Experimental Study of the Effect of Opening Factor on Self-Extinguishing and Blue Ghosting Flame in Under-Ventilated Compartment Fire

被引:4
作者
Wang, Dong [1 ]
Ju, Xiaoyu [2 ]
Zhou, Xiaodong [1 ]
Zhou, Zhizuan [1 ]
Liu, Hong [1 ]
Zhang, Ping [1 ,3 ]
Yang, Lizhong [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Anhui, Peoples R China
[2] Toyohashi Univ Technol, Dept Mech Engn, 1-1 Hibarigaoka,Tempaku, Toyohashi 4418580, Japan
[3] City Univ Hong Kong, Dept Architecture & Civil Engn, Hong Kong, Peoples R China
基金
中国国家自然科学基金;
关键词
Ventilation-controlled compartment fire; Blue ghosting flame; Self-extinguishing; Opening factor; Neutral plane; ELECTROCHEMICAL GAS SENSOR; SPECIES PRODUCTION; HEAT RELEASE; BEHAVIOR; EXTINCTION; COMBUSTION; HEIGHT; WALL;
D O I
10.1007/s10694-022-01353-9
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Blue ghosting flame and self-extinguishing are two typical flame behaviors in ventilation-controlled compartment fires. However, the study of the evolution of these two behaviors with opening factor and heat release rate (HRR) is incomplete. In this study, the experiments were performed in a 1/2-scale compartment model with openings of six different sizes. The temperature, oxygen concentration and carbon monoxide concentration in the compartment under different propane supply rates were recorded and analyzed. The results showed that the flame transformed from the stable stage to blue ghosting flame or extinguishment with the increase of the total HRR. When there is a blue ghosting flame and self-extinguishing, the combustion spontaneously regulates the oxygen concentration in the compartment and changes the trend of the oxygen concentration decreasing with the total HRR. The blue flame not only reflects that the real HRR is in an unstable state, but also changes the evolutionary trend of the ceiling temperature. The critical HRR for the appearance of blue ghosting flame and self-extinguishing behavior increases linearly with the opening factor. The value of the Global Equivalence Ratio stabilized around 0.73 only after the opening factor was greater than 0.0145. The blue ghosting flame cannot return to stability and is extinguished when the difference between the entrainment rate and the air consumption rate exceeds the limit of spontaneous regulation of combustion.
引用
收藏
页码:595 / 621
页数:27
相关论文
共 41 条
[2]   NON-COVENTIONAL FULLY-DEVELOPED POLYETHYLENE AND WOOD COMPARTMENT FIRES [J].
BOHM, B ;
HADVIG, S .
COMBUSTION AND FLAME, 1982, 44 (1-3) :201-221
[3]   A two-thermocouples probe for radiation corrections of measured temperatures in compartment fires [J].
Brohez, S ;
Delvosalle, C ;
Marlair, G .
FIRE SAFETY JOURNAL, 2004, 39 (05) :399-411
[4]  
Delichatsios MA, 2003, FIRE SAFETY SCI, P59, DOI DOI 10.3801/IAFSS.FSS.7-59
[5]   An electrochemical gas sensor based on paper supported room temperature ionic liquids [J].
Dossi, Nicolo ;
Toniolo, Rosanna ;
Pizzariello, Andrea ;
Carrilho, Emanuel ;
Piccin, Evandro ;
Battiston, Simone ;
Bontempelli, Gino .
LAB ON A CHIP, 2012, 12 (01) :153-158
[6]   Self-extinction of timber [J].
Emberley, Richard ;
Inghelbrecht, Arne ;
Yu, Zeyu ;
Torero, Jose L. .
PROCEEDINGS OF THE COMBUSTION INSTITUTE, 2017, 36 (02) :3055-3062
[7]  
Floyd JE, 2001, 9 INT FIRE SCI ENG C
[8]  
Foote K., 1987, 1986 LLNL ENCLOSURE
[9]   Ventilation limited extinction of fires in ceiling vented compartments [J].
He, Qize ;
Ezekoye, Ofodike A. ;
Li, Changhai ;
Lu, Shouxiang .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2015, 91 :570-583
[10]   A global non-dimensional factor characterizing side wall constraint effect on facade flame entrainment and flame height from opening of compartment fires [J].
Hu, L. H. ;
Lu, K. H. ;
Tang, F. ;
Delichatsios, M. ;
He, L. H. .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 75 :122-129