System for Indoor Comfort and Health Monitoring Tested in Office Building Environment

被引:5
作者
El-Leathey, Lucia-Andreea [1 ]
Anghelita, Paula [1 ]
Constantin, Alexandru-Ionel [1 ]
Circiumaru, Gabriela [1 ]
Chihaia, Rares-Andrei [1 ]
机构
[1] Natl Inst R&D Elect Engn ICPE CA Bucharest, Dept Renewable Sources & Energy Efficiency, Bucharest 030138, Romania
来源
APPLIED SCIENCES-BASEL | 2023年 / 13卷 / 20期
关键词
IoT; monitoring system; comfort; indoor air quality; carbon dioxide; formaldehyde; total volatile organic compounds; suspended particulate matter; radon; Arduino board;
D O I
10.3390/app132011360
中图分类号
O6 [化学];
学科分类号
0703 ;
摘要
The use of smart technologies and the Internet of Things (IoT) is becoming more and more popular in order to enhance the overall building performance by monitoring parameters related to occupants' comfort and health in the built environment. A new modular, custom-made and replicable IoT system is proposed based on an Arduino development board (MKR WiFi 1010) connected to the Arduino IoT Cloud. An Application Programming Interface (API) enables the integration of this system with other possible ones, thus making the system modular, custom-made and replicable. A series of parameters were simultaneously monitored over a 7-day period in two office spaces and a photovoltaic (PV)-testing laboratory. While the meteorological and comfort parameters (temperature, relative humidity, CO2) were monitored in all three spaces, the health parameters (total volatile organic compounds-TVOCs; formaldehyde-HCHO; particulate matter-PM; and radon-222Rn) were monitored only in an office setup located right next to a Chemical Analysis and Testing Laboratory. Generally, the registered values of the health parameters fell within the recommended thresholds. However, the thermal comfort parameters were constantly exceeded: over 90% of the working time in the two office spaces and 83.33% in the PV-testing laboratory. Still, the optimal relative humidity values in the monitored spaces contributed to the discomfort reduction in the occupants. Also, CO2 and TVOCs had some exceptions in particular conditions. CO2 values of up to 1500 ppm due to poor ventilation and TVOC levels of up to 1000 ppb related to chemical experiment development were registered. Also, several other peaks were recorded when monitoring HCHO as well as PM. Thus, special attention must be paid to natural ventilation or to the improvement of building characteristics. Also, the time intervals when experiments in the Chemical Analysis and Testing Laboratory are carried out should be communicated to other personnel from the nearest offices. The testing of the monitoring system over a one-week period showed that the proposed solution operated adequately, representing a reliable tool for data acquisition via the Arduino IoT Cloud.
引用
收藏
页数:23
相关论文
共 47 条
[1]  
Adeleke J., 2015, P 2015 ANN RES C S A
[2]   Modeling and Forecasting End-Use Energy Consumption for Residential Buildings in Kuwait Using a Bottom-Up Approach [J].
Alajmi, Turki ;
Phelan, Patrick .
ENERGIES, 2020, 13 (08)
[3]  
Anghelita P., 2015, Electroteh. Electron. Autom, V62, P93
[4]  
[Anonymous], 2011, USEPA EXP FACT HDB
[5]  
[Anonymous], 2013, 55 ANSIASHRAE
[6]  
[Anonymous], 2023, Order No. 153 of July 27, 2023 Regarding the Approval of the Methodology for Determining the Indoor Concentration of Radon in Buildings and at Workplaces
[7]  
[Anonymous], 2005, Ergonomics of the thermal environment _ Analytical determination and interpretation of thermal comfort using calculation of the PMV and PPD indices and local thermal comfort criteria, DOI DOI 10.1016/J.SOILDYN.2004.11.005
[8]  
[Anonymous], 2022, MDRT I5-2022
[9]  
[Anonymous], 2014, IAEA Radiation Protection and Safety of Radiation Sources: International Basic Safety Standards.
[10]  
Aquilina N., 2019, J. Environ. Pollut. Control, V2, P107