Performance analysis and optimization of a solar assisted heat pump-driven vacuum membrane distillation system for liquid desiccant regeneration

被引:21
作者
Su, Wei [1 ]
Li, Jiru [1 ]
Lu, Zhifei [1 ]
Jin, Xu [1 ]
Zhang, Jiayi [1 ]
Liu, Zhongyan [1 ]
Zhang, Xiaosong [2 ]
机构
[1] Northeast Elect Power Univ, Sch Energy & Power Engn, Jilin 132012, Peoples R China
[2] Southeast Univ, Sch Energy & Environm, Nanjing 210096, Peoples R China
关键词
Vacuum membrane distillation; Liquid desiccant regeneration; Solar/heat pump system; Energy analysis; Multi -objective optimization; WATER DESALINATION; ENERGY; DEHUMIDIFICATION; COLLECTOR; RECOVERY; MODULE; UNITS;
D O I
10.1016/j.enconman.2023.118047
中图分类号
O414.1 [热力学];
学科分类号
摘要
Liquid desiccant air-conditioning (LDAC) system is one of the excellent alternatives to conventional vapor compression refrigeration system due to its great energy-saving potential. However, regeneration of diluted liquid desiccant is the main energy-consuming process, and its performance plays a significant role in LDAC system. Recently vacuum membrane distillation (VMD) is becoming an emerging and promising separation process rely on the advantage of high permeate flux and low energy losses. The interest of usage solar energy techniques for feed solution heating in VMD systems is regarded as a sustainable path for membrane distillation process. In this work, a solar-driven VMD system incorporating a vapor-compression heat pump for liquid desiccant regeneration is introduced. An adapted solar/heat pump hybrid heating strategy has been devised to establish a connection between the heat-demanding process and the solar thermal supply. A comprehensive multicriteria assessment of energy, exergy, and environmental evaluation is conducted, and the influences of crucial parameters on both key components and system performance are evaluated to ensure a systematic examination. Results show that both the COP and STEC decrease obviously with the growth of the inlet solution temperature, whereas SEEC is improved abviously from 410.6 kW & sdot;h/m3 to 566.1 kW & sdot;h/m3 due to the effect of heat pump. The exergy analysis indicates that exergy losses in solar collector and stratified heat storage tank accounted for over 80 % of the total exergy losses. Additionally, single-objective optimization and multiobjective optimization are employed to explore the optimum operating conditions of key componets and whole system. Results show the ideal optimal solution can be obtained with a COP of 19.92 and a SEEC of 142.89 kW & sdot;h/m3 when the weights of COP and SEEC are taken as [0.5, 0.5].
引用
收藏
页数:27
相关论文
共 50 条
[11]   Operating characteristics and performance evaluation of carbon dioxide heat pump driven liquid desiccant dehumidification systems: A comparative study [J].
Cui, Qi ;
Qu, Hongshuo ;
Sun, Bo ;
Gao, Enyuan ;
Zhang, Xiaosong .
ENERGY CONVERSION AND MANAGEMENT, 2022, 254
[12]  
Dittus F.W., 1930, International Communications in Heat and Mass Transfer, V2, P443, DOI [DOI 10.1016/0735-1933(85)90003-X, 10.1016/0735-1933(85)90003-X]
[13]   The effect of tank geometry on thermally stratified sensible heat storage subject to low Reynolds number flows [J].
Eames, PC ;
Norton, B .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1998, 41 (14) :2131-2142
[14]   Performance evaluation of an innovative liquid desiccant air-conditioning system directly integrating a heat pump with two membrane energy exchangers [J].
Elsheniti, Mahmoud Badawy ;
Shehata, Ahmed ;
Attia, Abd El-Hamid ;
El-Maghlany, Wael .
ENERGY CONVERSION AND MANAGEMENT, 2023, 293
[15]  
GNIELINSKI V, 1976, INT CHEM ENG, V16, P359
[16]   A comprehensive review of dehumidifiers and regenerators for liquid desiccant air conditioning system [J].
Gurubalan, A. ;
Simonson, J. Carey .
ENERGY CONVERSION AND MANAGEMENT, 2021, 240
[17]  
Hottle HC., 1958, Transaction of Conference on the use of Solar Energy, V2, P74
[18]   Energetic and exergetic evaluation of flat plate solar collectors [J].
Jafarkazemi, Farzad ;
Ahmadifard, Emad .
RENEWABLE ENERGY, 2013, 56 :55-63
[19]  
Khayet M, 2011, MEMBRANE DISTILLATION: PRINCIPLES AND APPLICATIONS, P1
[20]   Solar-assisted multi-stage vacuum membrane distillation system with heat recovery unit [J].
Kim, Young-Deuk ;
Thu, Kyaw ;
Choi, Seung-Hak .
DESALINATION, 2015, 367 :161-171