Protection issues for under-impedance relay used as starting supervision for large synchronous motors

被引:0
作者
Marini, P. [1 ]
机构
[1] Maire Tecnimont Grp, Dept Elect Engn, Milan, Italy
关键词
Under impedance; Blocked rotor protection; Synchronous motor; Critical starting; Starting supervision;
D O I
10.1016/j.epsr.2023.109246
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Some petrochemical plants (low density polyethylene type) always require the use of big synchronous motors to feed large power compressors (typically from 10 to 30 MW).In certain supply network conditions, it could happen that the motor undergoes a critical starting which takes several tens of seconds to be completed. "Critical" means that the starting time is higher than the time the rotor can withstand in blocked condition: therefore, it is necessary to assess the actual motor rotation to be sure that the motor is being self-ventilating during its acceleration and can survive the critical starting.By means of numerical simulations, it is demonstrated that the solution of using an under-impedance relay (ANSI code 21) for starting supervision, as is proposed in technical literature since many years, gives some troubles for the correct and safe protection of the starting of the motor, with respect to the most common solution of adopting a supervision switch relay (ANSI code 14) based on rotor speed measurement.
引用
收藏
页数:12
相关论文
共 10 条
[1]  
AL-Najdi KS, 2014, PETROL CHEM INDUST
[2]  
[Anonymous], 2001, 242 IEEE STAND
[3]  
[Anonymous], 1987, Alternative Transient Program: ATP Rule Book
[4]  
[Anonymous], 2016, 30048 IEEE STAND
[5]  
Dommel HW., 1992, EMTP THEORY BOOK
[6]  
Eliasen A. N., 1979, Electra, P25
[7]  
Khan S., 2008, IND POWER SYSTEMS
[8]  
Nicoladelli de Oliveira M., 2019, PROC PCIC EUROPE 201
[9]  
Shulman J.M., 1978, IEEE T POWER AP SYST, V67
[10]  
Ziegler G., 1999, NUMERICAL DISTANCE P