Comparative analysis and optimization of the annual performance for a novel internet data center cooling system

被引:17
作者
Anka, Selorm Kwaku [1 ]
Lamptey, Nicholas Boafo [1 ]
Choi, Jong Min [2 ]
机构
[1] Hanbat Natl Univ, Grad Sch, Dept Mech Engn, Daejeon 34158, South Korea
[2] Hanbat Natl Univ, Dept Mech Engn, Daejeon 34158, South Korea
关键词
Internet data center; Dual-mode cooling system; Performance; COP; Analysis; ENERGY-CONSUMPTION; HEAT-PIPE; DRIVEN; PUMP; REFRIGERATION; COMPRESSION; BUILDINGS; DESIGN;
D O I
10.1016/j.jobe.2023.106064
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Internet data centers generate considerable heat loads and expend up to 50% of the total facility energy. This study investigate the performance of a novel internet data center cooling system that incorporates two operating modes, namely the forced cooling mode and a free cooling mode. The study optimized the secondary fluid flow rate to select the mode change temperature for the dualmode internet data center cooling system. Performance comparison between the novel dual-mode air source internet data center cooling system and a conventional air source internet data center cooling system was studied at varying outdoor air temperature range from -4 degrees C to 35 degrees C, and using the integrated coefficient of performance rating method. The novel dual-mode system performance was slightly lower than the conventional system performance at outdoor temperatures above the mode change temperature, but the former was significantly higher than the latter at outdoor temperatures below the mode change temperature. Furthermore, the integrated coefficient of performance of the novel dual-mode internet data center cooling system represented by 41% higher value comparing with the conventional system, showing that the novel dual-mode internet data center cooling system has great prospects in significantly enhancing the annual energy savings of internet data centers.
引用
收藏
页数:16
相关论文
共 45 条
[1]  
Air Movement Control Association International Inc, 1999, ANSI/AMCA 210-99, ANSI/ ASHRAE 51-1999, P210
[2]   A review of data-driven building energy consumption prediction studies [J].
Amasyali, Kadir ;
El-Gohary, Nora M. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 81 :1192-1205
[3]   Performance optimization of an air source HVAC system for an internet data center building using the integrated COP method [J].
Anka, Selorm Kwaku ;
Mensah, Kwesi ;
Boahen, Samuel ;
Ohm, Tae In ;
Cho, Yong ;
Choi, Jong Woong ;
Choo, Sung Hoon ;
Kim, Han-Young ;
Choi, Jong Min .
JOURNAL OF BUILDING ENGINEERING, 2022, 61
[4]  
[Anonymous], Code of Conduct
[5]  
[Anonymous], 2017, 1361SI AHRI, P2111
[6]  
[Anonymous], 2007, SYMPOSIUM
[7]  
ANSI/ASHRAE, 1986, ENG AN EXP DAT, V2
[8]  
ANSI/ASHRAE Method of Testing for Rating Air-Conditioning Units Serving Data Center (DC) and Other Information Technology Equipment (ITE), 127 ANSI ASHRAE, P127
[9]  
ANSI/ASHRAE standard, 2016, PERF RAT METH REF MA
[10]  
ASHRAE Technical Committee 9.9, 2011, THERMAL GUIDELINES D