Surface Charging and Flashover Characteristics of DC-GIS Epoxy Insulators Under AC-DC Composite Voltage

被引:5
|
作者
Li, Jin [1 ]
Wang, Yuhuai [1 ]
Duan, Xiaohui [2 ]
Wei, Jianwei [2 ]
Wang, Yaxiang [2 ]
Liang, Hucheng [1 ]
Du, Boxue [1 ]
机构
[1] Tianjin Univ, Sch Elect & Informat Engn, Key Lab Smart Grid Educ Minist, Tianjin 300072, Peoples R China
[2] PinggaoGroup Co Ltd, Pingdingshan 467001, Peoples R China
基金
中国国家自然科学基金;
关键词
Surface charging; Insulators; Flashover; Voltage measurement; Surface treatment; Insulation; Conductivity; AC-DC composite voltage; dc-gas-insulated switchgear (GIS); epoxy insulator; flashover voltage; fluorination; surface charge; POLARITY REVERSAL; TEMPERATURE;
D O I
10.1109/TDEI.2022.3221379
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, the surface charge distribution and flashover characteristics of epoxy basin insulators under ac-dc composite voltage with specific proportions in a down-sized dc-gas-insulated switchgear (GIS) are investigated by experiments. Results show that more heteropolar charges are observed on the insulator surface and tend to diffuse toward the central high-voltage electrode with increasing the composite voltage amplitude. Higher prestressing would result in a decline of the ac component but lifting of the absolute amplitude of the flashover voltage. With direct ramp voltage stressing, the insulators present higher flashover voltage than that with prestressing. Besides, the higher the component of ac voltage, the easier the surface flashover. The surface modification of the insulators is performed by direct fluorination. The surface charge distribution and flashover voltage of the fluorinated insulator are improved due to the increase in surface conductivity. It is confirmed that ac/dc superimposed voltage would have significant effects on the insulation performance of dc-GIS and direct fluorination is an effective method to improve the flashover voltage.
引用
收藏
页码:787 / 794
页数:8
相关论文
共 50 条
  • [1] Surface flashover characteristics of oil-paper insulation under combined AC-DC voltage
    Zhou, Yuanxiang
    Jin, Fubao
    Sun, Qinghua
    Sha, Yanchao
    Huang, Meng
    PROCEEDINGS OF THE 2013 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2013), VOLS 1 AND 2, 2013, : 1005 - 1008
  • [2] Resistance Characteristics and Electrification Characteristics of GIS Epoxy Insulators under DC Voltage
    Okabe, Shigemitsu
    Ueta, Genyo
    Nojima, Kenichi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (03) : 1260 - 1267
  • [3] Electric Conductivity Characteristics of FRP and Epoxy Insulators for GIS under DC Voltage
    Ueta, Genyo
    Okabe, Shigemitsu
    Utsumi, Tomoaki
    Nukaga, Jun
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (04) : 2320 - 2328
  • [4] High Voltage DC Partial Discharge and Flashover Characteristics with Surface Charging on Solid Insulators in Air
    Takabayashi, K.
    Nakane, R.
    Okubo, H.
    Kato, K.
    IEEE ELECTRICAL INSULATION MAGAZINE, 2018, 34 (05) : 18 - 26
  • [5] CALCULATION OF DC AND AC FLASHOVER VOLTAGE OF POLLUTED INSULATORS
    GUAN, ZC
    ZHANG, R
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1990, 25 (04): : 723 - 729
  • [6] DC FLASHOVER VOLTAGE CHARACTERISTICS OF CONTAMINATED INSULATORS
    FUJIMURA, T
    NAITO, K
    SUZUKI, Y
    IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1981, 16 (03): : 189 - 198
  • [7] Insulation Characteristics of GIS Epoxy Insulators with Non-uniform Surface Resistance under DC Voltage
    Okabe, Shigemitsu
    Ueta, Genyo
    Nojima, Kenichi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (01) : 516 - 525
  • [8] Surface Flashover Phenomenon of Aged Oil-paper Insulation Induced by DC Voltage Preloading Under the Combined AC-DC Voltage
    Jin F.
    Zhou Y.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (10): : 4421 - 4428
  • [9] Atmosphere Dependence of DC Surface Flashover Voltage of Insulators
    Zhang, Zhenjun
    Ji, Qingqun
    Zhu, Zhenhua
    Shen, Qinghe
    Han, Jianqiang
    Li, Na
    2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020), 2020, : 1350 - 1354
  • [10] Flashover Performance of Polluted Composite Insulators Under AC and Hybrid AC/DC Field Stress
    Saadati, Hassan
    Werle, Peter
    Gockenbach, Ernst
    Borsi, Hossein
    Seifert, Jens Martin
    2016 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2016, : 170 - 173