Active Location Method for Single-Line-to-Ground Fault of Flexible Grounding Distribution Networks

被引:6
|
作者
Lin, Jiahao [1 ]
Guo, Moufa [1 ]
Zheng, Zeyin [1 ]
机构
[1] Fuzhou Univ, Coll Elect Engn & Automat, Fuzhou 350108, Peoples R China
基金
中国国家自然科学基金;
关键词
Index Terms-Fault arc suppression; fault section active location method; flexible grounding distribution network; ground fault nature judgment; single-line-to-ground (SLG) fault; SECTION IDENTIFICATION; DISTRIBUTION-SYSTEMS; PHASE;
D O I
10.1109/TIM.2023.3298416
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The single-line-to-ground (SLG) fault is the most common fault in distribution networks. The output current of cascaded H-bridges (CHBs) can be controlled flexibly to suppress SLG fault current. Therefore, a CHB-based active location method is proposed in this article, which integrates the functions of SLG fault arc suppression, fault section location, and fault nature judgment. When an SLG fault occurs, CHB devices quickly inject full compensated current into the system neutral to suppress the fault current. Then, CHB devices are regulated to reduce the injected current, and the variations of zero-sequence voltage and zero-sequence current are actively constructed. The phase characteristics between zero-sequence voltage variation and zero-sequence current variation can be used as the criteria for fault section location and fault nature judgment. In addition, the measurement device, namely, the retrofitted feeder terminal unit (FTU), contains signal acquisition module, and signal calculation module is designed, which can collect the zero-sequence signal and calculate the phase difference. Finally, the effectiveness of these three functions and the fault-location accuracy of the proposed method have been verified through the simulation and experimental cases.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Single-line-to-ground fault location in the compensated distribution network
    Xu, B.
    Cai, X.
    Zhu, M.J.
    Qin, H.
    Xi, D.M.
    Australian Journal of Electrical and Electronics Engineering, 2013, 10 (04): : 449 - 458
  • [2] Single-line-to-ground Fault Location in Wind Farm Collection Line With Neutral Point Grounding With Resistor
    Wang B.
    Ren X.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (06): : 2136 - 2143
  • [3] New algorithm for location of single-line-to-ground fault on radial distribution network
    Jia, Wenchao
    Xu, Chengbin
    Harbin Gongye Daxue Xuebao/Journal of Harbin Institute of Technology, 2000, 32 (02): : 118 - 120
  • [4] Identification method for single-line-to-ground fault with line breaks in medium-voltage distribution networks
    Li Z.-C.
    Liu Y.-D.
    Yan Y.-J.
    Wang P.
    Jiang X.-C.
    Dianji yu Kongzhi Xuebao/Electric Machines and Control, 2022, 26 (02): : 43 - 53
  • [5] Faulty Phase Recognition Method for Single-Line-to-Ground Fault in Resonant Grounded Distribution Networks
    Ma, Mingwen
    Wang, Wen
    Wang, Faliang
    Ren, Xingqiang
    Wang, Zhen
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 351 - 357
  • [6] Location of Single-Line-to-Ground Fault Using 1-D Convolutional Neural Network and Waveform Concatenation in Resonant Grounding Distribution Systems
    Guo, Mou-Fa
    Gao, Jian-Hong
    Shao, Xiang
    Chen, Duan-Yu
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70
  • [7] Single-Line-to-Ground Fault Location in Resonant Grounded Systems Based on Fault Distortions
    Chen, Yougen
    Yin, Junbo
    Li, Zhiyong
    Wei, Renyong
    IEEE ACCESS, 2021, 9 (09): : 34325 - 34337
  • [8] A Single-Phase Ground Fault Line Selection Method in Active Distribution Networks Based on Transformer Grounding Mode Modification
    Su, Shi
    Xie, Qingyang
    Ma, Pengfei
    Li, Yuan
    Chen, Fahui
    Zhang, Jing
    Li, Botong
    Wang, Changqi
    ENERGIES, 2024, 17 (18)
  • [9] Faulty Phase Detection Method Under Single-Line-to-Ground Fault Considering Distributed Parameters Asymmetry and Line Impedance in Distribution Networks
    Wang, Wen
    Gao, Xiong
    Fan, Bishuang
    Zeng, Xiangjun
    Yao, Ganzhou
    IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1513 - 1522
  • [10] Identification Method for Single-line-to-ground Faults with Line Break Based on Phasor Measurement in Distribution Networks
    Yadong Liu
    Zichang Li
    Yingjie Yan
    Guanghui He
    Jian Fang
    Kejun Li
    Xiuchen Jiang
    JournalofModernPowerSystemsandCleanEnergy, 2023, 11 (03) : 907 - 916