Investigation on the cross-infection control performance of interactive cascade ventilation in multi-scenario of winter

被引:7
作者
Li, Han [1 ]
Lan, Yuer [1 ]
Ma, Xiuqin [1 ]
Kong, Xiangfei [1 ]
Fan, Man [1 ]
机构
[1] Hebei Univ Technol, Sch Energy & Environm Engn, Tianjin, Peoples R China
基金
中国国家自然科学基金;
关键词
COVID-19; Ventilation strategies; Interactive cascade ventilation; Cross-infection risk; Virus prevention and control performance; AIRBORNE INFECTION; STRATUM VENTILATION; RISK; TRANSMISSION; TRANSPORT; DROPLETS; OFFICE;
D O I
10.1016/j.jobe.2022.105728
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
With the wide spread of COVID-19, numerous cases demonstrate that proper ventilation method can reduce the cross-infection risk obviously. Interactive cascade ventilation (ICV) as a recently proposed ventilation method, the advantage of indoor environment construction has been proven. However, few studies are conducted to investigate the virus prevention and control characteristics of ICV, which is particularly important under epidemic normalizing. Hence, this study explored and compared the cross-infection control performance of three ventilation strategies, namely mixing ventilation (MV), stratum ventilation (SV), and interactive cascade ventilation (ICV), with a validated CFD model. A typical office was selected as the background scene, where an infected person coughs, sneezes with standing or sitting at different positions. Exposure doses, health infection risk, and disease burden (DB) were employed as the evaluation indicators under different ventilation methods of multi-scenario. The research results indicated that the average aerosol exposure dose among the human respiratory region under ICV was 0.29 g/day, which was reduced by 67 % and 50 % compared with MV and SV. In addition, only in ICV can the health infection risk meets the EPA standard. The average disease health burden for exposed persons under ICV was 0.93 x 10-6 DALYs pppy, which was 37 % and 70 % lower than SV and MV. The findings obtained from this study confirm that ICV performs excellently in reducing the cross-infection risk, providing the theoretical basis for future epidemic prevention and control.
引用
收藏
页数:23
相关论文
共 45 条
[1]   Tracer gas is a suitable surrogate of exhaled droplet nuclei for studying airborne transmission in the built environment [J].
Ai, Zhengtao ;
Mak, Cheuk Ming ;
Gao, Naiping ;
Niu, Jianlei .
BUILDING SIMULATION, 2020, 13 (03) :489-496
[2]   Emission characteristics and quantitative health risk assessment of bioaerosols in an indoor toilet after flushing under various ventilation scenarios [J].
Ali, Wajid ;
Yang, Ya-fei ;
Gong, Ling ;
Yan, Cheng ;
Cui, Bei-bei .
BUILDING AND ENVIRONMENT, 2022, 207
[3]   Improvements of air flow distribution in a freezing tunnel using Airpak [J].
Alonso, Maria Justo ;
Andresen, Trond ;
Frydenlund, Frode ;
Widell, Kristina N. .
11TH INTERNATIONAL CONGRESS ON ENGINEERING AND FOOD (ICEF11), 2011, 1 :1231-1238
[4]   Computation of zone-level ventilation requirement based on actual occupancy, plug and lighting load information [J].
Anand, Prashant ;
Cheong, David ;
Sekhar, Chandra .
INDOOR AND BUILT ENVIRONMENT, 2020, 29 (04) :558-574
[5]  
[Anonymous], 1983, Risk Assessment in the Federal Government: Managing the Process
[6]  
[Anonymous], 2012, GB50736 RUR DEV
[7]   A comparison between tracer gas and aerosol particles distribution indoors: The impact of ventilation rate, interaction of airflows, and presence of objects [J].
Bivolarova, M. ;
Ondracek, J. ;
Melikov, A. ;
Zdimal, V. .
INDOOR AIR, 2017, 27 (06) :1201-1212
[8]   Recent research on expiratory particles in respiratory viral infection and control strategies: A review [J].
Bu, Yunchen ;
Ooka, Ryozo ;
Kikumoto, Hideki ;
Oh, Wonseok .
SUSTAINABLE CITIES AND SOCIETY, 2021, 73
[9]   Sneezing and asymptomatic virus transmission [J].
Busco, Giacomo ;
Yang, Se Ro ;
Seo, Joseph ;
Hassan, Yassin A. .
PHYSICS OF FLUIDS, 2020, 32 (07)
[10]   COMPARISON OF DIFFERENT K-EPSILON MODELS FOR INDOOR AIR-FLOW COMPUTATIONS [J].
CHEN, Q .
NUMERICAL HEAT TRANSFER PART B-FUNDAMENTALS, 1995, 28 (03) :353-369