Research into a Method of Forming Neutral Point Voltage in a Three-Phase Four-Wire Voltage Inverter

被引:0
作者
Dar'enkov, Andrey [1 ]
Kurkin, Andrey [2 ]
Sluzov, Anton [1 ]
Berdnikov, Ivan [1 ]
Khramov, Anton [1 ]
Shalukho, Andrey [1 ]
机构
[1] Nizhnii Novgorod State Tech Univ, Elect Power Inst, Nizhnii Novgorod 603155, Russia
[2] Nizhnii Novgorod State Tech Univ, Dept Appl Math, Nizhnii Novgorod 603950, Russia
关键词
voltage inverter; space vector pulse width modulation; four leg inverter; neutral point modulation; zero voltage switching; total harmonic distortion; POWER QUALITY ENHANCEMENT;
D O I
10.3390/en16155739
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Three-phase four-wire voltage inverters are commonly used in energy complexes based on distributed generation sources (solar panels, wind power plants, hydrogen fuel cells) and accumulator batteries. They allow to power loads, including single-phase ones, which require neutral point connection. In these cases, phase voltage formed by spatial pulse-width modulation (PWM) methods considerably differs from sinusoidal waves and has high total harmonic distortions of voltage and current curves. This article is devoted to research into the authors' control method of a three-phase four-wire inverter, allowing for the rectification of the form of phase voltage supplying the load when applying the most common PWM (SVPWM, DPWMMIN, DPWMMAX, GDPWM) methods. The description of the method and its research results by simulation modeling and test bench are presented in the article. The simulation modeling was carried out by the developed Simulink-model of the three-phase four-wire inverter and its control system. The modeling results showed that the method application ensures sinusoidal voltage form when applying any PWM method. At this, THDU was reduced from 21.56% to 4.39%, while THDI was reduced from 21.16% to 1.69%. Experimental tests were carried out by a test bench featuring an uninterruptible power supply source. The authors researched the inverter operation as a component of the test bench under the control of the proposed method to form neutral point voltage. The experimental test results coincided with the simulation modeling results.
引用
收藏
页数:19
相关论文
共 21 条
[1]   Study on the Novel Generalized Discontinuous SVPWM Strategies for Three-Phase Voltage Source Inverters [J].
An, Shao-Liang ;
Sun, Xiang-Dong ;
Zhang, Qi ;
Zhong, Yan-Ru ;
Ren, Bi-Ying .
IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2013, 9 (02) :781-789
[2]   Minimization and Redistribution of Switching Losses Using Predictive PWM Strategy in a Voltage Source Inverter [J].
Anuchin, Alecksey ;
Aliamkin, Dmitry ;
Lashkevich, Maxim ;
Shpak, Dmitry ;
Zharkov, Alexandr ;
Briz, Fernando .
2018 25TH INTERNATIONAL WORKSHOP ON ELECTRIC DRIVES: OPTIMIZATION IN CONTROL OF ELECTRIC DRIVES (IWED2018), 2018,
[3]  
Chivenkov A., 2018, INTELL ELECT ENG, V1, P112, DOI [10.46960/2658-6754_2018_1_112, DOI 10.46960/2658-6754_2018_1_112]
[4]   Research and Development of Adjustable Discontinuous Pulse Width Modulation Method for Three-Phase Voltage Source Inverter [J].
Dar'enkov, Andrey ;
Sokolov, Victor ;
Sluzov, Anton ;
Berdnikov, Ivan ;
Shalukho, Andrey .
ENERGIES, 2022, 15 (20)
[5]   Distributed Control Strategies for Microgrids: An Overview [J].
Espina, Enrique ;
Llanos, Jacqueline ;
Burgos-Mellado, Claudio ;
Cardenas-Dobson, Roberto ;
Martinez-Gomez, Manuel ;
Saez, Doris .
IEEE ACCESS, 2020, 8 :193412-193448
[6]  
Garganeev AG, 2019, INT CONF SEMINAR, P558, DOI [10.1109/EDM.2019.8823098, 10.1109/edm.2019.8823098]
[7]   Improved control strategy for power quality enhancement in standalone systems based on four-leg voltage source inverters [J].
Houari, Azeddine ;
Djerioui, Ali ;
Saim, Abdelhakim ;
Ait-Ahmed, Mourad ;
Machmoum, Mohamed .
IET POWER ELECTRONICS, 2018, 11 (03) :515-523
[8]   Novel Common Mode Voltage Elimination Methods in Three-Phase Four-Wire Grid-Connected Inverters [J].
Julian, Alexander L. ;
Oriti, Giovanna .
2021 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2021, :2873-2880
[9]   Development and Operation Modes of Hydrogen Fuel Cell Generation System for Remote Consumers' Power Supply [J].
Kulikov, Aleksandr ;
Loskutov, Aleksey ;
Kurkin, Andrey ;
Dar'enkov, Andrey ;
Kozelkov, Andrey ;
Vanyaev, Valery ;
Shahov, Andrey ;
Shalukho, Andrey ;
Bedretdinov, Rustam ;
Lipuzhin, Ivan ;
Kryukov, Evgeny .
SUSTAINABILITY, 2021, 13 (16)
[10]   Microgrid power quality enhancement using a three-phase four-wire grid-interfacing compensator [J].
Li, YW ;
Vilathgamuwa, DM ;
Loh, PC .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2005, 41 (06) :1707-1719