A cascading failure model of cyber-coupled power system considering virus propagation

被引:2
作者
Gao, Xingle [1 ]
Peng, Minfang [2 ]
Zhang, Ji [1 ]
Shao, Hua [1 ]
Liu, Yanchen [2 ]
机构
[1] State Grid Hebei Elect Power Co Ltd, Econ & Technol Res Inst, Shijiazhuang, Hebei, Peoples R China
[2] Hunan Univ, Coll Elect & Informat Engn, Changsha, Hunan, Peoples R China
基金
中国国家自然科学基金;
关键词
Cyber-coupled system; Interdependent network; Virus propagation; Cascading failure; ROBUSTNESS;
D O I
10.1016/j.physa.2024.129549
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
Cyber attacks from the information layer can have a serious impact on the operation of the cybercoupled power system. In this paper, a practical cascading failure model used for investigating the impact of virus propagation on the cascading failure of cyber-coupled power system is proposed. The model takes into account the actual functionality of cyber-coupled system and the dynamic virus propagation in cyber network, and describes the effects of cyber node failure caused by virus infection and power flow overload on the cascading failure. Moreover, the impact of defense upgrade on the virus propagation is considered. Centralized control based on dispatching center and local regulation based on static power-frequency characteristic are introduced to describe the actual monitoring function of cyber system on the power grid. Then, the effects of defense upgrade strategy and modular community structure on the failure evolution are analyzed. The results indicate that the spread of virus destroys the monitoring function of cyber network on the power network and leads to more serious failure results. The effectiveness of defense upgrade strategies is related to the upgrade probability of information stations. In addition, the stronger community structure of cyber network can improve the robustness of cyber-coupled power system.
引用
收藏
页数:9
相关论文
共 20 条
  • [1] [Anonymous], 1962, IEEE 118-Bus System
  • [2] Catastrophic cascade of failures in interdependent networks
    Buldyrev, Sergey V.
    Parshani, Roni
    Paul, Gerald
    Stanley, H. Eugene
    Havlin, Shlomo
    [J]. NATURE, 2010, 464 (7291) : 1025 - 1028
  • [3] Robustness of Interdependent Power Grids and Communication Networks: A Complex Network Perspective
    Chen, Zhenhao
    Wu, Jiajing
    Xia, Yongxiang
    Zhang, Xi
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS II-EXPRESS BRIEFS, 2018, 65 (01) : 115 - 119
  • [4] Robustness analysis of cyber-coupled power systems with considerations of interdependence of structures, operations and dynamic behaviors
    Gao, Xingle
    Peng, Minfang
    Tse, Chi K.
    [J]. PHYSICA A-STATISTICAL MECHANICS AND ITS APPLICATIONS, 2022, 596
  • [5] Impact of wind power uncertainty on cascading failure in cyber-physical power systems
    Gao, Xingle
    Peng, Minfang
    Tse, Chi K.
    [J]. PHYSICA A-STATISTICAL MECHANICS AND ITS APPLICATIONS, 2021, 583
  • [6] Cascading Failure Analysis of CyberPhysical Power Systems Considering Routing Strategy
    Gao, Xingle
    Peng, Minfang
    Tse, Chi K.
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS II-EXPRESS BRIEFS, 2023, 70 (01) : 136 - 140
  • [7] A Stochastic Model of Cascading Failure Dynamics in Cyber-Physical Power Systems
    Gao, Xingle
    Peng, Minfang
    Tse, Chi K.
    Zhang, Haiyan
    [J]. IEEE SYSTEMS JOURNAL, 2020, 14 (03): : 4626 - 4637
  • [8] Small Cluster in Cyber Physical Systems: Network Topology, Interdependence and Cascading Failures
    Huang, Zhen
    Wang, Cheng
    Nayak, Amiya
    Stojmenovic, Ivan
    [J]. IEEE TRANSACTIONS ON PARALLEL AND DISTRIBUTED SYSTEMS, 2015, 26 (08) : 2340 - 2351
  • [9] A Tutorial on Modeling and Analysis of Cascading Failure in Future Power Grids
    Liu, Dong
    Zhang, Xi
    Tse, Chi K.
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS II-EXPRESS BRIEFS, 2021, 68 (01) : 49 - 55
  • [10] Cascading Failure of Cyber-Coupled Power Systems Considering Interactions Between Attack and Defense
    Liu, Dong
    Tse, Chi K.
    [J]. IEEE TRANSACTIONS ON CIRCUITS AND SYSTEMS I-REGULAR PAPERS, 2019, 66 (11) : 4323 - 4336