Ventilation and thermal conditions in secondary schools in the Netherlands: Effects of COVID-19 pandemic control and prevention measures

被引:26
作者
Ding, Er [1 ]
Zhang, Dadi [1 ]
Hamida, Amneh [1 ]
Garcia-Sanchez, Clara [2 ]
Jonker, Lotte [3 ]
de Boer, Annemarijn R. [3 ]
Bruijning, Patricia C. J. L. [3 ]
Linde, Kimberly J. [4 ]
Wouters, Inge M. [4 ]
Bluyssen, Philomena M. [1 ]
机构
[1] Delft Univ Technol, Fac Architecture & Built Environm, Chair Indoor Environm, Delft, Netherlands
[2] Delft Univ Technol, Fac Architecture & Built Environm, 3D Geoinformat Res Grp, Delft, Netherlands
[3] Univ Utrecht, UMC Utrecht, Julius Ctr Hlth Sci & Primary Care, Utrecht, Netherlands
[4] Univ Utrecht, Inst Risk Assessment Sci, Utrecht, Netherlands
关键词
Classrooms; Indoor air quality; Ventilation; Children; COVID-19; pandemic; Thermal comfort; INDOOR AIR-QUALITY; CLASSROOM VENTILATION; COMFORT; HEALTH; RATES; ASSOCIATION; PERFORMANCE; CHILDREN;
D O I
10.1016/j.buildenv.2022.109922
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
During the COVID-19 pandemic, the importance of ventilation was widely stressed and new protocols of ventilation were implemented in school buildings worldwide. In the Netherlands, schools were recommended to keep the windows and doors open, and after a national lockdown more stringent measures such as reduction of occupancy were introduced. In this study, the actual effects of such measures on ventilation and thermal conditions were investigated in 31 classrooms of 11 Dutch secondary schools, by monitoring the indoor and outdoor CO2 concentration and air temperature, both before and after the lockdown. Ventilation rates were calculated using the steady-state method. Pre-lockdown, with an average occupancy of 17 students, in 42% of the classrooms the CO2 concentration exceeded the upper limit of the Dutch national guidelines (800 ppm above outdoors), while 13% had a ventilation rate per person (VRp) lower than the minimum requirement (6 l/s/p). Postlockdown, the indoor CO2 concentration decreased significantly while for ventilation rates significant increase was only found in VRp, mainly caused by the decrease in occupancy (average 10 students). The total ventilation rate per classrooms, mainly induced by opening windows and doors, did not change significantly. Meanwhile, according to the Dutch national guidelines, thermal conditions in the classrooms were not satisfying, both preand post-lockdown. While opening windows and doors cannot achieve the required indoor environmental quality at all times, reducing occupancy might not be feasible for immediate implementation. Hence, more controllable and flexible ways for improving indoor air quality and thermal comfort in classrooms are needed.
引用
收藏
页数:14
相关论文
共 67 条
  • [1] Monitoring and Assessment of Indoor Environmental Conditions after the Implementation of COVID-19-Based Ventilation Strategies in an Educational Building in Southern Spain
    Aguilar, Antonio J.
    De la Hoz-torres, Maria L.
    Martinez-Aires, M. Dolores
    Ruiz, Diego P.
    [J]. SENSORS, 2021, 21 (21)
  • [2] Effects of the COVID-19 Pandemic on Indoor Air Quality and Thermal Comfort of Primary Schools in Winter in a Mediterranean Climate
    Alonso, Alicia
    Llanos, Jesus
    Escandon, Rocio
    Sendra, Juan J.
    [J]. SUSTAINABILITY, 2021, 13 (05) : 1 - 17
  • [3] Assessing the indoor air quality and their predictor variable in 21 home offices during the Covid-19 pandemic in Norway
    Alonso, M. Justo
    Moazami, T. N.
    Liu, P.
    Jorgensen, R. B.
    Mathisen, H. M.
    [J]. BUILDING AND ENVIRONMENT, 2022, 225
  • [4] [Anonymous], 2018, Standard Guide for Using Indoor Carbon Dioxide Concentrations to Evaluate Indoor Air Quality and Ventilation, DOI DOI 10.1520/D6245-18
  • [5] [Anonymous], 2005, 7730 ISO
  • [6] [Anonymous], 2017, Standard 55: Thermal Environmental Conditions For Human Occupancy
  • [7] ASHRAE, 2022, ASHRAE POSITION DOCU
  • [8] ASHRAE, 2016, VENT ACC IND AIR QUA
  • [9] Ventilation rates in schools and pupils' performance
    Bako-Biro, Zs.
    Clements-Croome, D. J.
    Kochhar, N.
    Awbi, H. B.
    Williams, M. J.
    [J]. BUILDING AND ENVIRONMENT, 2012, 48 : 215 - 223
  • [10] Review and Extension of CO2-Based Methods to Determine Ventilation Rates with Application to School Classrooms
    Batterman, Stuart
    [J]. INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH AND PUBLIC HEALTH, 2017, 14 (02):