Performance comparison of module layout for the mechanical draft wet cooling tower br

被引:4
作者
Deng, Weipeng [1 ]
Sun, Fengzhong [1 ]
Wang, Yuhao [1 ]
Zhang, Zhihui [1 ]
机构
[1] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
Plume abatement; Water saving; Rhombus module; Rectangular module; Mechanical draft wet cooling tower; PLUME ABATEMENT; THERMAL PERFORMANCE; REDUCE WATER; OPTIMIZATION;
D O I
10.1016/j.icheatmasstransfer.2022.106600
中图分类号
O414.1 [热力学];
学科分类号
摘要
The arrangement of modules with the plume abatement and water saving functions has a great impact on the performance of the mechanical draft wet cooling tower (MCT). The rectangular and rhombus modules are compared by the experiment in this study. The layout of modules in the MCT is divided into single-sided layout and double-sided layout. The ability of MCT to plume abatement, water saving rate, and thermal performance are analyzed. Results show that the MCT with rhombus modules has better ventilation capacity, and that is increased by at least 7.6% compared with the rectangular module. The water saving rate of the rhombus module is at least 5.6% higher than that of installing a rectangular module. After the rhombus module is installed, the temperature and moisture content of air discharged from the MCT decrease amount more than that of the rectangular module, and the plume abatement ability of the rhombic module is better than that of the rectangular module. Compared with the rectangular module, the water temperature drop with the rhombus module is increased by 0.2 degrees C on the single-sided layout module and 0.5 degrees C on the double-sided layout module
引用
收藏
页数:12
相关论文
共 50 条
  • [11] Comparison on the cooling performance of mechanical draft dry cooling towers pre-cooled with nozzle spray and wet medium
    Zhao, Cuilin
    Wang, Mingwei
    Gao, Qi
    Cheng, Shen
    Liu, Zhilan
    Geng, Zhe
    Zhang, Shuzhen
    He, Suoying
    Qi, Jianhui
    Han, Kuihua
    Gao, Ming
    Shi, Yuetao
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 298 - 314
  • [12] New retrofit method to cooling capacity improvement of mechanical draft wet cooling tower group
    Deng, Weipeng
    Sun, Fengzhong
    Chen, Kun
    Zhang, Xiaoyu
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 188
  • [13] Performance investigation of the natural draft wet cooling tower at different wet-bulb temperatures
    Raj, Gaurav
    Chandra, Prakash
    Pathak, Piyush Kumar
    INTERNATIONAL JOURNAL OF AMBIENT ENERGY, 2021, : 5864 - 5872
  • [14] Numerical study of natural draft wet cooling tower
    Zheng Shuihua
    Jin Tai
    Fan Jianren
    MEMS, NANO AND SMART SYSTEMS, PTS 1-6, 2012, 403-408 : 3191 - 3194
  • [15] Thermal optimization of a natural draft wet cooling tower
    Williamson, N.
    Behnia, M.
    Armfield, S. W.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (14) : 1349 - 1361
  • [16] Parallel hybrid model for mechanical draft counter flow wet-cooling tower
    Guo, Yuming
    Wang, Fuli
    Jia, Mingxing
    Zhang, Shuning
    APPLIED THERMAL ENGINEERING, 2017, 125 : 1379 - 1388
  • [17] A Comprehensive Approach to an Optimum Design and Simulation Model of a Mechanical Draft Wet Cooling Tower
    Panjeshahi, Mohammad Hassan
    Ataei, Abtin
    Gharaie, Mona
    IRANIAN JOURNAL OF CHEMISTRY & CHEMICAL ENGINEERING-INTERNATIONAL ENGLISH EDITION, 2010, 29 (01): : 21 - 32
  • [18] DYNAMIC MODELING OF MECHANICAL DRAFT COUNTER-FLOW WET COOLING TOWER WITH MODELICA
    Li, Xiao
    Li, Yaoyu
    Seem, John E.
    PROCEEDINGS OF THE ASME DYNAMIC SYSTEMS AND CONTROL CONFERENCE 2010, VOL 2, 2010, : 687 - 694
  • [19] Influence of non-uniform layout fillings on thermal performance for wet cooling tower
    Gao, Ming
    Zhang, Lei
    Wang, Ni-ni
    Shi, Yue-tao
    Sun, Feng-zhong
    APPLIED THERMAL ENGINEERING, 2016, 93 : 549 - 555
  • [20] Optimization of guide vane positions in bended inflow of mechanical draft wet-cooling tower
    Klimanek, Adam
    Musiol, Tomasz
    Stechman, Adam
    ARCHIVES OF THERMODYNAMICS, 2011, 32 (03) : 263 - 272