Indoor Climate Monitoring in Office Buildings-Comparative Analysis of Two Office Buildings without Air Conditioning

被引:1
|
作者
Voss, Karsten [1 ]
Voss, Tjado [1 ]
Kaliga, Marvin [1 ]
机构
[1] Univ Wuppertal, Fac Architecture & Civil Engn, Pauluskirchstr 7, D-42285 Wuppertal, Germany
关键词
thermal comfort; indoor air quality; passive cooling; ceiling fans; monitoring; commercial buildings; energy efficiency; ENERGY PERFORMANCE; COMFORT; QUALITY;
D O I
10.3390/en16196790
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Against the background of climate protection and the rising costs of a fossil-fuel-based energy supply, the interest in the energy performance and indoor climate of buildings in real operation is rising. This paper, therefore, deals with the indoor climate investigation of two medium-sized office buildings in Germany by taking measurements over a whole year. These relate to one new building and one refurbished building. Sensors of various types were installed and operated in a large number of office rooms, so that in total results are available for over 100 rooms, typically occupied by one or two persons. The analysis focuses on the indoor temperature in summer and the air quality in winter based on the CO2 concentration. The comfort classes according to DIN EN 16798 including the adaptive comfort approach are used as a basis to cluster the results. Both buildings have movable sun protection and openable windows but no facilities for active cooling. They, thus, represent a large number of existing 'low tech' office buildings in Germany and central Europe. The results reflect the respective building concepts but also show a wide range between the rooms due to the user preferences and behaviour. The refurbished building shows better results, especially in terms of air quality but also in terms of summer room temperatures. This underlines the benefit of the targeted measures as a result of an analysis of the deficits in the existing building before the refurbishment. The additional measures for decentralised mechanical ventilation and passive cooling are having positive effects. As part of the projects, further measures to improve the indoor climate were investigated in both buildings. In one case, this involved CO2 traffic lights to stimulate personal window ventilation in winter, and in the other, the use of newly developed individual ceiling fans supports convective heat dissipation on the human body during hot spells in summer. The positive effect could be demonstrated for both measures.
引用
收藏
页数:17
相关论文
共 50 条
  • [41] Association of subjective health symptoms with indoor air quality in European office buildings: The OFFICAIR project
    Sakellaris, Ioannis
    Saraga, Dikaia
    Mandin, Corinne
    de Kluizenaar, Yvonne
    Fossati, Serena
    Spinazze, Andrea
    Cattaneo, Andrea
    Mihucz, Victor
    Szigeti, Tamas
    Fernandes, Eduardo de Oliveira
    Kalimeri, Krystallia
    Mabilia, Rosanna
    Carrer, Paolo
    Bartzis, John
    INDOOR AIR, 2021, 31 (02) : 426 - 439
  • [42] Effects of indoor plants on CO2 concentration, indoor air temperature and relative humidity in office buildings
    Jiang, Junzhiwei
    Irga, Peter
    Coe, Robert
    Gibbons, Philip
    PLOS ONE, 2024, 19 (07):
  • [43] Fresh air rate in air conditioning buildings and indoor air quality
    Pei Qing-qing
    Liu Wei
    Zhou Zhi-ming
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2007, 14 : 95 - 98
  • [44] Evaluation and analysis of energy consumption in office buildings
    Maas, Stefan
    Scholzen, Frank
    Thewes, Andreas
    Waldmann, Daniele
    Zuerbes, Arno
    BAUPHYSIK, 2011, 33 (03) : 158 - 166
  • [45] Energy performance of direct expansion air handling unit in office buildings
    Yun, Geun Young
    Choi, Jongdae
    Kim, Jeong Tai
    ENERGY AND BUILDINGS, 2014, 77 : 425 - 431
  • [46] Global sensitivity analysis of fan coil air conditioning demand response-A case study of medium-sized office buildings
    Song, Jiaming
    Peng, Jinqing
    Cao, Jingyu
    Yin, Rongxin
    He, Yingdong
    Zou, Bin
    Zhao, Wanfang
    APPLIED THERMAL ENGINEERING, 2023, 230
  • [47] Visual and energy performance of glazed office buildings in Mediterranean climate
    Ierardi L.
    Liuzzi S.
    Stefanizzi P.
    Stefanizzi, Pietro (pietro.stefanizzi@poliba.it), 1600, International Information and Engineering Technology Association (35): : S252 - S260
  • [48] Building occupants' psycho-physiological response to indoor climate and CO2 concentration changes in office buildings
    Kim, Jimin
    Hong, Taehoon
    Kong, Minjin
    Jeong, Kwangbok
    BUILDING AND ENVIRONMENT, 2020, 169
  • [49] The study of indoor particulate matter in office buildings based on artificial intelligence
    Soleimani-Alyar, S.
    Soleimani-Alyar, M.
    Yarahmadi, R.
    Beyk-Mohammadloo, P.
    Fazeli, P.
    INTERNATIONAL JOURNAL OF ENVIRONMENTAL SCIENCE AND TECHNOLOGY, 2025, 22 (07) : 5763 - 5776
  • [50] Forecast of air-conditioning duration in office buildings in summer using machine learning and Bayesian theories
    Zhong, YuanXiang
    Knefaty, Ala Deen
    Chen, GaoXiang
    Yao, Jian
    Zheng, RongYue
    JOURNAL OF BUILDING ENGINEERING, 2022, 61