Ammonia-based hybrid chemisorption-compression heat pump for high-temperature heating

被引:6
|
作者
Xie, Xiangyu [1 ]
Jin, Shengxiang [1 ]
Gao, Peng [1 ]
Wu, Weidong [1 ]
Yang, Qiguo [1 ]
Wang, Liwei [2 ]
机构
[1] Univ Shanghai Sci & Technol, Sch Energy & Power Engn, Shanghai 200093, Peoples R China
[2] Shanghai Jiao Tong Univ, Key Lab Power Machinery & Engn, Minist Educ, Shanghai 200240, Peoples R China
基金
中国国家自然科学基金;
关键词
Chemisorption heat pump; Hybrid cycle; High-temperature heating; Regulation strategy; Waste heat recovery; WATER-VAPOR COMPRESSION; WASTE HEAT; SYSTEM; REFRIGERANTS; RECOVERY; STATE;
D O I
10.1016/j.applthermaleng.2023.121081
中图分类号
O414.1 [热力学];
学科分类号
摘要
Conventional compression heat pumps employing natural refrigerant of ammonia can barely meet the requirement of high-temperature heating above 90 & DEG;C, while ammonia-based chemisorption heat transformers characterised by high-temperature heating require driving heat source temperature above 80 & DEG;C. To address these issues, a novel ammonia-based hybrid chemisorption-compression high-temperature heat pump employing SrCl2NH3 as the working pair is designed and established in this paper. Particularly, a conventional normal temperature compressor instead of an expensive high-pressure ammonia compressor can be adopted to upgrade the abundant 50-80 & DEG;C waste heat to 90-120 & DEG;C high-temperature heat. Simultaneously, due to that chemisorption reaction heat is larger than condensing heat of refrigerant, this heat pump has significant potential for improving coefficient of performance (COP). For the first time, regulation strategies of key parameters such as sorption pressure, desorption pressure, and sorption reaction exothermic time are proposed, and these provide the theoretical support for the stable and efficient operation of the heat pump. Moreover, its performance is evaluated by varying operating conditions. The results indicate that at heat output temperature of 100 & DEG;C, the optimal sorption pressure and reaction exothermic time are 1.70 MPa and 22 min, respectively. At waste heat temperature of 70 & DEG;C and heat output temperature of 110 & DEG;C, the COP of the heat pump is 4.58, i.e., its efficiency is 14.5% more than that of R245fa compression one.
引用
收藏
页数:12
相关论文
共 50 条
  • [41] Performance of a single-stage recuperative high-temperature air source heat pump
    Sun, Shoujun
    Guo, Hao
    Lu, Ding
    Bai, Yin
    Gong, Maoqiong
    APPLIED THERMAL ENGINEERING, 2021, 193
  • [42] The Exploitation of Low-Temperature Hot Water Boiler Sources with High-Temperature Heat Pump Integration
    Goricanec, Darko
    Ivanovski, Igor
    Krope, Jurij
    Urbancl, Danijela
    ENERGIES, 2020, 13 (23)
  • [43] The thermodynamic potential of high-temperature transcritical heat pump cycles for industrial processes with large temperature glides
    Vieren, Elias
    Demeester, Toon
    Beyne, Wim
    Arteconi, Alessia
    De Paepe, Michel
    Lecompte, Steven
    APPLIED THERMAL ENGINEERING, 2023, 234
  • [44] Influence of operating parameters on the COP of an R600 high-temperature heat pump
    Verdnik, Manuel
    Rieberer, Rene
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 140 : 103 - 111
  • [45] Development and analysis of a high-temperature heat pump for steam generation using hydrocarbons as refrigerants
    Hassan, Abdelrahman H.
    Paya, Jorge
    Navarro-Peris, Emilio
    15TH IIR-GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS, 2022, : 1016 - 1023
  • [46] A mass-coupled hybrid absorption-compression heat pump with output temperature of 200 °C
    Feng, Jiayu
    Gao, Jintong
    Hu, Bin
    Wang, Ruzhu
    Xu, Zhenyuan
    ENERGY, 2024, 312
  • [47] New zeotropic CO2-based refrigerant mixtures for cascade high-temperature heat pump to reach heat sink temperature up to 180 °C
    Ganesan, P.
    Eikevik, Trygve M.
    ENERGY CONVERSION AND MANAGEMENT-X, 2023, 20
  • [48] Simulation study of an open compression absorption heat pump in water and heat recovery of low-temperature and high-humidity flue gas
    Wang, Xiaozhe
    Zhang, Hao
    Cui, Lin
    Wang, Jingying
    Lee, Chunhian
    Dong, Yong
    ENERGY CONVERSION AND MANAGEMENT, 2022, 269
  • [49] Theoretical study of a high-temperature heat pump system composed of a CO2 transcritical heat pump cycle and a R152a subcritical heat pump cycle
    Yang, Wei-wei
    Cao, Xing-qi
    He, Ya-ling
    Yan, Fei-yu
    APPLIED THERMAL ENGINEERING, 2017, 120 : 228 - 238
  • [50] A study of ammonia-hydrogen-electricity cogeneration coupled to a very high-temperature heat source
    Liu, Bin
    Huang, Jingzhong
    Chen, Wei
    Liu, Wei
    Pan, Liangming
    Zhu, Longxiang
    Kang, Zongyao
    NUCLEAR ENGINEERING AND DESIGN, 2023, 414