Novel Differential Protection for a Powerformer Considering Capacitive Current Compensation

被引:1
|
作者
Wang, Yuanyuan [1 ]
Luo, Xiaomin [1 ]
Zeng, Xiangjun [1 ]
Zhou, Lawu [1 ]
Ye, Yuxuan [1 ]
机构
[1] Changsha Univ Sci & Technol, Sch Elect & Informat Engn, Changsha 410114, Peoples R China
基金
中国国家自然科学基金;
关键词
Powerformer; stator faults; differential protection; capacitive current compensation; SYNCHRONOUS GENERATOR; VOLTAGE; FAULT;
D O I
10.1109/TPWRD.2023.3268302
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
A Powerformer is a special type of generator whose peak capacitive current is approximately 30 times larger than that of conventional generators with the same rated apparent power. Powerformer stator fault relays may be misoperated by using conventional differential protection strategies, thus degrading network reliability. Therefore, a novel differential protection scheme for a Powerformer is proposed in this paper. First, the nonlinear distribution laws of the Powerformer stator winding capacitance and induced electromotive force (EMF) are analyzed. Next, an equivalent distributed parameter circuit model of the Powerformer considering cable-windings with graded insulation is established and verified by using FEM-based analysis. Furthermore, to eliminate the influence of the capacitive current on the differential protection, the capacitive current is analyzed, and a novel differential protection scheme considering capacitive current compensation is proposed. A simulation model is established by using MATLAB and PSCAD, and extensive simulation studies verify the effectiveness of the proposed protection approach.
引用
收藏
页码:3169 / 3178
页数:10
相关论文
共 50 条
  • [1] A novel current differential protection scheme for powerformer
    Tian, Qing
    Lin, Xiangning
    Lu, Wenjun
    2006 INTERNATIONAL CONFERENCE ON POWER SYSTEMS TECHNOLOGY: POWERCON, VOLS 1- 6, 2006, : 417 - +
  • [2] Capacitive current compensation method for differential protection of EHV/UHV lines
    Liu, Kai
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2011, 31 (08): : 94 - 98
  • [3] Phaselet-based current differential protection scheme based on transient capacitive current compensation
    Yining, Z.
    Jiale, S.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2008, 2 (04) : 469 - 477
  • [4] A novel overvoltage protection for powerformer
    Gao, Yan
    Lin, Xiang-Ning
    Liu, Pei
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2008, 28 (34): : 101 - 105
  • [5] Novel self-adaptive compensated differential protection design suitable for powerformer
    Tian, Qing
    Lin, Xiangning
    Liu, Pei
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2006, 30 (24): : 62 - 68
  • [6] Research on Capacitive Current Compensation of Differential Protection on Segment Parallel Lines for Different Voltage Levels
    Yang, Yan
    Yin, Xianggen
    Tang, Cui
    Zhang, Zhe
    Wang, Xiongwei
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 988 - 992
  • [7] A novel principle of energy directional protection for powerformer
    Gao, Yan
    Lin, Xiangning
    Tian, Qing
    Liu, Pei
    2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2041 - +
  • [8] Impact of Capacitive current of EHV/UHV lines on Current Differential Protection
    Rane, P. S.
    Jawale, R. D.
    Bhaisare, S. D.
    Debre, P. D.
    2016 INTERNATIONAL CONFERENCE ON ENERGY EFFICIENT TECHNOLOGIES FOR SUSTAINABILITY (ICEETS), 2016, : 372 - 376
  • [9] Limiting Lengths of OL with Differential Phase Protection Without Compensation for Capacitive Currents
    N. A. Doni
    A. I. Leviush
    E. V. Tonkikh
    V. T. Uzhegov
    Power Technology and Engineering, 2003, 37 (1) : 62 - 64
  • [10] The Effects of the Reverse Current Caused by the Series Compensation on the Current Differential Protection
    Tang, Cui
    Yin, Xianggen
    Qi, Xuanwei
    Zhang, Zhe
    Wen, Minghao
    SCIENTIFIC WORLD JOURNAL, 2014,