On the control interaction of synchronous machine and inverter-based resources during system-split situations

被引:1
|
作者
Zhang, Yonggang [1 ]
Wiese, Nils [1 ,2 ]
Liu, Zheng [1 ]
Braun, Martin [1 ,2 ]
机构
[1] Univ Kassel, Dept Energy Management & Power Syst Operat, D-34121 Kassel, Germany
[2] Fraunhofer Inst Energy Econ & Energy Syst Technol, D-34117 Kassel, Germany
关键词
Control interaction; Grid -forming control; Modal impedance analysis; Synchronous machine; Small -signal stability; Voltage support; STABILITY; PARAMETERS;
D O I
10.1016/j.ijepes.2023.109227
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Motivated by the potential transient oscillation risks in inverter based resource (IBR) dominated power systems, the paper is to identify the unwanted control interactions between traditional synchronous machines (SMs) and IBRs during system-split situations. Modal impedance analysis method is applied to reveal oscillation risk and the underlying mechanism, while electromagnetic transient (EMT) simulation analysis is used to observe reliable oscillation phenomenon. Impedance models of IBRs considering both grid-following (GFL) and grid-forming (GFM) control schemes and SMs equipped with automatic voltage regulator (AVR) and power system stabilizer (PSS) are developed for grid conditions with large frequency and/or voltage deviations, and validated by EMT simulations. Potential adverse control interactions within an exemplary test system are analyzed taking into account the impacts of: 1) renewable penetration level; 2) converter control scheme (GFL or GFM); 3) converter control tuning; 4) SM control setting; 5) grid-support capabilities of converter-interfaced loads. It has been observed that oscillation instability at around several Hz can occur by high penetration of GFL controlled IBRs after system-splits, which can be mitigated by redesigning the AVR & PSS control, or retuning the power/voltage control loops and phase-locked loop (PLL) of GFL converter. However, such measures might inevitably induce other stability issues, e.g. synchronization instability. From the oscillation analysis, it has also been revealed, through replacing part of the GFL converters with GFM converter(s), the oscillation mode at several Hz can disappear, owning to the varied impedance including better damping of GFM than GFL for the frequencies between 1 and 10 Hz.
引用
收藏
页数:14
相关论文
共 19 条
  • [1] Investigating and addressing synchronous instabilities in inverter-based resources within microgrids
    Ide, T.
    Hirase, Y.
    Yoshimura, E.
    Umezu, Y.
    Bando, S.
    Sugimoto, K.
    APPLIED ENERGY, 2025, 377
  • [2] Power System Stability With a High Penetration of Inverter-Based Resources
    Gu, Yunjie
    Green, Timothy C.
    PROCEEDINGS OF THE IEEE, 2023, 111 (07) : 832 - 853
  • [3] Optimal directional overcurrent relay settings for stable microgrids with synchronous and inverter-based resources
    Eladl, Abdelfattah A.
    Sheta, Ahmed N.
    Elgamal, M.
    Vasquez, Juan C.
    Sedhom, Bishoy E.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2025, 167
  • [4] Dynamic State Estimation for Inverter-Based Resources: A Control-Physics Dual Estimation Framework
    Huang, Heqing
    Lin, Yuzhang
    Lu, Xiaonan
    Zhao, Yue
    Kumar, Avinash
    IEEE TRANSACTIONS ON POWER SYSTEMS, 2024, 39 (05) : 6456 - 6468
  • [5] Robust Optimal Control of Inverter-Based Resources Under Grid-Forming Operation
    Ameli, Sina
    Anubi, Olugbenga Moses
    Peng, Fang
    IEEE TRANSACTIONS ON CONTROL SYSTEMS TECHNOLOGY, 2025,
  • [6] Impact of Increased Inverter-based Resources on Power System Small-signal Stability
    Lin, Yashen
    Seo, Gab-Su
    Vijayshankar, Sanjana
    Johnson, Brian
    Dhople, Sairaj
    2021 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2021,
  • [7] Overview of frequency control techniques in power systems with high inverter-based resources: Challenges and mitigation measures
    Al Kez, Dlzar
    Foley, Aoife M.
    Ahmed, Faraedoon
    Morrow, D. John
    IET SMART GRID, 2023, 6 (05) : 447 - 469
  • [8] Robust Adaptive Control for Large-scale Inverter-based Resources with Partial and Complete Loss of Inverters
    Ameli, Sina
    Olajube, Ayobami
    Anubi, Olugbenga Moses
    IFAC PAPERSONLINE, 2023, 56 (03): : 211 - 216
  • [9] The impact of synchronous distributed control period on inverter-based cyber-physical microgrids stability with time delay
    Xu, Luo
    Guo, Qinglai
    He, Guannan
    Sun, Hongbin
    APPLIED ENERGY, 2021, 301
  • [10] Synchronous Generator Control Concept and Modified Droop for Frequency and Voltage Stability of Microgrid Including Inverter-Based DGs
    Rajamand, Sahbasadat
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2020, 15 (03) : 1035 - 1044