An experimental study on cooling of model data center building by using eutectic phase change material in their walls

被引:13
作者
Kurt, Kubra [1 ]
Oztop, Hakan F. [1 ]
Abu-Hamdeh, Nidal [2 ]
Gur, Muhammed [1 ]
机构
[1] Firat Univ, Technol Fac, Dept Mech Engn, Elazig, Turkiye
[2] King Abdulaziz Univ, Engn Fac, Dept Mech Engn, Jeddah, Saudi Arabia
关键词
Data Center; Energy storage; Eutectic phase change material; DSC; CALCIUM-CHLORIDE HEXAHYDRATE; THERMAL MANAGEMENT; STORAGE; PCM; COMPOSITE; MIXTURE; SYSTEM;
D O I
10.1007/s10973-023-12203-3
中图分类号
O414.1 [热力学];
学科分类号
摘要
A prototype data center was created as part of this project. Lauric acid (LA), stearic acid (SA), and undecanoic acid (UA) were blended at a mass of 16%, 10%, and 32%, respectively, to be placed in the system. LA, SA, and UA thermophysical characteristics were examined. The melting temperatures and latent heat values of LA, SA, and UA were determined by differential scanning calorimetry to be 17.13 degrees C, 71.9 degrees C, 26.82 degrees C, and 24.49 degrees C, respectively, and 190 J g(-1), 235 J g(-1), 178 J g(-1), and 150 J g(-1). Thermal conductivities measured with the KD2 Pro were 0.288 W mK(-1) for LA, 0.143 W mK(-1) for SA, 0.201 W mK(-1) for UA, and 0.245 W mK(-1) for LA-SA-UA. The heat capacity values for LA, SA, UA, and LA-SA-UA were found to be 22.15 J g(-1), 18.82 J g(-1), 17.20 J g(-1), and 20.49 J g(-1), respectively. The findings demonstrate the utility of the LA-SA-UA mixture in energy storage. Thermocouples are deployed in the system at predetermined locations to compare the conditions when the data center is empty and with PCM. At four different speeds (5 m s(-1), 4.45 m s(-1), 4.25 m s(-1), and 2.5 m s(-1)), empty and PCM cases were compared. 5 m s(-1), 4.45 m s(-1), 4.25 m s(-1), and 2.5 m s(-1) PCM system timings were 7800-16440 s, 6960-14,200 s, 5880-11900 s, 4440 s, and 9360 s, respectively. The presence of LA-SA-UA energy storage in the data center is demonstrated in this study.
引用
收藏
页码:7233 / 7258
页数:26
相关论文
共 23 条
[11]   Adopting PCM and natural ventilation in buildings to reduce energy demand in HVAC -Examining various PCM along with various natural ventilation scenarios [J].
Khdair, Adnan I. ;
Abu Rumman, Ghaida .
JOURNAL OF BUILDING ENGINEERING, 2022, 57
[12]  
Liao J, 2023, J THERM SCI, V188
[13]  
Lukic P., 2012, FACTA UNIVERSITATIS, Series: Architecture and Civil Engineering, V10, P343, DOI DOI 10.2298/FUACE1203343L
[14]   A review of thermal management and innovative cooling strategies for data center [J].
Nadjahi, Chayan ;
Louahlia, Hasna ;
Lemasson, Stephane .
SUSTAINABLE COMPUTING-INFORMATICS & SYSTEMS, 2018, 19 :14-28
[15]   Preparation, characterization and thermal properties of lauric acid/expanded perlite as novel form-stable composite phase change material [J].
Sari, Ahmet ;
Karaipekli, Ali ;
Alkan, Cemil .
CHEMICAL ENGINEERING JOURNAL, 2009, 155 (03) :899-904
[16]   Influence of basic raw materials on the maximum storage capacity of the phase change material calcium chloride hexahydrate [J].
Schmit, Henri ;
Rudaleviciene, Dovile ;
Rathgeber, Christoph ;
Hiebler, Stefan .
JOURNAL OF ENERGY STORAGE, 2020, 27
[17]   A novel calcium chloride hexahydrate-based deep eutectic solvent as a phase change materials [J].
Shahbaz, K. ;
AlNashef, I. M. ;
Lin, R. J. T. ;
Hashim, M. A. ;
Mjalli, F. S. ;
Farid, M. M. .
SOLAR ENERGY MATERIALS AND SOLAR CELLS, 2016, 155 :147-154
[18]   Calibration of differential scanning calorimeter (DSC) for thermal properties analysis of phase change material [J].
Su, Weiguang ;
Gao, Liying ;
Wang, Li ;
Zhi, Hui .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2021, 143 (04) :2995-3002
[19]   Direct contact melting due to a permeable rotating disk [J].
Turkyilmazoglu, M. .
PHYSICS OF FLUIDS, 2019, 31 (02)
[20]   Thermal management of parabolic pin fin subjected to a uniform oncoming airflow: optimum fin dimensions [J].
Turkyilmazoglu, Mustafa .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2021, 143 (05) :3731-3739