Robust State Estimation of Active Distribution Networks with Multi-source Measurements

被引:4
作者
Liu, Zhelin [1 ]
Li, Peng [1 ]
Wang, Chengshan [1 ]
Yu, Hao [1 ]
Ji, Haoran [1 ]
Xi, Wei [2 ]
Wu, Jianzhong [3 ]
机构
[1] Tianjin Univ, Minist Educ, Key Lab Smart Grid, Tianjin 300072, Peoples R China
[2] China Southern Power Grid, Digital Grid Res Inst, Guangzhou 510670, Peoples R China
[3] Cardiff Univ, Sch Engn, Inst Energy, Cardiff CF24 3AA, Wales
关键词
Current measurement; State estimation; Weight measurement; Voltage measurement; Time measurement; Power measurement; Rotation measurement; Active distribution network ADN; robust state estimation (RSE); second-order cone programming (SOCP); multi-source measurement; bad data identification; PHASOR MEASUREMENT UNIT; POINT; CONVEXIFICATION; RELAXATIONS; SOCP;
D O I
10.35833/MPCE.2022.000200
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The volatile and intermittent nature of distributed generators (DGs) in active distribution networks (ADNs) increases the uncertainty of operating states. The introduction of distribution phasor measurement units (D-PMUs) enhances the monitoring level. The trade-offs of computational performance and robustness of state estimation in monitoring the network states are of great significance for ADNs with D-PMUs and DGs. This paper proposes a second-order cone programming (SOCP) based robust state estimation (RSE) method considering multi-source measurements. Firstly, a linearized state estimation model related to the SOCP state variables is formulated. The phase angle measurements of D-PMUs are converted to equivalent power measurements. Then, a revised SOCP-based RSE method with the weighted least absolute value estimator is proposed to enhance the convergence and bad data identification. Multi-time slots of D-PMU measurements are utilized to improve the estimation accuracy of RSE. Finally, the effectiveness of the proposed method is illustrated in the modified IEEE 33-node and IEEE 123-node systems.
引用
收藏
页码:1540 / 1552
页数:13
相关论文
共 42 条
  • [31] Performance Enhancement of Distribution Systems via Distribution Network Reconfiguration and Distributed Generator Allocation Considering Uncertain Environment
    Naguib, Mina
    Omran, Walid A.
    Talaat, Hossam E. A.
    [J]. JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2022, 10 (03) : 647 - 655
  • [32] Phadke AG, 2008, POWER ELECTRON POWER, P3, DOI 10.1007/978-0-387-76537-2_1
  • [33] A Review on Distribution System State Estimation
    Primadianto, Anggoro
    Lu, Chan-Nan
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (05) : 3875 - 3883
  • [34] WEIGHTED LEAST ABSOLUTE VALUE STATE ESTIMATION USING INTERIOR-POINT METHODS
    SINGH, H
    ALVARADO, FL
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1994, 9 (03) : 1478 - 1484
  • [35] Optimal placement of phasor measurement unit in distribution networks considering the changes in topology
    Su, Hongzhi
    Wang, Chengshan
    Li, Peng
    Liu, Zhelin
    Yu, Li
    Wu, Jianzhong
    [J]. APPLIED ENERGY, 2019, 250 : 313 - 322
  • [36] Novel voltage-to-power sensitivity estimation for phasor measurement unit-unobservable distribution networks based on network equivalent
    Su, Hongzhi
    Wang, Chengshan
    Li, Peng
    Li, Peng
    Liu, Zhelin
    Wu, Jianzhong
    [J]. APPLIED ENERGY, 2019, 250 : 302 - 312
  • [37] Taylor J., 1997, INTRO ERROR ANAL STU
  • [38] Robust Power System State Estimation From Rank-One Measurements
    Wang, Gang
    Zhu, Hao
    Giannakis, Georgios B.
    Sun, Jian
    [J]. IEEE TRANSACTIONS ON CONTROL OF NETWORK SYSTEMS, 2019, 6 (04): : 1391 - 1403
  • [39] A Fast State Estimator for Systems Including Limited Number of PMUs
    Wu, Ting
    Chung, C. Y.
    Kamwa, Innocent
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (06) : 4329 - 4339
  • [40] Distribution System State Estimation: A Semidefinite Programming Approach
    Yao, Yiyun
    Liu, Xindong
    Zhao, Dongbo
    Li, Zuyi
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2019, 10 (04) : 4369 - 4378