Research on Transformer Partial Discharge Fault Location Based on Improved UCA-RB-MUSIC Algorithm

被引:1
作者
Lv, Yanling [1 ]
Ai, Kexian [1 ]
Guo, Feng [2 ]
机构
[1] Harbin Univ Sci & Technol, Sch Elect & Elect Engn, Harbin 150080, Peoples R China
[2] Zhaoqing Power Supply Bur China Southern Power Gri, Zhaoqing, Peoples R China
关键词
Partial discharges; Power transformer insulation; Estimation; Eigenvalues and eigenfunctions; Multiple signal classification; Microphone arrays; Matrix decomposition; Uniform circular array; partial discharge; power transformer; matrix reconstruction;
D O I
10.1109/ACCESS.2024.3354707
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Aiming at the problem that the coherent signal cannot be estimated when the traditional UCA-RB-MUSIC algorithm is used to detect the partial discharge of the transformer, an improved UCA-RB-MUSIC algorithm is suggested to reconstruct the signals captured by the array so that the number of calls sources is equivalent to the rank of the reconstructed signal matrix. The impact of correlated signals is eradicated. The results of simulation analysis and experimental verification show that when the improved UCA-RB-MUSIC algorithm is used to locate a single and double partial discharge source, the improved positioning error is only half of the mistake before improvement, which enhances the accuracy and resolution of uniform circular array positioning and the accuracy of transformer partial discharge detection.
引用
收藏
页码:16299 / 16309
页数:11
相关论文
共 10 条
  • [1] A TRANSFORMATION BETWEEN PHASING TECHNIQUES REQUIRED FOR LINEAR AND CIRCULAR AERIAL ARRAYS
    DAVIES, DEN
    [J]. PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1965, 112 (11): : 2041 - &
  • [2] Study of Ultra High Frequency Measurement Techniques for Online Monitoring of Partial Discharges in High Voltage Systems
    Ghanakota, Krishna Chaitanya
    Yadam, Yugandhara Rao
    Ramanujan, Sarathi
    Prasad, Vishnu V. J.
    Arunachalam, Kavitha
    [J]. IEEE SENSORS JOURNAL, 2022, 22 (12) : 11698 - 11709
  • [3] Partial Discharge Features for Power Electronic Transformers Under High-Frequency Pulse Voltage
    Jiang, Jun
    Zhang, Bendong
    Li, Zhi
    Ranjan, Prem
    Chen, Jiawei
    Zhang, Chaohai
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2021, 49 (02) : 845 - 853
  • [4] Phased-ultrasonic receiving-planar array transducer for partial discharge location in transformer
    Luo, YF
    Ji, SC
    Li, YM
    [J]. IEEE TRANSACTIONS ON ULTRASONICS FERROELECTRICS AND FREQUENCY CONTROL, 2006, 53 (03) : 614 - 622
  • [5] EIGENSTRUCTURE TECHNIQUES FOR 2-D ANGLE ESTIMATION WITH UNIFORM CIRCULAR ARRAYS
    MATHEWS, CP
    ZOLTOWSKI, MD
    [J]. IEEE TRANSACTIONS ON SIGNAL PROCESSING, 1994, 42 (09) : 2395 - 2407
  • [6] Nascimento S. S., Sens
  • [7] Partial discharge ultrasonic detection based on EULER-MUSIC algorithm and conformal array sensor
    Pang, Xianhai
    Wu, Han
    Li, Xiaofeng
    Qi, Yanxun
    Jing, Hao
    Zhang, Jiantao
    Xie, Qing
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (14) : 3596 - 3605
  • [8] Qiang Guo, 2014, Applied Mechanics and Materials, V610, P339, DOI 10.4028/www.scientific.net/AMM.610.339
  • [9] Sun J., 2022, J. Phys., Conf. Ser., V2195
  • [10] On the Feasibility of Gap Detection of Power Transformer Partial Discharge UHF Signals: Gap Propagation Characteristics of Electromagnetic Waves
    Zhang, Xiaoxing
    Zhang, Guozhi
    Li, Yalong
    Zhang, Jian
    Huang, Rui
    [J]. ENERGIES, 2017, 10 (10):