Transient Stability of Synchronous Condenser Co-Located With Renewable Power Plants

被引:5
|
作者
Liu, Xinyu [1 ]
Xin, Huanhai [1 ]
Zheng, Di [2 ]
Chen, Dong [3 ]
Tu, Jingzhe [4 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Peoples R China
[2] China Jiliang Univ, Coll Mech & Elect Engn, Hangzhou 310018, Peoples R China
[3] Natl HVDC Ctr, Cumbernauld G68 0FQ, Scotland
[4] China Elect Power Res Inst, Beijing 100192, Peoples R China
基金
中国国家自然科学基金;
关键词
Synchronous condenser; voltage source converter; equivalent synchronous generators (ESG); Lyapunov's direct method; transient rotor angle stability; WIND-POWER; REPRESENTATIVE DAYS; ENERGY; TIME; FRAMEWORK; SELECTION; PERIODS; SYSTEMS;
D O I
10.1109/TPWRS.2023.3271025
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Deployment of Synchronous Condensers (SynCons) has become one popular solution in accommodating large-scale renewable energy source (RES) for existing power systems. However, as a rotating device, SynCon may lose transient rotor angle stability caused by injected active power from nearby RES after a fault. To reveal this phenomenon, the transient stability of SynCon is investigated in this article. To derive intuitive mechanism and assist quantitative analysis, the equivalent synchronous generators (ESG) model is proposed to characterize the transient behavior of SynCon and co-located RES. The Lyapunov's direct method is employed for the assessment of transient stability by analyzing attraction domain for a typical benchmark system. On this basis, an index of transient stability margin against grid strength and an adaptive low voltage ride through (LVRT) control strategy are proposed for further assessment and enhancement of transient stability. The accuracy and effectiveness of the proposed methods are verified with EMT simulations of a typical windfarm configuration.
引用
收藏
页码:2030 / 2041
页数:12
相关论文
共 33 条
  • [31] Influence Mechanism Analysis of Phase Locked Loop Out-of-synchronization on Transient Power Angle Stability of Synchronous Generators
    Li X.
    Li J.
    Su C.
    Wang J.
    Liu C.
    Zheng L.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2022, 46 (22): : 101 - 110
  • [32] CO2 Capture Cost Reduction Potential of the Coal-Fired Power Plants under High Penetration of Renewable Power in China
    He, Song
    Zheng, Yawen
    ENERGIES, 2024, 17 (09)
  • [33] A data mining-based method for mining key factors affecting transient voltage stability for power systems with renewable energy sources
    Huang, Dan
    Sun, Huadong
    Zhang, Jian
    Zhao, Shanshan
    Zhou, Qinyong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (04) : 617 - 628