Novel Hotspot Temperature Prediction of Oil-Immersed Distribution Transformers: An Experimental Case Study

被引:15
|
作者
Abdali, Ali [1 ,2 ]
Abedi, Ali [1 ]
Mazlumi, Kazem [3 ]
Rabiee, Abbas [3 ]
Guerrero, Josep M. [4 ]
机构
[1] Kooshkan Transformers Co, R&D Dept, Zanjan 1991647113, Iran
[2] Univ Zanjan, Fac Engn, Dept Elect Engn, Zanjan 4537138791, Iran
[3] Univ Zanjan, Fac Engn, Dept Elec tr Engn, Zanjan 4537138791, Iran
[4] Aalborg Univ, CROM Ctr Res Microgrids, AAU Energy, DK-9220 Aalborg, Denmark
关键词
Oil insulation; Mathematical models; Power transformer insulation; Windings; Transformers; Oils; IEC Standards; Computational fluid dynamics (CFD); corrugated wall distribution transformer (DT); hotspot temperature (HST); optical fiber sensor (OFS); thermal camera; HOT-SPOT TEMPERATURE; POWER TRANSFORMER; MODEL; OPTIMIZATION; MANAGEMENT;
D O I
10.1109/TIE.2022.3206690
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Distribution transformers (DTs) are deemed fundamental and high-priced equipment for power grids, and their failure influences grid reliability. The continuity of DT operation highly depends on its insulation conditions and following that to the hotspot temperature (HST). In this article, a novel formula is proposed for HST prediction of DTs by considering the effective electrical and mechanical parameters on heat dissipation capacity. Additionally, complete and accurate 3D modeling based on computational fluid dynamics (CFD) is presented to validate the proposed novel formula for HST prediction. In this modeling, the conservator, which plays a key role in the HST value, is accurately modeled. Optical fiber sensors are utilized in the studied 500-kVA DT to verify the accuracy of the proposed HST prediction formula during the experimental temperature rise test. Experimental results show that the proposed formula is highly accurate and has an acceptable correlation with the empirical values. The root-mean-square error, mean error, and average error percentage (AEP) of the proposed formula are 0.3?, 0.3 ?, and 0.37%, respectively, in HST transient values, and 0.3 ?, 0.3 ?, and 0.29% in HST steady-state values, which substantiate the precision and proficiency of the proposed HST prediction formula rather than IEC and IEEE equations. Finally, a thermal camera is employed to verify the results of CFD-based 3D modeling in top-oil temperature, bottom-oil temperature, and conservator oil temperature during the experimental tests. According to the measurement results, temperatures of CFD-based 3D simulation and thermal camera in the aforementioned three points are in good agreement with each other and AEP is less than 1.4%, which indicates the accuracy and efficiency of the proposed 3-D modeling.
引用
收藏
页码:7310 / 7322
页数:13
相关论文
共 50 条
  • [31] A Dynamic Adam Based Deep Neural Network for Fault Diagnosis of Oil-Immersed Power Transformers
    Ou, Minghui
    Wei, Hua
    Zhang, Yiyi
    Tan, Jiancheng
    ENERGIES, 2019, 12 (06)
  • [32] Research on Inversion Model of Winding Hot Spot Temperature of 10-kV Oil-Immersed Three-Dimensional Coiled Core Transformer
    Chen, Qianyi
    Chen, Shaonan
    Huang, Weixiang
    Zhang, Wei
    Li, Kewen
    IEEE ACCESS, 2024, 12 : 97691 - 97700
  • [33] Measurements and performance evaluations of natural ester and mineral oil-immersed identical transformers
    Cilliyuz, Yusuf
    Bicen, Yunus
    Aras, Faruk
    Aydugan, Guzide
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 125
  • [34] Explainable Fault Diagnosis of Oil-Immersed Transformers: A Glass-Box Model
    Liao, Wenlong
    Zhang, Yi
    Cao, Di
    Ishizaki, Takayuki
    Yang, Zhe
    Yang, Dechang
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2024, 73 : 1 - 4
  • [35] Fault diagnosis method for oil-immersed transformers integrated digital twin model
    Yao, Haiyan
    Zhang, Xin
    Guo, Qiang
    Miao, Yufeng
    Guan, Shan
    SCIENTIFIC REPORTS, 2024, 14 (01):
  • [36] On Thermal Performance Analysis of Oil-Immersed Power Transformers: Winding Cooling Curve
    Gamil, A.
    Schluecker, E.
    2022 7TH INTERNATIONAL ADVANCED RESEARCH WORKSHOP ON TRANSFORMERS (ARWTR 2022), 2022, : 1 - 6
  • [37] A validated online algorithm for detection of fan failures in oil-immersed power transformers
    Djamali, Mohammad
    Tenbohlen, Stefan
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2017, 116 : 224 - 233
  • [38] Review of Modeling Approaches for Conjugate Heat Transfer Processes in Oil-Immersed Transformers
    Smolyanov, Ivan
    Shmakov, Evgeniy
    Butusov, Denis
    Khalyasmaa, Alexandra I.
    COMPUTATION, 2024, 12 (05)
  • [39] The Improved Thermal-circuit Model for hot-spot temperature calculation of Oil-immersed Power Transformers
    Wei Ben-gang
    Fu Chen-zhao
    Li Hong-lei
    Li Ke-jun
    Liang Yong-liang
    2016 IEEE INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC), 2016, : 809 - 813
  • [40] Numerical study on temperature rise and mechanical properties of winding in oil-immersed transformer
    Jia, Xiaoyu
    Lin, Mei
    Su, Shiwei
    Wang, Qiuwang
    Yang, Jian
    ENERGY, 2022, 239