Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170

被引:11
作者
Tan, Haihui [1 ]
Xu, Lingfei [2 ]
Yang, Linlin [2 ]
Bai, Minkai [3 ]
Liu, Zhan [3 ,4 ]
机构
[1] Univ Elect Sci & Technol China, Zhongshan Inst, Sch Mech & Elect Engn, Zhongshan 528400, Peoples R China
[2] Zhongshan Candor Elect Appliances Co Ltd, Zhongshan 528427, Peoples R China
[3] China Univ Min & Technol, Dept Bldg Environm & Energy Engn, Sch Mech & Civil Engn, Xuzhou 221116, Jiangsu, Peoples R China
[4] Lund Univ, Dept Energy Sci, Fac Engn, S-22100 Lund, Sweden
关键词
Cascade refrigeration system; Natural refrigerants R290-R170; Ultralow-temperature; Experimental measure; THERMODYNAMIC ANALYSIS; SYSTEM; ENERGY; OPTIMIZATION;
D O I
10.1007/s11356-022-24310-z
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In the present study, the operation performance of an ultralow-temperature cascade refrigeration freezer is experimentally researched. The natural refrigerants R290-R170 are adopted as high-temperature and low-temperature fluids. The experimental test is conducted in a type laboratory with a dry bulb temperature of 32.0 degrees C and a wet bulb temperature of 26.5 degrees C. Different state monitors are set to display the system operation performance, and several temperature monitors are arranged to study the pull-down performance and temperature variations in the freezer. Based on the established experimental rig, three freezing temperatures, including - 40 degrees C, - 80 degrees C, and - 86 degrees C, are measured and compared. The results show that it takes about 240 min for the freezer to be pulled down to - 80 degrees C. During the pull-down period, different monitors all experience rapid temperature drop, and the power consumption reduces from 1461.4 W to 997.5 W. Once the target temperature is achieved, the freezer comes into periodic start-stop operation. With the set temperature ranging from - 40 degrees C to - 86 degrees C, the inlet temperature of two compressors gradually decreases, while the discharge temperature has an increase trend. The cooling effect of the pre-cooled condenser reduces with the freezing temperature, while the long connection pipe has opposite variation profile. Moreover, it is observed that for different freezing temperatures, most of the space in the freezer can be cooled down to the target temperature. It is confirmed that the present ultralow-temperature freezer can be used for the storage and transportation of COVID-19 vaccines. However, it is also found that the cascade refrigeration system is not suitable for high freezing temperature, due to high power consumption and extensive start-stop switch of refrigeration system.
引用
收藏
页码:29790 / 29806
页数:17
相关论文
共 30 条
[1]   Comparative thermodynamic performance analysis of a cascade refrigeration system with new refrigerants paired with CO2 [J].
Adebayo, Victor ;
Abid, Muhammad ;
Adedeji, Michael ;
Dagbasi, Mustafa ;
Bamisile, Olusola .
APPLIED THERMAL ENGINEERING, 2021, 184
[2]   Energy and Exergy Analysis of a Subcritical Cascade Refrigeration System With Internal Heat Exchangers Using Environmentally Friendly Refrigerants [J].
Aktemur, Cenker ;
Ozturk, Ilhan Tekin .
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2021, 143 (10)
[3]   Comparative energy and exergy analysis of a subcritical cascade refrigeration system using low global warming potential refrigerants [J].
Aktemur, Cenker ;
Ozturk, Ilhan Tekin ;
Cimsit, Canan .
APPLIED THERMAL ENGINEERING, 2021, 184
[4]   Experimental evaluation of a cascade refrigeration system prototype with CO2 and NH3 for freezing process applications [J].
Alberto Dopazo, J. ;
Fernandez-Seara, Jose .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2011, 34 (01) :257-267
[5]   Thermodynamic Assessment of Using Water as a Refrigerant in Cascade Refrigeration Systems With Other Environmentally Friendly Refrigerants [J].
Alkhulaifi, Yousif M. ;
Mokheimer, Esmail M. A. .
JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2022, 144 (02)
[6]   Analysis of an R744 typical booster configuration, an R744 parallel-compressor booster configuration and an R717/R744 cascade refrigeration system for retail food applications. Part 1: Thermodynamic analysis [J].
Amaris, Carlos ;
Tsamos, Konstantinos M. ;
Tassou, Savvas A. .
PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND RESOURCE USE IN FOOD CHAINS INCLUDING WORKSHOP ON ENERGY RECOVERY CONVERSION AND MANAGEMENT;ICSEF 2018, 2019, 161 :259-267
[7]  
[Anonymous], 2014, ASHRAE Handbook Refrigeration, VSI
[8]   Energy evaluation of R152a as drop in replacement for R134a in cascade refrigeration plants [J].
Cabello, R. ;
Sanchez, D. ;
Llopis, R. ;
Catalan, J. ;
Nebot-Andres, L. ;
Torrella, E. .
APPLIED THERMAL ENGINEERING, 2017, 110 :972-984
[9]   Experimental performance analysis of a packaged R290 refrigeration unit retrofitted with R170 for ultra-low temperature freezing [J].
Carlos Rodriguez-Criado, Juan ;
Antonio Exposito-Carrillo, Jose ;
Peris Perez, Bernardo ;
Dominguez-Munoz, Fernando .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 134 :105-114
[10]   Multi-objective optimization of a cascade refrigeration system: Exergetic, economic, environmental, and inherent safety analysis [J].
Eini, Saeed ;
Shahhosseini, Hamidreza ;
Delgarm, Navid ;
Lee, Moonyong ;
Bahadori, Alireza .
APPLIED THERMAL ENGINEERING, 2016, 107 :804-817