Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170

被引:11
作者
Tan, Haihui [1 ]
Xu, Lingfei [2 ]
Yang, Linlin [2 ]
Bai, Minkai [3 ]
Liu, Zhan [3 ,4 ]
机构
[1] Univ Elect Sci & Technol China, Zhongshan Inst, Sch Mech & Elect Engn, Zhongshan 528400, Peoples R China
[2] Zhongshan Candor Elect Appliances Co Ltd, Zhongshan 528427, Peoples R China
[3] China Univ Min & Technol, Dept Bldg Environm & Energy Engn, Sch Mech & Civil Engn, Xuzhou 221116, Jiangsu, Peoples R China
[4] Lund Univ, Dept Energy Sci, Fac Engn, S-22100 Lund, Sweden
关键词
Cascade refrigeration system; Natural refrigerants R290-R170; Ultralow-temperature; Experimental measure; THERMODYNAMIC ANALYSIS; SYSTEM; ENERGY; OPTIMIZATION;
D O I
10.1007/s11356-022-24310-z
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present study, the operation performance of an ultralow-temperature cascade refrigeration freezer is experimentally researched. The natural refrigerants R290-R170 are adopted as high-temperature and low-temperature fluids. The experimental test is conducted in a type laboratory with a dry bulb temperature of 32.0 degrees C and a wet bulb temperature of 26.5 degrees C. Different state monitors are set to display the system operation performance, and several temperature monitors are arranged to study the pull-down performance and temperature variations in the freezer. Based on the established experimental rig, three freezing temperatures, including - 40 degrees C, - 80 degrees C, and - 86 degrees C, are measured and compared. The results show that it takes about 240 min for the freezer to be pulled down to - 80 degrees C. During the pull-down period, different monitors all experience rapid temperature drop, and the power consumption reduces from 1461.4 W to 997.5 W. Once the target temperature is achieved, the freezer comes into periodic start-stop operation. With the set temperature ranging from - 40 degrees C to - 86 degrees C, the inlet temperature of two compressors gradually decreases, while the discharge temperature has an increase trend. The cooling effect of the pre-cooled condenser reduces with the freezing temperature, while the long connection pipe has opposite variation profile. Moreover, it is observed that for different freezing temperatures, most of the space in the freezer can be cooled down to the target temperature. It is confirmed that the present ultralow-temperature freezer can be used for the storage and transportation of COVID-19 vaccines. However, it is also found that the cascade refrigeration system is not suitable for high freezing temperature, due to high power consumption and extensive start-stop switch of refrigeration system.
引用
收藏
页码:29790 / 29806
页数:17
相关论文
共 30 条
[11]   Thermodynamic analysis of an R744-R717 cascade refrigeration system [J].
Getu, H. M. ;
Bansal, P. K. .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (01) :45-54
[12]   Energy and irreversibility analysis of a cascade refrigeration system for various refrigerant couples [J].
Kilicarslan, A. ;
Hosoz, M. .
ENERGY CONVERSION AND MANAGEMENT, 2010, 51 (12) :2947-2954
[13]   Thermodynamic analysis of optimal condensing temperature of cascade-condenser in CO2/NH3 cascade refrigeration systems [J].
Lee, Tzong-Shing ;
Liu, Cheng-Hao ;
Chen, Tung-Wei .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (07) :1100-1108
[14]  
Liu Z, 2023, J BUILD ENG, V63
[15]   Thermal performance of ice-making machine with a multi-channel evaporator [J].
Liu, Zhan ;
Tan, Haihui .
INTERNATIONAL JOURNAL OF GREEN ENERGY, 2019, 16 (07) :520-529
[16]   Experimental study on temperature distribution in an ice-making machine multichannel evaporator [J].
Liu, Zhan ;
Yan, Jia ;
Gao, Penghui ;
Tan, Haihui .
SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2019, 25 (01) :69-82
[17]   Energy and environmental comparison of two-stage solutions for commercial refrigeration at low temperature: Fluids and systems [J].
Llopis, Rodrigo ;
Sanchez, Daniel ;
Sanz-Kock, Carlos ;
Cabello, Ramon ;
Torrella, Enrique .
APPLIED ENERGY, 2015, 138 :133-142
[18]   Advanced high temperature heat pump configurations using low GWP refrigerants for industrial waste heat recovery: A comprehensive study [J].
Mateu-Royo, Carlos ;
Arpagaus, Cordin ;
Mota-Babiloni, Adrian ;
Navarro-Esbri, Joaquin ;
Bertsch, Stefan S. .
ENERGY CONVERSION AND MANAGEMENT, 2021, 229
[19]   Ultralow-temperature refrigeration systems: Configurations and refrigerants to reduce the environmental impact [J].
Mota-Babiloni, Adrian ;
Joybari, Mahmood Mastani ;
Navarro-Esbri, Joaquin ;
Mateu-Royo, Carlos ;
Barragan-Cervera, Angel ;
Amat-Albuixech, Marta ;
Moles, Francisco .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 111 :147-158
[20]  
Mouneer TA, 2021, World Journal of Engineering and Technology, V09, P309, DOI [10.4236/wjet.2021.92022, 10.4236/wjet.2021.92022, DOI 10.4236/WJET.2021.92022]