Numerical Investigation on Thermal Performance of Two-Phase Immersion Cooling Method for High-Power Electronics

被引:1
|
作者
Zhou, Liqun [1 ]
Yang, Weilin [1 ]
Li, Chaojie [2 ]
Lin, Shi [3 ]
机构
[1] Lanzhou Univ Technol, Coll Petrochem Engn, Lanzhou 730050, Peoples R China
[2] Qingdao Univ Sci & Technol, Coll Environm & Safety Engn, Qingdao 266042, Peoples R China
[3] Yango Univ, Coll Artificial Intelligence, Fuzhou 350015, Peoples R China
来源
FRONTIERS IN HEAT AND MASS TRANSFER | 2024年 / 22卷 / 01期
关键词
Immersion cooling; operating condition; high -power electronics; thermal management; SOLAR-CELLS; FLOW;
D O I
10.32604/fhmt.2023.045135
中图分类号
O414.1 [热力学];
学科分类号
摘要
The power density of electronic components grows continuously, and the subsequent heat accumulation and temperature increase inevitably affect electronic equipment's stability, reliability and service life. Therefore, achieving efficient cooling in limited space has become a key problem in updating electronic devices with high performance and high integration. Two-phase immersion is a novel cooling method. The computational fluid dynamics (CFD) method is used to investigate the cooling performance of two-phase immersion cooling on high -power electronics. The two-dimensional CFD model is utilized by the volume of fluid (VOF) method and Reynolds Stress Model. Lee's model was employed to calculate the phase change rate. The heat transfer coefficient along the heated walls and the shear-lift force on bubbles are calculated. The simulation data are verified with the literature results. The cooling performance of different coolants has been studied. The results indicate that the boiling heat transfer coefficient can be enhanced by using a low boiling point coolant. The methanol is used as the cooling medium for further research. In addition, the mass flow rate and inlet temperature are investigated to assess the thermal performance of twophase immersion cooling. The average temperature of the high -power electronics is 80 degrees C, and the temperature difference can be constrained to 8 degrees C. Meanwhile, the convective heat transfer coefficient reaches 2740 W/(m2 center dot degrees C) when the inlet temperature is 50 degrees C, and the mass flow rate is 0.3 kg/s. In conclusion, the results demonstrated that two-phase immersion cooling has provided an effective method for the thermal management of high -power electronics.
引用
收藏
页码:157 / 173
页数:17
相关论文
共 50 条
  • [1] Innovative Two-Phase Immersion Cooling Solutions for high-power Advanced Packages
    Sharma, Sumit
    Ahinad, Aqbal
    Huang, ICheng
    Lu, Ying-Xu
    Huang, Hung-Hsien
    Wang, Chen-Chao
    Hung, Chih-Pin
    Wang, Chi-Chuan
    PROCEEDINGS OF THE IEEE 74TH ELECTRONIC COMPONENTS AND TECHNOLOGY CONFERENCE, ECTC 2024, 2024, : 1515 - 1521
  • [2] Enhanced Thermal Performance of High Flux LED Systems with Two-Phase Immersion Cooling
    Cengiz, Ceren
    Muslu, Ahmet Mete
    Arik, Mehmet
    Dogruoz, Baris
    PROCEEDINGS OF THE NINETEENTH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM 2020), 2020, : 196 - 206
  • [3] Chip Level Thermal Performance Measurements in Two-Phase Immersion Cooling
    Shah, Jimil M.
    Crandall, Thomas
    Tuma, Phillip E.
    JOURNAL OF ELECTRONIC PACKAGING, 2023, 145 (04)
  • [4] Flat plate two-phase heat spreader on the thermal management of high-power electronics: a review
    Lim, Hyunmuk
    Lee, Jungho
    JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2021, 35 (11) : 4801 - 4814
  • [5] Flat plate two-phase heat spreader on the thermal management of high-power electronics: a review
    Hyunmuk Lim
    Jungho Lee
    Journal of Mechanical Science and Technology, 2021, 35 : 4801 - 4814
  • [6] Heat transfer dependence of power usage effectiveness of an augmented two-phase immersion cooling system for high-power servers
    Ma, Yu
    Bao, Yuchen
    Li, Ji
    ENERGY, 2025, 323
  • [7] Thermal Performance of Single-Phase and Two-Phase Immersion Cooling in Data Center
    Liu, Chun-Kai
    Chang, Tan-Yi
    2022 17TH INTERNATIONAL MICROSYSTEMS, PACKAGING, ASSEMBLY AND CIRCUITS TECHNOLOGY CONFERENCE (IMPACT), 2022,
  • [8] POWER DENSITY IN THE CONTEXT OF TWO-PHASE IMMERSION COOLING
    Shah, Jimil M.
    Tuma, Phillip E.
    PROCEEDINGS OF ASME 2022 INTERNATIONAL TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC MICROSYSTEMS, INTERPACK2022, 2022,
  • [9] Compact Two-Phase Immersion Cooling With Dielectric Fluid for PCB-Based Power Electronics
    Ristic-Smith, Aleksandar
    Rogers, Daniel J.
    IEEE OPEN JOURNAL OF POWER ELECTRONICS, 2024, 5 : 1107 - 1118
  • [10] Passive Two-Phase Cooling for Automotive Power Electronics
    Moreno, Gilberto
    Jeffers, Jana R.
    Narumanchi, Sreekant
    Bennion, Kevin
    2014 30TH ANNUAL SEMICONDUCTOR THERMAL MEASUREMENT AND MANAGEMENT SYMPOSIUM (SEMI-THERM), 2014, : 58 - 65