Comparative analysis of a new desiccant dehumidifier design with a traditional rotary desiccant wheel for air conditioning purpose

被引:19
作者
Abdelgaied, Mohamed [1 ]
Saber, Mohamed A. [1 ]
Bassuoni, M. M. [1 ]
Khaira, Ahmad M. [1 ]
机构
[1] Tanta Univ, Fac Engn, Mech Power Engn Dept, Tanta, Egypt
关键词
Comparative study; Innovative desiccant dehumidifiers; Rotary desiccant wheel; Solar energy; Air conditioning; Thermal recovery unit; PERFORMANCE ASSESSMENT; MATHEMATICAL-MODEL; SYSTEM; ENERGY; VAPOR; OPTIMIZATION; BUILDINGS; SILICA; HOT; BED;
D O I
10.1016/j.applthermaleng.2022.119945
中图分类号
O414.1 [热力学];
学科分类号
摘要
Rotary desiccant dehumidifiers for air conditioning purposes are considered one of the most promising air conditioners for regions that suffer from high humidity and temperatures. The heat generated by the adsorption effect represents the most important problem facing the rotary desiccant dehumidifier. So, the present study aims to suggest an innovative design of a desiccant dehumidifier that has a higher dehumidification capacity, in addition, to cooling the process air with cooling rates higher than the heat generated by the adsorption effect. To evaluate the performance of the proposed desiccant dehumidifier, a comparative experimental study was conducted for both the novelty innovative configuration of the desiccant dehumidifier (NICDD) and traditional rotary desiccant dehumidifier (TRDD) under the same weather conditions. The experimental results presented that the utilization of NICDD represents a good choice that can reduce the temperatures of the process air that leaves the desiccant dehumidifier by rates varying between 17.8 and 23.8 degrees C as compared to TRDD. Also, the use of NICDD causes improved average dehumidification capacity from 5.57 to 9.82 gw/kgda, with an improvement of 70.2%. Moreover; the use of NICDD causes improved the dehumidification coefficient of performance from 0.268 to 1.012, with an improvement of 277.6% compared to TRDD.
引用
收藏
页数:16
相关论文
共 40 条
[1]   Performance improvement of desiccant air conditioner coupled with humidification-dehumidification desalination unit using solar reheating of regeneration air [J].
Abdelgaied, Mohamed ;
Kabeel, A. E. ;
Zakaria, Yehya .
ENERGY CONVERSION AND MANAGEMENT, 2019, 198
[2]   Experimental investigation of an integrated absorption- solid desiccant air conditioning system [J].
Ali, Muzaffar ;
Habib, Muhammad Farhan ;
Sheikh, Nadeem Ahmed ;
Akhter, Javed ;
Gilani, Syed Ihtsham ul Haq .
APPLIED THERMAL ENGINEERING, 2022, 203
[3]  
[Anonymous], 1999, BUILD SERV ENG RES T
[4]   Comparison between the conventional and recirculation modes in desiccant cooling cycles and deriving critical efficiencies of components [J].
Bourdoukan, P. ;
Wurtz, E. ;
Joubert, P. .
ENERGY, 2010, 35 (02) :1057-1067
[5]   Experiences with a gas driven, desiccant assisted air conditioning system with geothermal energy for an office building [J].
Casas, W ;
Schmitz, G .
ENERGY AND BUILDINGS, 2005, 37 (05) :493-501
[6]   Experimental investigation of precooling desiccant-wheel air-conditioning system in a high-temperature and high-humidity environment [J].
Chen, L. ;
Chen, S. H. ;
Liu, L. ;
Zhang, B. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 95 :83-92
[7]   Optimization of desiccant wheel speed and area ratio of regeneration to dehumidification as a function of regeneration temperature [J].
Chung, Jae Dong ;
Lee, Dae-Young ;
Yoon, Seok Mann .
SOLAR ENERGY, 2009, 83 (05) :625-635
[8]   ENGINEERING APPLICATION OF EXPERIMENTAL UNCERTAINTY ANALYSIS [J].
COLEMAN, HW ;
STEELE, WG .
AIAA JOURNAL, 1995, 33 (10) :1888-1896
[9]  
Dunkle R.C., 1965, Aust. Mech. Chem. Eng. Transm, V1, P73
[10]   Effect of inter-cooling on the performance and economics of a solar energy assisted hybrid air conditioning system with six stages one-rotor desiccant wheel [J].
Elzahzby, Ali M. ;
Kabeel, A. E. ;
Bassuoni, M. M. ;
Abdelgaied, Mohamed .
ENERGY CONVERSION AND MANAGEMENT, 2014, 78 :882-896