Investigation of thermal comfort conditions by heat pump Hybridized with phase change Material-based solar desiccant cooling system

被引:9
|
作者
Bozorgi, Mehran [1 ]
Ghasemi, Kasra [1 ]
Tasnim, Syeda Humaira [1 ]
Mahmud, Shohel [1 ]
机构
[1] Univ Guelph, Sch Engn, Guelph, ON, Canada
关键词
Desiccant cooling; Solar energy; Phase change material; Thermal comfort condition; Heat pump; ENERGY; AIR; PERFORMANCE; WHEEL; PCM;
D O I
10.1016/j.applthermaleng.2023.121097
中图分类号
O414.1 [热力学];
学科分类号
摘要
In response to the challenge of providing energy-efficient thermal comfort in hot and high-humidity cities, this study investigates innovative cooling systems that can mitigate issues of overcooling and excessive energy consumption seen in conventional air conditioning systems. Also, conventional cooling systems contribute to global warming by emitting high levels of greenhouse gases. In this research, two systems Phase Change Material (PCM)-based Solar Desiccant Cooling System (PSDC) and Heat Pump Hybridized with a PCM-based Solar Desiccant Cooling System (HP-PSDC) were investigated for a typical residential house located in Doha (Qatar), Vancouver and Toronto (Canada), and Bangkok (Thailand). According to the findings, the PSDC system provides thermal comfort conditions in Vancouver and Toronto with COP of 1.05 and 1.44, respectively. While in Doha and Bangkok, the innovative system that is HP-PSDC system has better performance when the COP (Coefficient of Performance) of the former is 4.98 and the latter is 4.5. The novelty of this work lies in the approach to balancing thermal comfort conditions with energy consumption. Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) were determined to set design criteria for the selection of the proper system based on the weather conditions of each city by using Design of Experiment (DOE) analysis. According to DOE, the dry bulb temperature, the wet bulb temperature, and the absolute humidity of the ambient air are three key characteristics that must be considered when choosing the appropriate system to provide thermal comfort conditions. It was found that if the wet bulb temperature of the building location is more than 21.5 degrees C, utilizing the HP-PSDC system can guarantee thermal comfort condition. However, for wet bulb temperatures less than 18.5 degrees C, the PSDC system is recommended. This research presents implications for the design of sustainable cooling systems, offering energy efficiency improvements and climate-specific system selection guidelines.
引用
收藏
页数:14
相关论文
共 50 条
  • [31] Performance assessment of phase change material-based thermal energy storage
    Rajan, Abhinav
    Gan, Yixiang
    Reddy, K. S.
    JOURNAL OF ENERGY STORAGE, 2024, 87
  • [32] Effectiveness of the phase change material-based thermal energy storage integrated with the conventional cooling systems of the buildings - A review
    Waqas, Adeel
    Ji, Jie
    Ali, Majid
    Alvi, Jahan Zeb
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART A-JOURNAL OF POWER AND ENERGY, 2018, 232 (06) : 735 - 766
  • [33] A phase change material-based constructal design finned heat sink: An evolutionary design for thermal management
    Arshad, Adeel
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2025, 161
  • [34] Experimental investigation on a novel heat pump system based on desiccant coated heat exchangers
    Hua, L. J.
    Jiang, Y.
    Ge, T. S.
    Wang, R. Z.
    ENERGY, 2018, 142 : 96 - 107
  • [35] Thermal performance of phase change material-based heat sink with hybrid fin-metal foam structure under hypergravity conditions
    Ding, Chen
    Shan, Yijiao
    Nie, Qing
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2022, 46 (05) : 5811 - 5827
  • [36] Experimental Investigations on Effect of Orientation on Thermal Performance of a Novel Phase Change Material-Based Heat Sink
    Shankar, Ch Ravi
    Naresh, Y.
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2023, 15 (09)
  • [37] Experimental investigation on phase change material based thermal storage system for solar air heating applications
    Esakkimuthu, S.
    Hassabou, Abdel Hakim
    Palaniappan, C.
    Spinnler, Markus
    Blumenberg, Jurgen
    Velraj, R.
    SOLAR ENERGY, 2013, 88 : 144 - 153
  • [38] Research on the thermal performance of electronic cooling system using phase change material (PCM)-Based heat sinks
    Guo, C. X.
    Huang, Y. H.
    Wei, X. L.
    2008 PROCEEDINGS OF INFORMATION TECHNOLOGY AND ENVIRONMENTAL SYSTEM SCIENCES: ITESS 2008, VOL 1, 2008, : 456 - 460
  • [39] Application of phase change material in solar assisted ground-source heat pump system
    Wang, Fang
    Zheng, Maoyu
    Li, Zhongjian
    Lei, Bangwei
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2006, 27 (12): : 1231 - 1234
  • [40] Energy and exergy performance of an integrated desiccant cooling system with photovoltaic/thermal using phase change material and maisotsenko cooler
    Song, Jiyun
    Sobhani, Behnam
    JOURNAL OF ENERGY STORAGE, 2020, 32