Thermal monitoring of live-line power transmission lines with an infrared camera mounted on an unmanned aerial vehicle

被引:7
作者
Jeong, Siheon [1 ]
Kim, Min-Gwan [1 ]
Kim, Joo-Hyung [2 ]
Oh, Ki-Yong [1 ,3 ]
机构
[1] Hanyang Univ, Dept Mech Convergence Engn, Seoul, South Korea
[2] Inha Univ, Dept Mech Engn, Incheon, South Korea
[3] Hanyang Univ, Dept Mech Convergence Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
来源
STRUCTURAL HEALTH MONITORING-AN INTERNATIONAL JOURNAL | 2023年 / 22卷 / 06期
基金
新加坡国家研究基金会;
关键词
Autonomous camera tracking; infrared camera; thermal imaging; patrol inspection; transmission lines; unmanned aerial vehicle;
D O I
10.1177/14759217231156359
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This study proposes a thermal monitoring method in outdoor environments to inspect the health state of overhung transmission lines (TLs) with an infrared camera mounted on an unmanned aerial vehicle (UAV). The suggested method features three characteristics. First, the thermal energy of TLs measured by an infrared camera is converted into accurate temperature accounting for the conversion principle of the infrared camera. Characteristic parameters in the conversion principle, including emissivity, transmissibility, and reflectability, are systematically quantified through experiments. Second, a simple yet effective postprocessing method is proposed to eliminate thermal energy emitted from other heat sources in outdoor environments. Third, an automatic line-tracking method is proposed to focus on TLs for reliable thermal imaging during patrol inspection. The proposed method with an infrared camera deployed on a UAV is field-tested through an autonomous flight and gimbal control. A systemic analysis on field tests demonstrates that the proposed method overcomes several bottlenecks in current technologies and reveals several important considerations regarding thermally monitoring overhung TLs in outdoor environments. This insightful discovery supports developing a fully autonomous solution for accurate outdoor thermal imaging despite the many challenges that remain.
引用
收藏
页码:3707 / 3722
页数:16
相关论文
共 17 条
[1]   Causes of the 2003 major grid blackouts in north America and Europe, and recommended means to improve System Dynamic Performance [J].
Andersson, G ;
Donalek, P ;
Farmer, R ;
Hatziargyriou, N ;
Kamwa, I ;
Kundur, P ;
Martins, N ;
Paserba, J ;
Pourbeik, P ;
Sanchez-Gasca, J ;
Schulz, R ;
Stankovic, A ;
Taylor, C ;
Vittal, V .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2005, 20 (04) :1922-1928
[2]  
AUAV, 2016, Drone Types: Multi-Rotor vs Fixed-Wing vs Single Rotor vs Hybrid VTOL
[3]   Transmission line conductor temperature impact on state estimation accuracy [J].
Bockarjova, Marija ;
Andersson, Goeran .
2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, :701-706
[5]  
Ferraro R., 2015, FIELD GUIDE INSPECTI
[6]  
FLIR, 2014, LEPT RAD APPL NOT
[7]  
Gubareff G. G., 1960, Thermal Radiation Properties survey: a Review of the literature
[8]  
Hough P.V., 1962, US Patent, Patent No. [3,069,654, 3069654]
[9]  
Kalman R E., 1960, Transactions ASME Journal of Basic Engineering, V82, P35, DOI [DOI 10.1115/1.3662552, 10.1115/1.3662552]
[10]  
김성덕, 2008, [Journal of the Korean Institute of Illuminating and Electrical Installation Engineers, 조명.전기설비학회논문지], V22, P139