Monitoring SF6 Gas Leakage Based on a Customized Binocular System

被引:2
|
作者
Si, Wenrong [1 ]
Zhao, Yingying [1 ]
Wang, Yan [2 ,3 ]
Li, Ben [2 ,3 ]
Tong, Geng [2 ,3 ]
Yu, Yiting [2 ,3 ]
机构
[1] State Grid Shanghai Elect Power Res Inst, Shanghai 200437, Peoples R China
[2] Northwestern Polytech Univ, Sch Mech Engn, Ningbo Inst, Xian 710072, Peoples R China
[3] Northwestern Polytech Univ, Key Lab Micro Nano Syst Aerosp, Key Lab Microand Nanoelectro Mech Syst Shaanxi Pro, Minist Educ, Xian 710072, Peoples R China
关键词
infrared imaging; customized; binocular system; SF6 gas detection; SENSOR;
D O I
10.3390/s24030993
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Sulfur hexafluoride (SF6) gas is extensively utilized as an insulating and arc-quenching medium in the circuit breakers and isolating switches of electrical equipment. It effectively isolates the circuits from the atmosphere and promptly extinguishes arcs. Therefore, the issue of SF6 gas leakage poses a significant threat to the related application fields, and the detection of SF6 gas leakage becomes extremely important. Infrared imaging detection offers advantages including non-contact, high precision, and visualization. However, most existing infrared detection systems are equipped with only one filter to detect SF6 gas. The images captured contain background noise and system noise, making these systems vulnerable to interference from such noises. To address these issues, we propose a method for monitoring SF6 gas leakage based on a customized binocular imaging (CBI) system. The CBI system has two filters, greatly reducing the interference of system noise and background noise. The first filter features the absorption resonant peak of SF6 gas. The second filter is used to record background noise and system noise. One aspect to note is that, in order to avoid the interference of other gases, the central wavelength of this second filter should keep away from the absorption resonant peaks of those gases. Accordingly, the central wavelengths of our customized filters were determined as 10,630 nm and 8370 nm, respectively. Then, two cameras of the same type were separately assembled with a customized filter, and the CBI prototype was accomplished. Finally, we utilized the difference method using two infrared images captured by the CBI system, to monitor the SF6 gas leakage. The results demonstrate that our developed system achieves a high accuracy of over 99.8% in detecting SF6 gas. Furthermore, the CBI system supports a plug-and-play customization to detect various gases for different scenarios.
引用
收藏
页数:9
相关论文
共 50 条
  • [31] A highly accurate algorithm for SF6 leakage detection
    Inami, Hisao
    Tatemi, Masaru
    Rokunohe, Toshiaki
    Hirose, Makoto
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2016, 11 : S17 - S21
  • [32] Research on Quantitative Detection Technology of SF6 Gas Leakage Based on Dual-band Infrared Imaging
    Gao, Keli
    Yang, Yuan
    Yan, Xianglian
    Ji, Yansong
    Gao, Kai
    Wang, Shaojing
    Dianwang Jishu/Power System Technology, 2025, 49 (01): : 167 - 176
  • [33] Technology of optical SF6 breaker leakage detection
    School of Electrical Engineering, Northeast Dianli University, Jilin 132012, China
    Gaodianya Jishu, 2009, 2 (250-254):
  • [34] Applied-information Technology in A Kind of SF6 Gas Density on-line Monitoring System
    Xiang, Qiong
    Wang, Quan
    ADVANCED DEVELOPMENT OF ENGINEERING SCIENCE IV, 2014, 1046 : 261 - 265
  • [35] Development of On-line Monitoring System for SF6 Circuit Breaker
    Xiao Jin
    Zhang Liujun
    Hu Xiaoguang
    Liu Liang
    Zhang Lei
    2011 6TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA), 2011, : 537 - 541
  • [36] Separation and concentration of SF6 from N2/SF6 gas mixtures
    Nam, S. E.
    Park, A.
    Kim, B. S.
    Park, Y. I.
    EUROMEMBRANE CONFERENCE 2012, 2012, 44 : 970 - 971
  • [37] SEARCHING FOR GAS OR GAS MIXTURES AS SF6 SUBSTITUTES
    Li, Xuewen
    Sun, Keping
    Yu, Gefei
    PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON APPLIED ELECTROSTATICS, 2008, : 84 - 87
  • [38] An Effective Low-Contrast SF6 Gas Leakage Detection Method for Infrared Imaging
    Lu, Quan
    Li, Qin
    Hu, Likun
    Huang, Lifeng
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70
  • [39] Evaluation of SF6 Leakage from Gas Insulated Equipment on Electricity Networks in Great Britain
    Widger, Phillip
    Haddad, Abderrahmane
    ENERGIES, 2018, 11 (08):
  • [40] DC DIELECTRIC STRENGTH OF A SF6 GAS INSULATED SYSTEM.
    Menju, S.
    Takahashi, K.
    1977,