Phase-Shifted Full Bridge DC-DC Converter for Photovoltaic MVDC Power Collection Networks

被引:6
作者
Metayer, Pierre Le [1 ,2 ]
Loeuillet, Quentin [1 ]
Wallart, Francois [1 ]
Buttay, Cyril [2 ]
Dujic, Drazen [3 ]
Dworakowski, Piotr [1 ]
机构
[1] SuperGrid Inst, F-69100 Villeurbanne, France
[2] Univ Claude Bernard Lyon 1, Ecole Cent Lyon, Ctr Natl Rech Sci CNRS, Ampere Lab,Inst Natl Sci Appl INSA Lyon,UMR5005, F-69621 Villeurbanne, France
[3] Ecole Polytech Fed Lausanne EPFL, Power Elect Lab, CH-1015 Lausanne, Switzerland
关键词
DC-DC power converters; Voltage control; Circuit faults; Topology; Photovoltaic systems; Medium voltage; Inductance; photovoltaic systems; medium voltage; SMALL-SIGNAL ANALYSIS;
D O I
10.1109/ACCESS.2023.3247952
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
The connection of photovoltaic sources to a medium voltage dc collection network requires a dc-dc converter having specific grid-connected converter capabilities. This article presents the application of a phase-shifted full bridge (PSFB) converter for medium voltage dc collection networks suited to photovoltaic power plants. The unidirectional structure of the converter is beneficial in terms of cost and simplicity of hardware implementation of the MV circuit components. The design of the PSFB converter is presented considering ratings of 250 kW power, 1.2 kV input, and 20 kV output. A converter model and a novel PSFB input voltage control regulating the dc-link voltage are developed and verified. A tuning method is given taking into account the effect of different transformer leakage inductance values. The behaviour of the PSFB under the PV power production profile and MV network faults is studied in simulation and verified against a reduced-scale prototype with ratings of 30 kW and 350 V / 600 V operating at 20 kHz. The experimental verification of the control is performed considering a real PV power profile. The experimental results under faults show the same response as in simulations. The PSFB fault response is observed to be superior compared to other dc-dc topologies with capacitive output filter only, making it suitable for grid-connected operation.
引用
收藏
页码:19039 / 19048
页数:10
相关论文
共 38 条
[1]  
[Anonymous], 2016, HIGH RES SOL RAD DAT
[2]  
[Anonymous], 2018, ABB STRING INVERTERS
[3]  
[Anonymous], 2019, SG250HX MULTIMPPT ST
[4]   Topologies for large scale photovoltaic power plants [J].
Cabrera-Tobar, Ana ;
Bullich-Massague, Eduard ;
Araguees-Penalba, Monica ;
Gomis-Bellmunt, Oriol .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2016, 59 :309-319
[5]   Minimum DC-Link Voltage Control for Efficiency and Reliability Improvement in PV Inverters [J].
Callegari, Joao Marcus Soares ;
Cupertino, Allan Fagner ;
Ferreira, Victor de Nazareth ;
Pereira, Heverton Augusto .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2021, 36 (05) :5512-5520
[6]   A 3-PHASE SOFT-SWITCHED HIGH-POWER-DENSITY DC-DC CONVERTER FOR HIGH-POWER APPLICATIONS [J].
DEDONCKER, RWAA ;
DIVAN, DM ;
KHERALUWALA, MH .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1991, 27 (01) :63-73
[7]   An Enhanced Model for Small-Signal Analysis of the Phase-Shifted Full-Bridge Converter [J].
Di Capua, Giulia ;
Shirsavar, Seyed Ali ;
Hallworth, Michael Andrew ;
Femia, Nicola .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2015, 30 (03) :1567-1576
[8]  
Dworakowski P., 2022, CIGRE SESSION
[9]  
European Commission, EUR COMM PRIOR
[10]  
Ferencz I, 2020, INT POWER ELECT ELEC, P763, DOI [10.1109/speedam48782.2020.9161962, 10.1109/SPEEDAM48782.2020.9161962]