Monitoring SF6 Gas Leakage Based on a Customized Binocular System

被引:2
|
作者
Si, Wenrong [1 ]
Zhao, Yingying [1 ]
Wang, Yan [2 ,3 ]
Li, Ben [2 ,3 ]
Tong, Geng [2 ,3 ]
Yu, Yiting [2 ,3 ]
机构
[1] State Grid Shanghai Elect Power Res Inst, Shanghai 200437, Peoples R China
[2] Northwestern Polytech Univ, Sch Mech Engn, Ningbo Inst, Xian 710072, Peoples R China
[3] Northwestern Polytech Univ, Key Lab Micro Nano Syst Aerosp, Key Lab Microand Nanoelectro Mech Syst Shaanxi Pro, Minist Educ, Xian 710072, Peoples R China
关键词
infrared imaging; customized; binocular system; SF6 gas detection; SENSOR;
D O I
10.3390/s24030993
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Sulfur hexafluoride (SF6) gas is extensively utilized as an insulating and arc-quenching medium in the circuit breakers and isolating switches of electrical equipment. It effectively isolates the circuits from the atmosphere and promptly extinguishes arcs. Therefore, the issue of SF6 gas leakage poses a significant threat to the related application fields, and the detection of SF6 gas leakage becomes extremely important. Infrared imaging detection offers advantages including non-contact, high precision, and visualization. However, most existing infrared detection systems are equipped with only one filter to detect SF6 gas. The images captured contain background noise and system noise, making these systems vulnerable to interference from such noises. To address these issues, we propose a method for monitoring SF6 gas leakage based on a customized binocular imaging (CBI) system. The CBI system has two filters, greatly reducing the interference of system noise and background noise. The first filter features the absorption resonant peak of SF6 gas. The second filter is used to record background noise and system noise. One aspect to note is that, in order to avoid the interference of other gases, the central wavelength of this second filter should keep away from the absorption resonant peaks of those gases. Accordingly, the central wavelengths of our customized filters were determined as 10,630 nm and 8370 nm, respectively. Then, two cameras of the same type were separately assembled with a customized filter, and the CBI prototype was accomplished. Finally, we utilized the difference method using two infrared images captured by the CBI system, to monitor the SF6 gas leakage. The results demonstrate that our developed system achieves a high accuracy of over 99.8% in detecting SF6 gas. Furthermore, the CBI system supports a plug-and-play customization to detect various gases for different scenarios.
引用
收藏
页数:9
相关论文
共 50 条
  • [41] A laser photoacoustic system for detection of SF6 in gas insulated systems
    Shwehdi, MH
    Gondal, MA
    2001 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2001, : 104 - 109
  • [42] SF6 GAS-ANALYSIS TECHNIQUE AND ITS APPLICATION FOR EVALUATION OF INTERNAL CONDITIONS IN SF6 GAS EQUIPMENT
    TOMINAGA, S
    KUWAHARA, H
    HIROOKA, K
    YOSHIOKA, T
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (09): : 4196 - 4206
  • [43] Life Management of SF6 Circuit Breakers based on Monitoring and Diagnosis
    Zhang, Xiang
    Zhang, Jiaosuo
    Gockenbach, Ernst
    Borsi, Hossein
    IEEE ELECTRICAL INSULATION MAGAZINE, 2009, 25 (03) : 21 - 29
  • [44] An Algorithm for Estimation of SF6 Leakage on Power Substation Assets
    Castro Aranda, Ferley
    Garcia Sierra, Rodolfo
    Ceron Piamba, Andres Felipe
    Mailhe, Benjamin
    Gil, Luis Miguel Leon
    ALGORITHMS, 2022, 15 (02)
  • [45] The Development of SF6 Green Substitute Gas
    Jiang, Tao
    Meng, Xiangzhao
    Wei, Qiming
    Jin, Lijun
    Sun, Yanjun
    SUSTAINABILITY, 2021, 13 (16)
  • [46] Minimizing the potential of SF6 gas emission
    Asset Management Department, PT PLN P3B, Jawa Bali Jakarta, Indonesia
    Proc. IEEE Int. Conf. Cond. Monit. Diagn., CMD, 1600, (476-479):
  • [47] Breakdown temperature of electrons in SF6 gas
    Uhm, Han S.
    Choi, Eun H.
    Cho, Guangsup
    Ryu, Han-Yong
    APPLIED PHYSICS LETTERS, 2010, 97 (16)
  • [48] Minimizing the Potential of SF6 Gas Emission
    Naswil, S.
    Siregar, R.
    Pharmatrisanti, A.
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 476 - 479
  • [49] IONIZATION AND ATTACHMENT COEFFICIENTS MEASURED IN SF6/AR AND SF6/KR GAS-MIXTURES
    QIU, Y
    XIAO, DM
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1994, 27 (12) : 2663 - 2665
  • [50] Diffusion principles of SF6 tracer gas: constraints on SF6 mixing distance in mine tunnels
    Xu, Fang
    Liu, Jian
    Wang, Dong
    Liu, Xue
    SCIENTIFIC REPORTS, 2025, 15 (01):