共 77 条
Thermal design of composite cold plates by topology optimization
被引:20
作者:
Sun, Chen
[1
]
Wang, Wei
[1
,2
]
Tian, Xi-Wei
[1
]
Zeng, Xu
[1
]
Qian, Si-Hao
[1
]
Cai, Yan-Zhao
[1
,3
]
Wang, Xiao-Hui
[4
]
机构:
[1] Xidian Univ, Key Lab Elect Equipment Struct Design, Minist Educ, Xian 710071, Peoples R China
[2] Xidian Univ, Shannxi Key Lab Space Solar Power Stn Syst, Xian 710071, Peoples R China
[3] Avic Jonhon Optron Technol Co Ltd, Luoyang 471003, Peoples R China
[4] China Acad Launch Vehicle Technol, R&D Dept, Beijing 100076, Peoples R China
基金:
中国国家自然科学基金;
关键词:
Topology optimization;
Composite cold plate;
Conjugate heat transfer;
Hydrothermal performance;
Multi -material design;
HEAT-TRANSFER;
PERFORMANCE;
CHANNEL;
FLOW;
SYSTEM;
DEVICE;
SINK;
D O I:
10.1016/j.ijmecsci.2023.108594
中图分类号:
TH [机械、仪表工业];
学科分类号:
0802 ;
摘要:
Topology optimization has been extensively utilized to generate cold plates with efficient cooling performance. However, the design of composite cold plates remains challenging. This study presents a two-solid topology optimization method for conjugate heat transfer based on ordered SIMP (solid isotropic material with penali-zation). The proposed method aims to develop high-performance composite cold plates by leveraging the dif-ferences in thermal conductivity of various materials. The optimization results were investigated for four inlet and outlet combinations at various Reynolds numbers. The results indicate that using a staggered distribution of multiple inlets and outlets yields higher heat transfer than a single distribution. Furthermore, composite cold plates derived from the two-dimensional optimized models were numerically compared with rectangular flow channel and non-composite cold plates. The optimized channels exhibited superior hydrothermal performance over the rectangular flow channel, which was primarily attributed to the weakening of the velocity stagnation region. The average temperature (T) and root mean square temperature (RMST) of the heat source were reduced by a maximum of 2.53% and 57.67%, respectively. The friction factor decreased by up to 50.42%. Compared to non-composite cold plates, the decrease in RMST reached 16.24% without any additional increase in the pumping power. Composite cold plates further promote temperature uniformity by accelerating the heat transfer rate through their high thermal conductivity, thereby mitigating the occurrence of hotspots. Finally, the per-formance of the three test samples was experimentally compared to validate the numerical results. The optimized design enables the strategic allocation of highly thermally conductive material on a cold plate while employing more cost-effective alternatives in other areas. The proposed method is anticipated to expand the design pos-sibilities for cold plates and provide insights into addressing concerns related to hotspots in equipment.
引用
收藏
页数:19
相关论文