A single-ended traveling wave based fault location method using DWT in hybrid parallel HVAC/HVDC overhead transmission lines on the same tower

被引:20
作者
Fayazi, Mohammad [1 ]
Joorabian, Mahmood [1 ]
Saffarian, Alireza [1 ]
Monadi, Mehdi [1 ]
机构
[1] Shahid Chamran Univ Ahvaz, Fac Engn, Dept Elect Engn, Ahvaz 6135785311, Iran
关键词
Hybrid parallel HVAC; HVDC overhead; transmission line; AC and DC faults; Intersystem faults; Fault location; Discrete Wavelet Transform (DWT); Traveling wave (TW); Signal processing; PROTECTION; VOLTAGE;
D O I
10.1016/j.epsr.2023.109302
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, a single ended traveling wave based fault location method is presented for Hybrid Parallel HVAC/ HVDC Overhead Transmission Lines (HPOTLs) on the same tower using Discrete Wavelet Transform (DWT). In HPOTLs, the AC and DC transmission lines are adjacent to each other from the sending to the receiving end of the lines and there is electromagnetic coupling between them. Fault detection and classification algorithms in HPOTLs are presented in another paper. Therefore, in order to summarizing, in this paper, it is assumed that the fault is detected in the HVAC or/and HVDC lines and faulty line is identified. HPOTL faults include AC faults, DC faults and AC/DC intersystem faults. AC and DC voltage signals on sending end of the transmission line with a sampling frequency of 100 kHz are used for fault location in this paper. In order to minimize the noise effect, the squared wavelet transform coefficients (WTC2) is used for proposed fault location method. Finally, BewleyLattice diagrams are checked for the traveling wave pattern and locate the fault. At the end of paper, it has been shown that the proposed method has high accuracy, noise immunity, robustness against fault inception angles, and high impedance faults.
引用
收藏
页数:17
相关论文
共 39 条
[11]   Wavelet-based protection strategy for DC faults in multi-terminal VSC HVDC systems [J].
De Kerf, K. ;
Srivastava, K. ;
Reza, M. ;
Bekaert, D. ;
Cole, S. ;
Van Hertem, D. ;
Belmans, R. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (04) :496-503
[12]   Simulation and analysis of cascading faults in hybrid AC/DC power grids [J].
Dong, Xinzhou ;
Guan, Eryong ;
Jing, Liuming ;
Wang, Hao ;
Mirsaeidi, Sohrab .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 115
[13]   Fault Handling at Hybrid High-Voltage AC/DC Transmission Lines With VSC Converters [J].
Ebner, Guenter ;
Doering, David ;
Schettler, Frank ;
Wuerflinger, Klaus ;
Zeller, Marcus .
IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) :901-908
[14]  
Elhaffar AbdelsalamMohamed., 2008, Power Transmission Line Fault Location based on Current Travelling Waves
[15]  
Gilany M., 2008, International Journal of Power and Energy Systems, V28, P160, DOI 10.2316/Journal.203.2008.2.203-3843
[16]  
Greenwood A., 1991, ELECT TRANSIENTS POW, V2nd
[17]   Natural Frequency-Based Line Fault Location in HVDC Lines [J].
He, Zheng-You ;
Liao, Kai ;
Li, Xiao-Peng ;
Lin, Sheng ;
Yang, Jian-Wei ;
Mai, Rui-Kun .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) :851-859
[18]  
Hu J. J., 2011, MIPSYCON
[19]   Wavelet transforms in power systems - Part 1 - General introduction to the wavelet transforms [J].
Kim, CH ;
Aggarwal, R .
POWER ENGINEERING JOURNAL, 2000, 14 (02) :81-87
[20]  
Kizilcay M., 2009, P INT C POW SYST TRA, P3