Liquid desiccant-based deep dehumidifier working with a novel ionic liquid: Prediction model and performance comparison

被引:11
作者
Cao, Bowen [1 ]
Yin, Yonggao [1 ,2 ]
Zhang, Fan [1 ]
Ji, Qiang [1 ]
Chen, Wanhe [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
[2] Minist Educ, Engn Res Ctr Bldg Energy Environm & Equipments, Beijing, Peoples R China
关键词
Liquid desiccant; Deep dehumidification; Ionic liquids; Moisture transfer characteristics; Prediction model; Performance comparison; VAPOR-PRESSURE MEASUREMENT; MASS-TRANSFER COEFFICIENTS; AIR; HEAT; CYCLE; LIBR;
D O I
10.1016/j.ijrefrig.2022.09.033
中图分类号
O414.1 [热力学];
学科分类号
摘要
Deep dehumidification system with energy conservation and stable operation is expected to be used in industrial occasions with low-humidity environment. Compared with solid desiccant dehumidification, liquid desiccant -based dehumidification is a promising alternative because of its advantages of continuous operation and low regeneration temperature. However, corrosion and crystallization problems exist with liquid desiccant-based deep dehumidifier (LDDD) using salt solutions. In this work, LDDD using a novel ionic liquid (IL) was intro-duced, and the heat and moisture transfer model was established based on the finite difference method. Meanwhile, the moisture transfer characteristics were numerically simulated under different operating param-eters (i.e., inlet humidity ratio wa,in, air velocity va, solution mass concentration X, solution temperature ts and solution volume flow Vs). Besides, the significance of various factors and their interactions were analyzed based on response surface methodology. The numerical model is validated against the experiment of the LDDD test bench with a relative deviation of 3%-8%. Numerical results show that the LDDD using IL can achieve deep air dehumidification, and outlet humidity ratio of less than 4 g/kgda is possible. In particular, the order of signifi-cance for influencing factors of outlet humidity ratio is: wa,in > X > ts > va > Vs. Moreover, it is found that dehumidification rate of 60% LiBr solution (saturated state) is less than that of 90% IL. This study establishes a prediction model of moisture transfer between IL and air under the coupling of multiple physical fields, and provides guidance for the application of LDDD using ILs.
引用
收藏
页码:74 / 87
页数:14
相关论文
共 40 条
[1]   Experimental study on heat and mass transfer characteristics between a novel ionic liquid and air under low-humidity conditions [J].
Cao, Bowen ;
Yin, Yonggao ;
Zhang, Fan ;
Tong, Shoubao ;
Che, Chunwen ;
Chen, Wanhe ;
Ji, Qiang ;
Xu, Guoying ;
Li, Xiao .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 198
[2]   A novel drift eliminator enhanced by Voronoi-based porous foam applied to liquid desiccant system: Separation performance and preliminary design [J].
Cao, Bowen ;
Yin, Yonggao ;
Zhao, Xingwang ;
Qian, Fuping .
BUILDING AND ENVIRONMENT, 2022, 216
[3]   Performance comparison on different liquid desiccants in the liquid desiccant air-conditioning using electrodialysis regeneration: LiCl and LiBr aqueous solutions [J].
Cheng, Qing ;
Pei, Wang .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 107 :1-10
[4]   Experimental study and performance analysis on a new dehumidifier with outside evaporative cooling [J].
Cheng, Xiaosong ;
Peng, Donggen ;
Yin, Yonggao ;
Xu, Shaohua ;
Luo, Danting .
BUILDING AND ENVIRONMENT, 2019, 148 :200-211
[5]   Ionic liquid-based hybrid absorption cycle for water heating, dehumidification, and cooling [J].
Chugh, Devesh ;
Gluesenkamp, Kyle ;
Abdelaziz, Omar ;
Moghaddam, Saeed .
APPLIED ENERGY, 2017, 202 :746-754
[6]   Cascade deep air dehumidification with integrated direct-contact cooling and liquid desiccant absorption [J].
Fang, Song ;
Xu, Zhuoren ;
Zhou, Xia ;
Zhang, Hanwei ;
Zhi, Xiaoqin ;
Qiu, Limin ;
Wang, Kai .
ENERGY CONVERSION AND MANAGEMENT, 2022, 268
[7]   Toward Advanced Ionic Liquids. Polar, Enzyme-friendly Solvents for Biocatalysis [J].
Gorke, Johnathan ;
Srienc, Friedrich ;
Kazlauskas, Romas .
BIOTECHNOLOGY AND BIOPROCESS ENGINEERING, 2010, 15 (01) :40-53
[8]   Review of internally cooled liquid desiccant air dehumidification: Materials, components, systems, and performances [J].
Guan, Bowen ;
Zhang, Tao ;
Liu, Jun ;
Liu, Xiaohua ;
Yin, Yonggao .
BUILDING AND ENVIRONMENT, 2022, 211
[9]   Exergy analysis on optimal desiccant solution flow rate in heat exchanger for air dehumidification using liquid desiccant [J].
Guan, Bowen ;
Liu, Xiaohua ;
Zhang, Tao .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 128 :129-138
[10]   On the importance of air-solution flow rate matching in liquid-desiccant deep-dehumidification system [J].
Guan, Bowen ;
Liu, Xiaohua ;
Zhang, Tao .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 164