Research on intervention PID control of VAV terminal based on LabVIEW

被引:9
作者
Cao, Shuanghua [1 ]
Zhao, Weichao [1 ]
Zhu, Anxiong [1 ]
机构
[1] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Shanghai 200093, Peoples R China
关键词
Terminal control; PID control; Intervention identification algorithm; LabVIEW; ENERGY-CONSUMPTION; SIMULATION; DESIGN;
D O I
10.1016/j.csite.2023.103002
中图分类号
O414.1 [热力学];
学科分类号
摘要
In recent years, the research on the control method of variable air volume (VAV) has been the focus of VAV air-conditioning research. Single terminal PID control is prone to overshoot in the system when the temperature difference is large. Aiming at the deficiency of single terminal PID control at the air conditioning terminal, a control method of coupling intervention control and PID control is proposed. This thesis used LabVIEW simulation and experiment to analyze the performance of terminal intervention PID control. According to the experiment, the change of room temperature after adding 1500W heat load in the room was recorded by thermocouple, and the step response of room temperature was obtained. The LabVIEW simulation program of PID and intervention PID control is established according to the characteristics of room step response. The reliability of LabVIEW simulation program was verified by experimental data, respectively. The intervention PID control and conventional PID control are simulated by LabVIEW simulation program under 1000W and 1500w load to compare their stability, anti-interference and robustness. The experiments and simulation results show that the control strategy using the intervention recognition algorithm nested with the PID algorithm has good dynamic perfor-mance, robustness, and adaptability.
引用
收藏
页数:14
相关论文
共 42 条
[1]  
Almasani S.A.M., 2015, INT J ENG RES TECHNO, V4, P808
[2]   A review of data-driven building energy consumption prediction studies [J].
Amasyali, Kadir ;
El-Gohary, Nora M. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 81 :1192-1205
[3]  
[Anonymous], 2011, IFAC P, DOI DOI 10.3182/20110828-6-IT-1002.03085
[4]  
[Anonymous], 2000, CHOICE REV ONLINE, V38, DOI [10.5860/choice.38-0348,38-0348-38-0348, DOI 10.5860/CHOICE.38-0348,38-0348-38-0348]
[5]   The future of PID control [J].
Åström, KJ ;
Hägglund, T .
CONTROL ENGINEERING PRACTICE, 2001, 9 (11) :1163-1175
[6]   The correlation coefficient:: An overview [J].
Asuero, AG ;
Sayago, A ;
González, AG .
CRITICAL REVIEWS IN ANALYTICAL CHEMISTRY, 2006, 36 (01) :41-59
[7]   Research on a hierarchical air balancing control method of variable air volume ventilation system [J].
Cai, Hui ;
Cui, Can ;
Zhang, Xin ;
Cai, Wenjian ;
Dai, Jinyang .
BUILDING AND ENVIRONMENT, 2020, 175
[8]  
Cai J, 2015, P AMER CONTR CONF, P986, DOI 10.1109/ACC.2015.7170862
[9]   Fuzzy comprehensive evaluation of human thermal comfort in simulating natural wind environment [J].
Cao, Shuang-hua ;
Ming, Pan-pan ;
Zhao, Xiao .
BUILDING AND ENVIRONMENT, 2021, 188
[10]   Numerical study on settlement characteristics of inhalable particles in under-floor air distribution system [J].
Cao, Shuanghua ;
Li, Fan ;
Li, Xin .
JOURNAL OF BUILDING ENGINEERING, 2022, 45