Variable Virtual Impedance-Based Overcurrent Protection for Grid-Forming Inverters: Small-Signal, Large-Signal Analysis and Improvement

被引:46
作者
Qoria, Taoufik [1 ]
Wu, Heng [2 ]
Wang, Xiongfei [3 ]
Colak, Ilknur [4 ]
机构
[1] Maschinenfabr Reinhausen, Medium Voltage Power Elect R&D Dept, D-93059 Regensburg, Germany
[2] Aalborg Univ, Dept Energy Technol, Tekn Nat Videnskabelige Fak, DK-9220 Aalborg, Denmark
[3] KTH Royal Inst Technol, S-11428 Stockholm, Sweden
[4] Schneider Elect, Dept Power Elect, F-92500 Rueil Malmaison, France
关键词
Grid-forming; virtual impedance; current limitation; small-signal stability; large-signal stability; CURRENT LIMITATION; VOLTAGE CONTROL; MMC;
D O I
10.1109/TSG.2022.3232987
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Grid-forming inverters are sensitive to large grid disturbances that may engender overcurrent due to their voltage source behavior. To overcome this critical issue and ensure the safety of the system, current limitation techniques have to be implemented. In this context, the variable virtual impedance (VI) appears as a suitable solution for this problem. The design of the variable virtual impedance basically rests on static considerations, while, its impact on the system stability and dynamics considering both small-signal and large-signal aspects can be significant. This paper proposes small-signal and nonlinear power models to assess the impact of the virtual impedance parameters on the grid current dynamics and on the angle stability. Thanks to the proposed approach, it has been demonstrated that the virtual impedance ratio sXVI/RVI has a contradictory effect on the system dynamics and the transient stability, i.e., a resistive virtual impedance results in a well-damped current response but a very limited transient stability margin, while an inductive virtual impedance results in a poorly-damped current response but an acceptable transient stability margin. Based on that, it has been concluded that the conventional virtual impedance cannot cope at once with the current dynamic performances and the transient stability. To overcome this constraint, a Variable Transient Virtual Resistance (VTVR) has been proposed as an additional degree of freedom to vary sXVI/RVI. It decreases sXVI/RVI in the transient to damp the current response and it increases sXVI/RVI in the quasi-static and steady-state to guarantee the maximum angle stability margin allowed by the variable virtual impedance. The effectiveness of the proposed control has been proven through time-domain simulations.
引用
收藏
页码:3324 / 3336
页数:13
相关论文
共 25 条
[1]  
[Anonymous], 2015, Infineon Rep. AN2011-05
[2]  
[Anonymous], 2020, H2020 migrate project
[3]   Virtual synchronous machine [J].
Beck, Hans-Peter ;
Hesse, Ralf .
PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON ELECTRICAL POWER QUALITY AND UTILISATION, VOLS 1 AND 2, 2007, :107-+
[4]  
Bergna-Diaz G, 2018, IEEE IND ELEC, P5999, DOI 10.1109/IECON.2018.8592881
[5]   Equivalence of Virtual Synchronous Machines and Frequency-Droops for Converter-Based MicroGrids [J].
D'Arco, Salvatore ;
Suul, Jon Are .
IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (01) :394-395
[6]   The Migrate project: the challenges of operating a transmission grid with only inverter-based generation. A grid-forming control improvement with transient current-limiting control [J].
Denis, Guillaume ;
Prevost, Thibault ;
Debry, Marie-Sophie ;
Xavier, Florent ;
Guillaud, Xavier ;
Menze, Andreas .
IET RENEWABLE POWER GENERATION, 2018, 12 (05) :523-529
[7]   Grid-Forming Control With Current Limitation for MMC Under Unbalanced Fault Ride-Through [J].
Freytes, Julian ;
Li, Jiaqi ;
de Preville, Guillaume ;
Thouvenin, Marc .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (03) :1914-1916
[8]   Transient Stability Analysis and Control Design of Droop-Controlled Voltage Source Converters Considering Current Limitation [J].
Huang, Linbin ;
Xin, Huanhai ;
Wang, Zhen ;
Zhang, Leiqi ;
Wu, Kuayu ;
Hu, Jiabing .
IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (01) :578-591
[9]   Comparison of Dynamic Characteristics Between Virtual Synchronous Generator and Droop Control in Inverter-Based Distributed Generators [J].
Liu, Jia ;
Miura, Yushi ;
Ise, Toshifumi .
IEEE TRANSACTIONS ON POWER ELECTRONICS, 2016, 31 (05) :3600-3611
[10]  
Pan DH, 2019, IEEE ENER CONV, P4311, DOI [10.1109/ECCE.2019.8912567, 10.1109/ecce.2019.8912567]