Liquid desiccant-based deep dehumidifier working with a novel ionic liquid: Prediction model and performance comparison

被引:10
|
作者
Cao, Bowen [1 ]
Yin, Yonggao [1 ,2 ]
Zhang, Fan [1 ]
Ji, Qiang [1 ]
Chen, Wanhe [1 ]
机构
[1] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
[2] Minist Educ, Engn Res Ctr Bldg Energy Environm & Equipments, Beijing, Peoples R China
关键词
Liquid desiccant; Deep dehumidification; Ionic liquids; Moisture transfer characteristics; Prediction model; Performance comparison; VAPOR-PRESSURE MEASUREMENT; MASS-TRANSFER COEFFICIENTS; AIR; HEAT; CYCLE; LIBR;
D O I
10.1016/j.ijrefrig.2022.09.033
中图分类号
O414.1 [热力学];
学科分类号
摘要
Deep dehumidification system with energy conservation and stable operation is expected to be used in industrial occasions with low-humidity environment. Compared with solid desiccant dehumidification, liquid desiccant -based dehumidification is a promising alternative because of its advantages of continuous operation and low regeneration temperature. However, corrosion and crystallization problems exist with liquid desiccant-based deep dehumidifier (LDDD) using salt solutions. In this work, LDDD using a novel ionic liquid (IL) was intro-duced, and the heat and moisture transfer model was established based on the finite difference method. Meanwhile, the moisture transfer characteristics were numerically simulated under different operating param-eters (i.e., inlet humidity ratio wa,in, air velocity va, solution mass concentration X, solution temperature ts and solution volume flow Vs). Besides, the significance of various factors and their interactions were analyzed based on response surface methodology. The numerical model is validated against the experiment of the LDDD test bench with a relative deviation of 3%-8%. Numerical results show that the LDDD using IL can achieve deep air dehumidification, and outlet humidity ratio of less than 4 g/kgda is possible. In particular, the order of signifi-cance for influencing factors of outlet humidity ratio is: wa,in > X > ts > va > Vs. Moreover, it is found that dehumidification rate of 60% LiBr solution (saturated state) is less than that of 90% IL. This study establishes a prediction model of moisture transfer between IL and air under the coupling of multiple physical fields, and provides guidance for the application of LDDD using ILs.
引用
收藏
页码:74 / 87
页数:14
相关论文
共 50 条
  • [1] Liquid desiccant dehumidifier: Development of a new performance predication model based on CFD
    Luo, Yimo
    Yang, Hongxing
    Lu, Lin
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 69 : 408 - 416
  • [2] Mathematical model and performance analysis of a novel outside evaporative cooling liquid desiccant dehumidifier
    Peng, Donggen
    Cheng, Xiaosong
    Li, Shuangling
    Zhang, Xiaosong
    Luo, Danting
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 82 : 212 - 226
  • [3] Energy efficient liquid desiccant-based dryer
    Rane, MV
    Reddy, SVK
    Easow, RR
    APPLIED THERMAL ENGINEERING, 2005, 25 (5-6) : 769 - 781
  • [4] An online model for predicting dynamic response of a packed liquid desiccant dehumidifier
    Zhang, Xiaobo
    Xu, Xiangguo
    Zhu, Yuxian
    ENERGY AND BUILDINGS, 2020, 224
  • [5] Performance analysis on the internally cooled dehumidifier using liquid desiccant
    Liu, X. H.
    Chang, X. M.
    Xia, J. J.
    Jiang, Y.
    BUILDING AND ENVIRONMENT, 2009, 44 (02) : 299 - 308
  • [6] Performance analysis of a multistage internal circulation liquid desiccant dehumidifier
    Cheng, Xingwang
    Rong, Yangyiming
    Zhou, Xia
    Gu, Chenjie
    Zhi, Xiaoqin
    Qiu, Limin
    Yuan, Yijun
    Wang, Kai
    APPLIED THERMAL ENGINEERING, 2020, 172
  • [7] Optimization of Liquid Desiccant Dehumidifier Performance Using Taguchi Method
    Seenivasan, D.
    Selladurai, V.
    Senthil, P.
    ADVANCES IN MECHANICAL ENGINEERING, 2014,
  • [8] Performance prediction of a liquid desiccant dehumidifier using artificial neural networks approach
    Bouzeffour, Fatih
    Khelidj, Benyoucef
    Yahi, Ferhat
    Belkacemi, Djelloul
    Taane, Walid
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 27 (02) : 211 - 225
  • [9] Numerical modeling and performance analysis of a membrane-based air dehumidifier using ionic liquid desiccant
    Liu, Xiaoli
    Qu, Ming
    Liu, Xiaobing
    Wang, Lingshi
    Warner, Joseph
    APPLIED THERMAL ENGINEERING, 2020, 175
  • [10] Performance Evaluation of Packed Tower Liquid Desiccant Dehumidifier Based on LSSVM
    Wang, Xinli
    Lu, Jiangang
    Yang, Qinmin
    Cai, Wenjian
    Sun, Youxian
    2013 10TH IEEE INTERNATIONAL CONFERENCE ON CONTROL AND AUTOMATION (ICCA), 2013, : 987 - 990