Monitoring SF6 Gas Leakage Based on a Customized Binocular System

被引:2
|
作者
Si, Wenrong [1 ]
Zhao, Yingying [1 ]
Wang, Yan [2 ,3 ]
Li, Ben [2 ,3 ]
Tong, Geng [2 ,3 ]
Yu, Yiting [2 ,3 ]
机构
[1] State Grid Shanghai Elect Power Res Inst, Shanghai 200437, Peoples R China
[2] Northwestern Polytech Univ, Sch Mech Engn, Ningbo Inst, Xian 710072, Peoples R China
[3] Northwestern Polytech Univ, Key Lab Micro Nano Syst Aerosp, Key Lab Microand Nanoelectro Mech Syst Shaanxi Pro, Minist Educ, Xian 710072, Peoples R China
关键词
infrared imaging; customized; binocular system; SF6 gas detection; SENSOR;
D O I
10.3390/s24030993
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
Sulfur hexafluoride (SF6) gas is extensively utilized as an insulating and arc-quenching medium in the circuit breakers and isolating switches of electrical equipment. It effectively isolates the circuits from the atmosphere and promptly extinguishes arcs. Therefore, the issue of SF6 gas leakage poses a significant threat to the related application fields, and the detection of SF6 gas leakage becomes extremely important. Infrared imaging detection offers advantages including non-contact, high precision, and visualization. However, most existing infrared detection systems are equipped with only one filter to detect SF6 gas. The images captured contain background noise and system noise, making these systems vulnerable to interference from such noises. To address these issues, we propose a method for monitoring SF6 gas leakage based on a customized binocular imaging (CBI) system. The CBI system has two filters, greatly reducing the interference of system noise and background noise. The first filter features the absorption resonant peak of SF6 gas. The second filter is used to record background noise and system noise. One aspect to note is that, in order to avoid the interference of other gases, the central wavelength of this second filter should keep away from the absorption resonant peaks of those gases. Accordingly, the central wavelengths of our customized filters were determined as 10,630 nm and 8370 nm, respectively. Then, two cameras of the same type were separately assembled with a customized filter, and the CBI prototype was accomplished. Finally, we utilized the difference method using two infrared images captured by the CBI system, to monitor the SF6 gas leakage. The results demonstrate that our developed system achieves a high accuracy of over 99.8% in detecting SF6 gas. Furthermore, the CBI system supports a plug-and-play customization to detect various gases for different scenarios.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Minimize leakage of SF6 gas by online monitoring
    Wang, CN
    Luan, KN
    Liu, HB
    Li, Y
    Proceedings of the World Engineers' Convention 2004, Vol F-B, Power and Energy, 2004, : 398 - 403
  • [2] SF6 Gas Leakage Monitoring Technology Based on Diffuse Photoacoustic Sensor
    Yang, Tianhe
    He, Jiahui
    Zhao, Jikuan
    Zhao, Xinyu
    Wu, Tong
    Zou, Jingyi
    Jian, Xu
    Chen, Ke
    ACTA PHOTONICA SINICA, 2024, 53 (12)
  • [3] Study on Detection of SF6 Gas Leakage Based on Photoacoustic Spectrometry
    Xu, Yuanzhe
    Zhou, Hongjing
    Li, Bo
    Zhao, Xin
    2009 INTERNATIONAL CONFERENCE ON MEASURING TECHNOLOGY AND MECHATRONICS AUTOMATION, VOL I, 2009, : 261 - 265
  • [4] Research on SF6 Leakage Detection Based on Artificial Intelligence Gas Cloud Leakage Algorithm
    Lai, Junju
    Xie, Da
    Lai, Jiawen
    Wang, Jingcheng
    Xian, Feng
    Chen, Yunxin
    2024 3RD INTERNATIONAL CONFERENCE ON ROBOTICS, ARTIFICIAL INTELLIGENCE AND INTELLIGENT CONTROL, RAIIC 2024, 2024, : 451 - 457
  • [5] Tightness monitoring of SF6 gas equipment
    Bykovets Yu.Ya.
    Egorov V.G.
    Seryakov K.I.
    Toropchin Yu.V.
    Chemeris V.S.
    Russian Electrical Engineering, 2010, 81 (09) : 498 - 503
  • [6] Early Leakage Detection of SF6 Gas in Gas Insulated Switchgear
    Kaur, Pallavjot
    Choudhury, Tapas
    2016 7TH INDIA INTERNATIONAL CONFERENCE ON POWER ELECTRONICS (IICPE), 2016,
  • [7] Development of monitoring and diagnostic system for SF6 gas insulated switchgear
    Kim, JB
    Kim, MS
    Park, KS
    Song, WP
    Kim, DS
    Kil, GS
    CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 453 - 456
  • [8] Analysis and Treatment of SF6 Gas Leakage of GIS Equipment
    Wang Kai
    Wang Sheng-xi
    12TH ANNUAL MEETING OF CHINA ASSOCIATION FOR SCIENCE AND TECHNOLOGY ON INFORMATION AND COMMUNICATION TECHNOLOGY AND SMART GRID, 2010, : 34 - 36
  • [9] The research on some problems of SF6 gas leakage with the on-line detection system
    Zhu, ZW
    Shi, J
    Wang, CM
    ISTM/2005: 6TH INTERNATIONAL SYMPOSIUM ON TEST AND MEASUREMENT, VOLS 1-9, CONFERENCE PROCEEDINGS, 2005, : 6682 - 6685
  • [10] A Soft Measurement Model of SF6 Gas Leakage State Based on Neural Network
    Wang, Zelin
    Lv, Jianxun
    Chen, Cong
    Jin, Haiyong
    Huang, Xiaobeng
    Yuan, Haiwen