Research on early warning method for pollution flashover based on phase angle of insulator leakage current

被引:0
作者
Li, Zong [1 ]
Wang, Naixiao [2 ]
Wang, Liming [3 ]
机构
[1] State Grid Qingdao Power Supply Co, State Grid, Qingdao, Shandong, Peoples R China
[2] Elect Power Dispatching & Control Cent Guangdong P, Guangzhou, Guangdong, Peoples R China
[3] Tsinghua Univ, Tsinghua Shenzhen Int Grad Sch, Shenzhen, Guangdong, Peoples R China
关键词
failure analysis; HVDC power transmission; insulation; insulators; powersystem faults; power transmission lines; PORCELAIN;
D O I
10.1049/ell2.12705
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Pollution flashover is a systematic disaster of power system. It is significant to early warning insulator pollution flashover in real time and accurately. The phase angle of the insulator leakage current is a critical parameter for insulator pollution flashover early warning. However, in field applications, the operating voltage waveform cannot be obtained so that this characteristic parameter cannot be applied to the insulator pollution flashover early warning system. This paper proposes a method to obtain the phase angle of the leakage current of the online insulator. This method avoids the direct measurement of the operating voltage waveform, but uses the stray capacitance between the signal plate of the early warning device metal shell and the transmission line to obtain the operating voltage signal indirectly. In this paper, the method and the early warning mechanism of pollution flashover are analyzed theoretically, and then the early warning device for pollution flashover is designed. Finally, the effectiveness of the early warning device is verified by experiments.
引用
收藏
页数:3
相关论文
共 9 条
  • [1] Method for Predicting the Water Absorption of External Insulating Silicone Rubber
    Cheng, Li
    Liu, Yunfan
    Chen, Rongxin
    Zhang, Sida
    Liao, Ruijin
    Yang, Lijun
    Wang, Tingting
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2022, 29 (04) : 1242 - 1250
  • [2] Leakage Current on Porcelain and Silicone Insulators Under Sea or Light Industrial Pollution
    Chrzan, Krystian L.
    Vosloo, Wallace L.
    Holtzhausen, Jacobus P.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (03) : 2051 - 2052
  • [3] Flashover Process and Frequency Analysis of the Leakage Current on Insulator Model under non-Uniform Pollution Conditions
    Douar, M. A.
    Mekhaldi, A.
    Bouzidi, M. C.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1284 - 1297
  • [4] Jiang Xing-liang, 2010, Proceedings of the CSEE, V30, P118
  • [5] Stage pre-warning based on leakage current characteristics before contamination flashover of porcelain and glass insulators
    Li, J. Y.
    Sun, C. X.
    Sima, W. X.
    Yang, Q.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2009, 3 (07) : 605 - 615
  • [6] Contamination Level Prediction of Insulators Based on the Characteristics of Leakage Current
    Li, Jingyan
    Sun, Caixin
    Sima, Wenxia
    Yang, Qing
    Hu, Jianlin
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2010, 25 (01) : 417 - 424
  • [7] Life Estimation for Long Rod Composite Insulators Subjected to Accelerating Ageing by Combined Static and Cyclic Loading
    Wankowicz, Jacek Gracjan
    Bielecki, Jerzy
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (01) : 106 - 113
  • [8] On-line monitoring, data analysis for electrolytic corrosion of ±800 kV high voltage direct current insulators
    Yang, Daiming
    Cao, Bin
    Li, Zong
    Yang, Lianwu
    Wu, Yankun
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 131
  • [9] Yang L, 2016, IEEE T DIELECT EL IN, V23, P2875, DOI [10.1109/TDEI.2016.005821, 10.1109/TDEI.2016.7736848]