, Jingdong
    Ge, Yijing
    Deng, Shiming
    [J]. ENERGY AND BUILDINGS, 2018, 177 : 140 - 153
  • [3] Bound J., 2001, Handbook of econometrics, V5, P3705, DOI [10.1016/S1573-4412(01)05012-7, DOI 10.1016/S1573-4412(01)05012-7]
  • [4] Frosting modeling on a cold flat plate: Comparison of the different assumptions and impacts on frost growth predictions
    Breque, Florent
    Nemer, Maroun
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 69 : 340 - 360
  • [5] Carlson D.M., 2001, Deposition, distribution, and effects of frost on a multi-row heat exchanger performance
  • [6] Development of a steady-state physical-based mathematical model for a direct expansion based enhanced dehumidification air conditioning system
    Chen, Wenjing
    Chan, Ming-yin
    Weng, Wenbing
    Yan, Huaxia
    Deng, Shiming
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 91 : 55 - 68
  • [7] Defrosting performances of a multi-split air source heat pump with phase change thermal storage
    Dong, Jiankai
    Li, Shuo
    Yao, Yang
    Jiang, Yiqiang
    Tian, Yu
    Tian, Hao
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 55 : 49 - 59
  • [8] Experimental study on frost growth and dynamic performance of air source heat pump system
    Guo, Xian-Min
    Chen, Yi-Guang
    Wang, Wei-Hua
    Chen, Chun-Zheng
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (17-18) : 2267 - 2278
  • [9] Hayashi Y., 1976, T JAPAN SOC MECH ENG, V40, P885
  • [10] A semi-empirical model for predicting frost accretion on hydrophilic and hydrophobic surfaces
    Hermes, Christian J. L.
    Sommers, Andrew D.
    Gebhart, Colton W.
    Nascimento, Valter S., Jr.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 87 : 164 - 171