Surface Charging and Flashover Characteristics of DC-GIS Epoxy Insulators Under AC-DC Composite Voltage

被引:5
作者
Li, Jin [1 ]
Wang, Yuhuai [1 ]
Duan, Xiaohui [2 ]
Wei, Jianwei [2 ]
Wang, Yaxiang [2 ]
Liang, Hucheng [1 ]
Du, Boxue [1 ]
机构
[1] Tianjin Univ, Sch Elect & Informat Engn, Key Lab Smart Grid Educ Minist, Tianjin 300072, Peoples R China
[2] PinggaoGroup Co Ltd, Pingdingshan 467001, Peoples R China
基金
中国国家自然科学基金;
关键词
Surface charging; Insulators; Flashover; Voltage measurement; Surface treatment; Insulation; Conductivity; AC-DC composite voltage; dc-gas-insulated switchgear (GIS); epoxy insulator; flashover voltage; fluorination; surface charge; POLARITY REVERSAL; TEMPERATURE;
D O I
10.1109/TDEI.2022.3221379
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, the surface charge distribution and flashover characteristics of epoxy basin insulators under ac-dc composite voltage with specific proportions in a down-sized dc-gas-insulated switchgear (GIS) are investigated by experiments. Results show that more heteropolar charges are observed on the insulator surface and tend to diffuse toward the central high-voltage electrode with increasing the composite voltage amplitude. Higher prestressing would result in a decline of the ac component but lifting of the absolute amplitude of the flashover voltage. With direct ramp voltage stressing, the insulators present higher flashover voltage than that with prestressing. Besides, the higher the component of ac voltage, the easier the surface flashover. The surface modification of the insulators is performed by direct fluorination. The surface charge distribution and flashover voltage of the fluorinated insulator are improved due to the increase in surface conductivity. It is confirmed that ac/dc superimposed voltage would have significant effects on the insulation performance of dc-GIS and direct fluorination is an effective method to improve the flashover voltage.
引用
收藏
页码:787 / 794
页数:8
相关论文
共 50 条
  • [31] DC Surface Flashover Characteristics on Polyimide Under Different Temperature in Vacuum
    Zhang, Zhen-Jun
    Zheng, Xiao-Quan
    Wu, Wen-Bin
    Yang, Pei
    Peng, Ping
    2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 468 - 471
  • [32] Breakdown Characteristics of Converter Transformer Insulation under Composite AC and DC Voltage
    Wang, Yonghong
    Wei, Xinlao
    Chen, Qingguo
    Huang, Yongrui
    Nie, Hongyan
    ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 634 - 637
  • [33] Understanding the effect of SiC/epoxy coating on surface flashover under DC voltage: from surface charge accumulation
    Han, Pu
    Pan, Zijun
    Mao, Shiyi
    Ye, Yuhan
    Tang, Ju
    Pan, Cheng
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2023, 56 (40)
  • [34] Understanding Effects of Deep Traps on DC Surface Flashover Characteristics of Epoxy/MWCNTs-TiO2 Nanocomposites in a Vacuum
    Li, Zhen
    Ma, Kaiyue
    Li, Bingnan
    Wang, Xiaoping
    Li, Mingru
    Liu, Ji
    Li, Shengtao
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (05) : 1838 - 1846
  • [35] Influence of polluting methods on icing and flashover characteristics of 220 kV composite insulators under ac working voltage
    State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Shapingba District, Chongqing
    400044, China
    不详
    400015, China
    Zhongguo Dianji Gongcheng Xuebao, 18 (4817-4824): : 4817 - 4824
  • [36] Gaseous Ionization Dependence of Surface Charge Pattern on Epoxy Insulator With Complex Surface Profile Under DC Voltage
    Gao, Yu
    Wang, Huan
    Li, Ziyi
    Yuan, Xiaochen
    Zhao, Huicun
    IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (05) : 1627 - 1635
  • [37] Negative DC flashover characteristics of alumina filled epoxy resin insulators in SF6
    Li, Peng
    Li, Jinzhong
    Zhang, Qiaogen
    Zhao, Junping
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2014, 34 (36): : 6523 - 6529
  • [38] AC Icing Flashover Characteristics and Maximum Withstand Voltage Gradient of 220 kV Polluted Composite Insulators
    Wang, Huan
    Hu, Qin
    Shu, Lichun
    Yin, Pancheng
    Wu, Yufan
    Jiang, Xingliang
    Yu, Zhou
    Wang, Li
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (04) : 2161 - 2168
  • [39] Enhancement of DC Flashover Voltage of Epoxy Insulators and Gap Breakdown Voltage in SF6 Gas by Direct Fluorination of Metal Electrodes
    Liu, Xuguang
    An, Zhenlian
    Lan, Haiquan
    Zhang, Chenglong
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (01) : 22 - 30
  • [40] Surface Charge and Flashover Voltage of Fluorinated Polypropylene Film under DC and Pulse Voltages
    Du, B. X.
    Xu, R. R.
    Li, Jin
    Han, C. L.
    Wang, M. Y.
    2018 IEEE 2ND INTERNATIONAL CONFERENCE ON DIELECTRICS (ICD), 2018,