High pass filter based traveling wave method for fault location in VSC-Interfaced HVDC system

被引:6
作者
Javaid, Samreen [1 ]
Li, Dongyu [1 ]
Ukil, Abhisek [1 ]
机构
[1] Univ Auckland, Dept Elect Comp & Software Engn, 3 Grafton Rd, Auckland 1010, New Zealand
关键词
High voltage direct current(HVDC); Traveling wave(TW); Wavelet transform(WT); Voltage source converter(VSC); High pass filter(HPF); Pulse width modulation(PWM);
D O I
10.1016/j.epsr.2023.110004
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Due to the difficult topography and bad weather conditions across large distances, dc line breakdown is a serious danger to the safety of high-voltage direct-current systems (HVDC). Thus, there is a need of an accurate and reliable fault location method to safely isolate the dc grid in the occurrence of a dc fault. Traveling wave (TW) fault location techniques have gained in popularity over the decades, with the expectation that power networks will become considerably more credible and accurate throughout. However, in the existing traveling wave based location, the signal processing methodology for extracting the wave front consumes too many computer resources, necessitating the development of a new location method with a fast response and high accuracy. In this paper, a new algorithm of TW based on high pass filter is proposed, it can differentiate the TW peak more easily by removing the oscillation in a signal. To ensure more accuracy double ended method (Type D) is used to obtain the location for the fault. The theory behind this new algorithm is presented in detail. High pass filter is designed for this purpose and its validity tested on point to point (P2P) dc simulation model which is created in PSCAD software to gather the voltage data from both terminals during transient. Following that the proposed fault location algorithm is executed in the MATLAB environment to get the fault location results. A comparison of the proposed algorithm with two popular methods namely the wavelet transforms (WT) and the single ended method highlights the superiority.
引用
收藏
页数:13
相关论文
共 38 条
[1]   Design of digital IIR filter: A research survey [J].
Agrawal, N. ;
Kumar, A. ;
Bajaj, Varun ;
Singh, G. K. .
APPLIED ACOUSTICS, 2021, 172
[2]   Fault location in overhead transmission line: A novel non-contact measurement approach for traveling wave-based scheme [J].
Anane, Paul Oswald Kwasi ;
Huang, Qi ;
Bamisile, Olusola ;
Ayimbire, Patrick Nyaaba .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 133
[3]   DEVELOPMENT AND FIELD-DATA EVALUATION OF SINGLE-END FAULT LOCATOR FOR 2-TERMINAL HVDC TRANSMISSION-LINES .1. DATA-COLLECTION SYSTEM AND FIELD DATA [J].
ANDO, M ;
SCHWEITZER, EO ;
BAKER, RA .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (12) :3524-3530
[4]  
Chen P., 2006, INT C POW SYST TECHN, P1
[5]   Travelling Wave Based Fault Location Analysis for Transmission Lines [J].
de Andrade, L. ;
Ponce de Leao, T. .
2ND EUROPEAN ENERGY CONFERENCE, 2012, 33
[6]   THE APPLICATION OF SATELLITE TIME REFERENCES TO HVDC FAULT LOCATION [J].
DEWE, MB ;
SANKAR, S ;
ARRILLAGA, J .
IEEE TRANSACTIONS ON POWER DELIVERY, 1993, 8 (03) :1295-1302
[7]  
Dong X., 2003, IPST2003
[8]  
E.U. Guide, 2003, Manitoba hvdc research centre inc
[9]   A Novel Fault-Location Method for HVDC Transmission Lines Based on Similarity Measure of Voltage Signals [J].
Farshad, Mohammad ;
Sadeh, Javad .
IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) :2483-2490
[10]   VSC-Based HVDC Power Transmission Systems: An Overview [J].
Flourentzou, Nikolas ;
Agelidis, Vassilios G. ;
Demetriades, Georgios D. .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2009, 24 (3-4) :592-602