Insulation evaluation of MV underground cable with partial discharge and dielectric dissipation factor measurements

被引:15
作者
Arikan, Oktay [1 ]
Uydur, Cihat Cagdas [2 ]
Kumru, Celal Fadil [3 ]
机构
[1] Yildiz Tech Univ, Dept Elect Engn, Istanbul, Turkiye
[2] Trakya Univ, Tech Sci Vocat Sch, Edirne, Turkiye
[3] Suleyman Demirel Univ, Dept Elect Elect Engn, Isparta, Turkiye
关键词
Diagnosis procedure; Dissipation factor; Electrical stresses; Partial discharge; Operation of XLPE cable; LOW-FREQUENCY; KV XLPE; VOLTAGE; VLF;
D O I
10.1016/j.epsr.2023.109338
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As it is known overvoltage and impulse voltage are the most common stresses that cables are exposed to in practice. Since the occurrence frequency, duration and amplitude of these two stresses are different, their deteriorating effects on the cable insulation also differ. At this point, it is necessary to know how sensitively the preferred dielectric diagnosis method can detect the deteriorations on cable insulation. Since it is not technically possible to detect all isolation errors with a single preferred diagnostic method, the methods must be used together in a certain procedure. In this study, 12/20.8 kV, XLPE insulated Cable Samples were artificially aged using 50 aging cycles of overvoltage (36 kV and 60 kV) and 50 kV, standard positive impulse voltage. After each aging cycle, dielectric performance of cable insulation was measured using partial discharge (PD) and dielectric dissipation factor (DDF) methods. The accuracy of dielectric diagnosis methods due to overvoltage and impulse voltage are analyzed and discussed based on the measurement results. In order to analyze dielectric diagnostic performances of the methods, both individual trends and the correlation between PD and DDF parameters during overvoltage and impulse voltage aging processes were shared. As a result, it was found that diagnostic perfor-mances of PD and DDF methods differ according to the amplitude and waveform of the applied electrical stress. Therefore, a dielectric diagnosis procedure for MV cables including both PD and DDF methods to improve diagnostic process in field applications was proposed. In this context, the use of the proposed diagnosis procedure will contribute to the evaluation of the findings resulting from the diagnostic methods during the operation of MV cables.
引用
收藏
页数:12
相关论文
共 37 条
[1]   Partial discharge inception voltage of voids enclosed in epoxy/mica versus voltage frequency and temperature [J].
Aakre, Torstein Grav ;
Ildstad, Erling ;
Hvidsten, Sverre .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2020, 27 (01) :214-221
[2]  
[Anonymous], 2015, 605022 IEC CENELEC
[3]  
[Anonymous], 2012, IEEE Standard 400-2023
[4]   Prediction of dielectric parameters of an aged mv cable: A comparison of curve fitting, decision tree and artificial neural network methods [J].
Arikan, Oktay ;
Uydur, Cihat Cagdas ;
Kumru, Celal Fadil .
ELECTRIC POWER SYSTEMS RESEARCH, 2022, 208
[5]  
Arora R, 2011, HIGH VOLTAGE AND ELECTRICAL INSULATION ENGINEERING, P1, DOI 10.1002/9780470947906
[6]   Trend adjusted lifetime monitoring of underground power cable [J].
Bicen, Yunus .
ELECTRIC POWER SYSTEMS RESEARCH, 2017, 143 :189-196
[7]  
Cao L., 2010, 2010 International Conference on High Voltage Engineering and Application (ICHVE 2010), P148, DOI 10.1109/ICHVE.2010.5640844
[8]   Accelerated Aging Study on 15 kV XLPE and EPR Cables Insulation Caused by Switching Impulses [J].
Cao, Linfeng ;
Grzybowski, Stanislaw .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (05) :2809-2817
[9]  
Chi P., 2020, ELECTR POW SYST RES, V195, DOI [10.1016/j.epsr.2021.107136,2021, DOI 10.1016/J.EPSR.2021.107136,2021]
[10]   A reliability assessment model for an outdoor 88 kV XLPE cable termination [J].
Chimunda, Samantha ;
Nyamupangedengu, Cuthbert .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 177